7-1
ELECTRIC
A
L D
A
T
A
S
M PN
X
DCI 1-
A
.1 GB
7.
ELECTRICAL DATA
7.1 Single
Phase
Unit
Model
PNX 25 DCI PNX 35 DCI PNX 50 DCI PNX 60 DCI
PNX 72 DCI
Power
S
upply
1 PH ,220-240V
A
C ,50HZ
Connected to
To indoor
To outdoor
Maximum Current
10
A
13.5
A
15
A
15.7
A
Inrush Current \
(a)
35
A
45
A
<35
A
S
tarting Current\
(b)
10
A
13.5
A
15
A
15.7
A
Circuit Breaker
16
A
20
A
Power
S
upply 3
X
1.5 mm²
3
X
2.5 mm²
Interconnecting cable
4
X
1.5 mm²
4
X
2.5 mm²
(a) Inrush current is the current when power is up (charging the DC capacitors
at outdoor unit controller).
(b)
S
tarting current is the current at compressor start up.
NOTE
Power wiring cord should comply with local lows and electrical
regulations requirements.
CONTENTS
Содержание PNX 12 DCI
Страница 16: ...4 3 OUTLINE DIMENSIONS SM PNXDCI 1 A 1 GB 4 5 Outdoor Unit GC 24 Z DCI CONTENTS...
Страница 108: ...14 4 EXPLODED VIEWS AND SPARE PARTS LISTS SM PNXDCI 1 A 1 GB 14 4 Outdoor Unit GC 9 12 DCI CONTENTS...
Страница 110: ...14 6 EXPLODED VIEWS AND SPARE PARTS LISTS SM PNXDCI 1 A 1 GB 14 6 Indoor Unit PNX 18 21 24 DCI CONTENTS...
Страница 114: ...14 10 EXPLODED VIEWS AND SPARE PARTS LISTS SM PNXDCI 1 A 1 GB 14 10 Outdoor Unit GC 18 DCI CONTENTS...
Страница 116: ...14 12 EXPLODED VIEWS AND SPARE PARTS LISTS SM PNXDCI 1 A 1 GB 14 12 Outdoor Unit GC 21 DCI CONTENTS...
Страница 118: ...14 14 EXPLODED VIEWS AND SPARE PARTS LISTS SM PNXDCI 1 A 1 GB 14 14 Outdoor Unit GC 24 Z DCI CONTENTS...
Страница 121: ...16 1 APPENDIX A SM PNXDCI 1 A 1 GB APPENDIX A INSTALLATION AND OPERATION MANUALS CONTENTS...