12-13
CONTROL SYSTEM
SM PNXDCI 1-A.1 GB
ANY
0
ON
NLOAD
PUMP
OFF
ON
OPER
LED
OFF
Overflow
Water Level
Normal
BLINK
NLOAD is
forced to 0
8 min
8 min
Overflow when
unit is ON
Overflow when
unit is OFF
8 min
12.8
Indoor Unit Dry Contact
Indoor unit Dry contact has two alternative functions that are selected by J9.
Function
Contact=open
Contact=short
J9=open
Presence Detector
Connection
No limit
Force to STBY
J9=short
Power Shedding Function
No limit
Limit NLOAD
12.9
Operating the Unit from Mode Button
Forced operation allows to start, stop and operate in Cooling or Heating, in pre-set
temperature according to the following table:
Forced operation Mode
Pre-set Temperature
Cooling
20°C
Heating
28°C