![Airwell FLO 12 DCI Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/airwell/flo-12-dci/flo-12-dci_service-manual_2880063012.webp)
5-1
PERFORMANCE DATA
SM FLODCI 1-A.1 GB
5. PERFORMANCE
DATA
5.1
FLO 9 DCI
5.1.1
Cooling Capacity (kW) - Run Mode
ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC]
OD COIL
ENTERING AIR DB
TEMPERATURE
[C
0
]
DATA 22/15 24/17 27/19 29/21 32/23
TC
80 - 110 % of nominal
SC
80 - 105 % of nominal
-10 - 20
(protection range)
PI
25 - 50 % of nominal
TC 2.42 2.57 2.73 2.89 3.05
SC 1.64 1.67 1.71 1.74 1.77
25
PI 0.47 0.48 0.49 0.49 0.50
TC 2.30 2.46 2.62 2.77 2.93
SC 1.60 1.63 1.67 1.70 1.73
30
PI 0.52 0.53 0.54 0.55 0.56
TC 2.18 2.34
2.50
2.66 2.82
SC 1.56 1.59
1.63
1.66 1.69
35
PI 0.58 0.59
0.60
0.60 0.61
TC 2.07 2.23 2.38 2.54 2.70
SC 1.52 1.55 1.58 1.62 1.65
40
PI 0.63 0.64 0.65 0.66 0.67
TC 1.93 2.09 2.24 2.40 2.56
SC 1.47 1.50 1.53 1.57 1.60
46
PI 0.70 0.71 0.72 0.72 0.73
LEGEND
TC – Total Cooling Capacity, kW
SC – Sensible Capacity, kW
PI – Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C)
ID – Indoor
OU - Outdoor
5.1.2 Capacity
Correction
Factors
0.5
0.6
0.7
0.8
0.9
1
1.1
1.2
20
25
30
35
40
45
Outdoor Temperature [deg C]
Ca
p
a
c
ity
Ra
ti
o