1.3. EQUIPMENT SAFETY DATA

Safety Data

R407C

Toxicity

Low

In contact with skin

Liquid splashes or sprays may cause freeze burns. Unlikely to be hazardous by skin absorption. 
However, R407C may be slightly irritant and, if liquid, it has a strong degreasing effect. Flush contaminated skin 
areas with running water. If it comes into contact with fabrics, the liquid refrigerant will cause them to freeze and 
adhere to the skin. Carefully remove the contaminated clothing since it might adhere to the skin and cause freeze 
burns. Contact a doctor if the affected skin areas are reddened or irritated.

In contact with eyes

Vapours have no effect. Liquid splashes or sprays may cause freeze burns. In these cases rinse your eyes with 
running water or with a solution for eye lavages for at least 10 minutes. Immediately contact a doctor.

Ingestion

Very unlikely to occur. If this should be the case, it may cause freeze burns. Never induce vomiting. 
keep the patient awake. Make him rinse his mouth with running water and make him drink about 1/4 of a litre. 
Immediately contact a doctor.

Inhalation

R407C: High concentration levels of its vapours in the air can produce an anaesthetic effect, including the loss of 
consciousness. Particularly severe exposures may cause heart arrhythmia and sometimes prove to be also fatal.

At high concentrations there is a danger of asphyxia due to a reduced oxygen content in the atmosphere. In these 
cases take the patient to the open air, in a cool place and keep him at rest. Administer oxygen, if required. Apply 
artificial respiration if breathing has ceased or if it has become irregular. In case of heart failure immediately apply 
cardiac massage. Immediately contact a doctor.

Further Medical Advice A symptomatic and supportive therapy is generally suitable. A heart sensitisation has been observed in some cases, 

as a result of exposures to particularly high concentrations. In the presence of catecholamines (such as for example 
adrenaline) in the blood flow, it has increased the irregularity of the cardiac rhythm and then caused the heart fai-
lure.

Long-term exposure

R407C: A lifetime study which has been conducted on the effects inhalation may have on rats at 50,000 ppm has 
shown the onset of benign tumours of the testicle. These remarks suggest that there is no danger for human beings 
if they are exposed to concentrations below the occupational limits or equal to them.

Occupational exposure 
limits

R407C: Recommended limits: 1,000 ppm v/v 
8 hours TWA.

Stability

R407C: Not specified.

Conditions to avoid

Use in the presence of exposed flames, red heat surfaces and high humidity levels.

Hazardous reactions

Possibility of violent reactions with sodium, potassium, barium and other alkaline substances. 
Incompatible materials: magnesium and all the alloys containing over 2% of magnesium.

Hazardous decomposi-
tion products

R407 C: Halogen acids deriving from thermal decomposition and hydrolysis.

General precautions

Avoid the inhalation of high concentrations of vapours. The concentration in the atmosphere shall be kept at the 
minimum value and anyway below the occupational limits. Since vapours are heavier than air and they tend to sta-
gnate and to build up in closed areas, any opening for ventilation shall be made at the lowest level.

Breathing protection

In case of doubt about the actual concentration, wear breathing apparatus. It should be self-contained and appro-
ved by the bodies for safety protection.

Storage Preservation

Refrigerant containers shall be stored in a cool place, away from fire risk, direct sunlight and all heat sources, such 
as radiators. The maximum temperature shall never exceed 45°C in the storage place.

Protection clothes

Wear boots, safety gloves and glasses or masks for facial protection.

Behaviour in case of 
leaks or escapes

Never forget to wear protection clothes and breathing apparatus. Isolate the source of the leakage, provided that 
this operation may be performed in safety conditions. Any small quantity of refrigerant which may have escaped 
in its liquid state may evaporate provided that the room is well ventilated.In case of a large leakage, ventilate the 
room immediately. Stop the leakage with sand, earth or any suitable absorbing material. Prevent the liquid refrige-
rant from flowing into drains, sewers, foundations or absorbing wells since its vapours may create an asphyxiating 
atmosphere.

Disposal

The best procedure involves recovery and recycle. If this is not possible, the refrigerant shall be given to a plant 
which is well equipped to destroy and neutralise any acid and toxic by-product which may derive from its disposal.

Combustibility features R407C: Non flammable in the atmosphere.
Containers

If they are exposed to the fire, they shall be constantly cooled down by water sprays. 
Containers may explode if they are overheated.

Behaviour in case of 
fire

In case of fire wear protection clothes and self-contained breathing apparatus.

Содержание CW-AR

Страница 1: ...N WASSERSCHLEIFE POMPA DI CALORE SU CIRCUITO DI ACQUA BOMBA DE CALOR EN CIRCUITO DE AGUA Installation and maintenance manual Manuel d installation et de maintenance Installations und Wartungshandbuch...

Страница 2: ......

Страница 3: ...INSTALLATION INSTRUCTION NOTICE D INSTALLATION INSTALLATIONSHANDBUCH ISTRUZIONI INSTALLAZIONE instRUCCIONES DE INSTALACI N...

Страница 4: ...ELECTRICAL POWER SUPPLY CONNECTION 14 13 RCL AND BMS CONTROL MODULES WIRING 15 13 1 RCL 15 13 2 BMS 17 13 3 APPLIANCE configuration 18 13 4 Return air temperature measurement 19 13 5 POWER FAILURE 19...

Страница 5: ...handled using lifting and handling equipment appropriate to the unit s size and weight Any wiring produced on site must comply with the corresponding national electrical regulations Make sure that the...

Страница 6: ...low the occupational limits or equal to them Occupational exposure limits R407C Recommended limits 1 000 ppm v v 8 hours TWA Stability R407C Not specified Conditions to avoid Use in the presence of ex...

Страница 7: ...C can harm certain plastic materials and cause permanent damage Moreover the performance of certain electrical or electronic components can be impaired The appliances are delivered fully assembled fac...

Страница 8: ...ture limits correspond to the nominal appliance water flow 0 50 100 150 200 250 300 350 400 450 500 550 600 650 Water flow l h 10 Water inlet temperature C 12 14 16 18 20 22 24 26 28 30 32 0 50 100 15...

Страница 9: ...e of 10 is acceptable in relation to the operating voltage marked on the appliance s Maker s Plate Operating voltages 230V 1 ph 50 Hz 207 Volts minimum 253 Volts maximum Comments the stated voltages r...

Страница 10: ...ee space for servicing personnel to perform maintenance and repairs Leave sufficient space for the water and electricity connections 2 The unit must be pitched slightly towards condensate drain outlet...

Страница 11: ...angle bracket to attach the appliance to the wall 9 3 1 CABINET REMOVAL When removing cabinet do not pull or lift it up by the discharge grilles to avoid any damages on articulated fasteners of the ac...

Страница 12: ...st be equipped with removable connectors to facilitate future removal of the unit from its location Main return pipe work Hoses Spherical dome valve Main water supply pipe work Main condensate drainag...

Страница 13: ...its Check the pump inlet pressure gauge and manually adjust the compensating valve to maintain the same pressure before and after the opening of the drain taps Flushing must be performed for at least...

Страница 14: ...z 10 11 2 LEGEND 11 2 1 POWER SUPPLY All the electrical installations and wiring associated with this equipment must comply with local installations regulations 11 2 2 WIRING DIAGRAM KEY DESCRIPTIONS...

Страница 15: ...responding to the unit model Any modification performed without our prior authorisation may result in the unit s warranty being declared null and void The power supply cable section must be sufficient...

Страница 16: ...nection box on the right hand side or on the top of the appliance or on a remote terminal box located on the left hand side of the appliance 1 Open the electrical box 2 Connect the power supply cable...

Страница 17: ...t bracket Present the support bracket to the desired location and align it with a spirit level Mark the screw locations Make a hole or install appropriate plugs according to the material wood concrete...

Страница 18: ...the support bracket Replace the lower screw in such a way that the RCL control is held firmly in place on the support bracket RCL control recommended setting Accessible modes PLUG Dip J1 Dip J2 0 1 0...

Страница 19: ...ne wire with a section of between 0 12 and 0 5 mm for wiring the control modules Refer to the following chapter for detail of the appliances addressing RCL A B 12V GND The use of the BMS recall comman...

Страница 20: ...ON Cool heat by electric heat Jumper Configuration J3 OFF the fan is controlled via the compressor and the ICT sensor in Heating mode ON the fan operates continuously in Heating mode except in OFF mo...

Страница 21: ...imise disruptions caused by power cuts the BMS supervision module is equipped with rechargeable batteries offering 24 hours autonomy After 24 hours the time and date will need to be reprogrammed Howev...

Страница 22: ...nables the BMS supervision module to send the command to all the units at the same time The maximum distance between the RCL and the first unit is 30 metres The maximum distance between the RCL and th...

Страница 23: ...D CARTE STORM 2 A B CW AR 1 1 2 4 3 RS 485 12V GND CARTE STORM 2 A B CW AR 2 1 2 4 3 RS 485 12V GND CARTE STORM 2 A B CW AR 3 100m MAXI RCL 123 CW AR MAXIMUM The use of the BMS recall command is not c...

Страница 24: ...cted to a BMS central supervision unit or a MODBUS system must receive an address according to the procedure below BEFORE STARTING THE ADDRESSING PROCEDURE YOU MUST MAKE SURE THAT THE UNIT IS SWITCHED...

Страница 25: ...FF OFF on on OFF OFF on on dip 3 OFF OFF OFF on on on on OFF OFF OFF OFF on on on on dip 4 OFF OFF OFF OFF OFF OFF OFF on on on on on on on on binary code 0001 0010 0011 0100 0101 0110 0111 1000 1001...

Страница 26: ...rticularly to ensure that the water circulation pump operates correctly Non compliance with this rule may result in irreversible damage to the plate exchanger In addition we recommend the use of a flo...

Страница 27: ...L control modules select HEAT mode and then set the maximum temperature with the UP and DOWN arrows The ambient temperature should be within the operating limits Refer to Operating limits In the same...

Страница 28: ...ng check Start the compressor Check for any unusual noise or vibration 3 Operating Pressures Operate the unit for at last 20 minutes and ensure that the refrigerant pressures are stabilised and cheek...

Страница 29: ...al and shall contain all necessary information concerning the problem encountered The return of the part is not an order for replacement Therefore a purchase order must be entered through your nearest...

Страница 30: ...aged or altered in such a way as to affect the insulation The contact surfaces of relays and contactors should be inspected regularly by an electrician and replaced as judged necessary On these occasi...

Страница 31: ...ring the first year of operation in order to determine the frequency required If it is not possible to see light through the filter when it is held up to the sun or in front of a strong light the filt...

Страница 32: ...ompressors do not generate any abnormal noises or vibrations 4 Check the compressor discharge temperature 5 Check that the crankcase heater is energised during the OFF cycle INDOOR COILS 1 Clean the f...

Страница 33: ...e compressor 5 The internal compressor circuit is open circuit perform a continuity test with an Ohmmeter If the circuit is open circuit replace the compressor 19 1 3 INSUFFICIENT COOLING OR HEATING P...

Страница 34: ...surface Reposition slightly as required 5 Check that all the attachment screws are tightened properly 6 Check that air is not being sucked into the hydraulic system 7 Test that the relays open and clo...

Страница 35: ...high above 50 C Test the water temperature at the level of the main loop Cut the mains power supply for 5 seconds and then reconnect Insufficient water flow or no water flow at the level of the applia...

Страница 36: ...ection of the LP pressostat and or conduct a continuity test Refrigerant leak Find and repair any leaks on the pipe circuits Water inlet valve closed Test the valve electrical supply Test the directio...

Страница 37: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO...

Страница 38: ...GRAM VII dimensions III CW AR CAR III CW AR NU IV CW AR CARB V CW AR NUB VI SCHEMAS ELECTRIQUES VII abmessungen III CW AR CAR III CW AR NU IV CW AR CARB V CW AR NUB VI STROMLAUFPLANS VII dimensioni II...

Страница 39: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO III dimensions dimensions abmessungen dimensioni dimensiones 1138 105 716 251 1138 716 720 mini 750 maxi 251 CW AR CAR...

Страница 40: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO IV 1005 40 5 522 105 142 5 40 50 229 624 769 530 54 92 24 1005 502 525 mini 555 maxi 142 50 38 50 229 530 54 92 24 CW AR NU...

Страница 41: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO V 1323 578 105 683 251 1323 580 mini 610 maxi 251 CW AR CARB...

Страница 42: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO VI 1005 40 5 1183 139 522 105 229 624 530 100 18 54 1005 502 525 mini 555 maxi 138 50 1144 38 50 229 530 100 18 54 CW AR NUB...

Страница 43: ...ferten Stromlaufplan hinzuziehen ATTENZIONE Questi schemi sono corretti al momento della pubblicazione Le varianti apportate nel corso della fabbricazione possono comportare modifiche Far sempre rifer...

Страница 44: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO VIII SE 4273 N786 3991288 CWAR 7 9 12 BMS WIRING DIAGRAM...

Страница 45: ......

Страница 46: ...ur oder Ihre Stadt oder Gemeindeverwaltung um einen Entsorgungsbetrieb in Ihrer N he ausfindig zu machen Eine M glichkeit besteht darin das Ger t kostenlos bei Ihrem H ndler oder Installateur abzugebe...

Страница 47: ...108 CEE DIRECTIVA DE LOS EQUIPOS A PRESION DESP 97 23 CEE BAJA MODULO A CATEGORIA I D claration CE de conformit Nous d clarons sous notre responsabilit que les produits d sign s dans la pr sente noti...

Страница 48: ...rherige Ank ndigung ge ndert werden Fotos nicht vertraglich bindend A causa della politica di continua miglioria posta in atto dal costruttore questi prodotti sono soggetti a modifiche senza alcun obb...

Отзывы: