Preparations and Precautions

Air and foreign matter in the refrigerant circuit can 

cause abnormal rises in pressure, which can damage 

the air conditioner, reduce its efficiency, and cause

injury. Use a vacuum pump and manifold gauge to 

evacuate the refrigerant circuit, removing any 

non-condensable gas and moisture from the system.      

Evacuation should be performed upon initial 

installation and when unit is relocated. 

BEFORE PERFORMING EVACUATION

  

Check to make sure the connective pipes

between the indoor and outdoor units

are connected properly .

  

Check to make sure all wiring is connected

properly.

Evacuation Instructions

Manifold Gauge

Compound 

gauge

-76cmHg

Low pressure 

valve

High pressure

valve

Pressure hose / 

Charge hose

Charge hose

V

acuum

pump

Pressure gauge

Low pressure valve

 1.

Connect the charge hose of the manifold

gauge to service port on the outdoor unit’s

low pressure valve.

Connect another charge hose from the

manifold gauge to the vacuum pump.

Open the Low Pressure side of the manifold

gauge. Keep the High Pressure side closed.

Turn on the vacuum pump to evacuate the

system.

5.

Run the vacuum for at least 15 minutes, or

until the Compound Meter reads -76cmHG

(-10

5

Pa).    

 2.

3.

 4.

Flare nut

Cap

valve body

valve stem

6.

Close the Low Pressure side of the manifold

gauge, and turn off the vacuum pump.

7.

Wait for 5 minutes, then check that there

has been no change in system pressure.

8.

If there is a change in system pressure, refer

to Gas Leak Check section for information

on how to check for leaks. If there is no

change in system pressure, unscrew the cap

9.

from the packed valve (high pressure valve).

Insert hexagonal wrench into the packed valve

(high pressure valve) and open the valve by

turning the wrench in a 1/4 counterclockwise

turn. Listen for gas to exit the system, then

close the valve after 5 seconds.

10.

Watch the Pressure Gauge for one minute

to make sure that there is no change in

pressure. The Pressure Gauge should read

slightly higher than atmospheric pressure.

11.

Remove the charge hose from the service port.

12.

Using hexagonal wrench, fully open both the

high pressure and low pressure valves.

13.

Tighten valve caps on all three valves (service

port, high pressure, low pressure) by hand.

You may tighten it further using a torque

wrench if needed.

OPEN VALVE STEMS GENTLY

When opening valve stems, turn the hexagonal 

wrench until it hits against the stopper. Do not 

try to force the valve to open further.

Air Evacuation

Air Evacuation

Содержание CDM Cassette AW-YDFA012-H91

Страница 1: ...d this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference Installation Manual CDM Cassette R32 R410A 20 AW CDM 12 48 R32...

Страница 2: ......

Страница 3: ...tdoor Uint Wiring 23 2 Indoor Uint Wiring 24 Anchor outdoor unit 17 3 Refrigerant Piping Connection 18 Note on Pipe Length 18 A B Connection Instructions Refrigerant Piping 19 1 Cut pipe 19 2 Remove b...

Страница 4: ...like a burning smell immediately turn off the unit and disconnect the power Call your dealer for instructions to avoid electric shock fire or injury Do not insert fingers rods or other objects into th...

Страница 5: ...unit Do not share the electrical outlet with other appliances Improper or insufficient power supply can cause fire or electrical shock If connecting power to fixed wiring an all pole disconnection dev...

Страница 6: ...cians for disconnection and reinstallation of the unit How to install the appliance to its support please read the information for details in indoor unit installation and outdoor unit installation sec...

Страница 7: ...appliance contains refrigerant and other potentially hazardous materials When disposing of this appliance the law requires special collection and treatment Do not dispose of this product as household...

Страница 8: ...6 35 1 4i n 9 52 3 8in 12 7 1 2in 9 52 3 8in 12 7 1 2in 16 5 8in 19 3 4in 22 7 8in 2 4 1 Name of Accessories Q ty pc Shape 1 1 1 1 1 Name of Accessories Q ty pc Shape Soundproof insulation sheath 1 S...

Страница 9: ...the outdoor unit Install the drainpipe L N 1 2 3 4 5 MC MC 6 Install the indoor unit Evacuate the refrigeration system Connect the wires Connect the refrigerant pipes Perform a test run 7 8 Install t...

Страница 10: ...al shape shall prevail NOTE The installation must be performed in accordance with the requirement of local and national standards The installation may be slightly different in different areas Page 10...

Страница 11: ...exists for installation and maintenance Enough room exists for the connecting the pipe and drainpipe The ceiling is horizontal and its structure can sustain the weight of the indoor unit The air inle...

Страница 12: ...1m 39 on all sides The cut hole size should be 4cm 1 6 larger than the boby size Be sure to mark the areas where ceiling hook holes will be drilled 24k 48K Slim models ceiling hole size Refrigerant p...

Страница 13: ...asten them using the included washers and nuts NOTE The bottom of the unit should be 10 18mm 0 4 0 7 Slim models or 24mm 0 9 Compact models higher than the ceiling board Generally L indicated in the f...

Страница 14: ...ke sure that the hooks do not come loose due to concrete shrinkage After installing the indoor unit fasten the installation paper template onto the unit with bolts to determine in advance the dimensio...

Страница 15: ...azard NOTE The drainpipe outlet should be at least 5cm 1 9 above the ground If it touches the ground the unit may become blocked and malfunction If you discharge the water directly into a sewer make s...

Страница 16: ...ir outlet fan is at a 90 angle to the direction of the wind If needed build a barrier in front of the unit to protect it from extremely heavy winds See Figures below Strong wind Strong wind Strong win...

Страница 17: ...following 1 Insert the drain joint into the hole in the base pan of the unit The drain joint will click in place 2 Connect a drain hose extension not included to the drain joint to redirect water from...

Страница 18: ...The Maximum Length And Drop Height Based on Models Unit m ft L H 300 cm 118 or more A 60 cm 23 6 or more 150 cm 59 or more 25 cm 9 8 or more 25 cm 9 8 or more Rows of series installation L H L 1 2H L...

Страница 19: ...ompressor should be maintained with suction gas velocity If velocities drop below7 62m s 1500fpm feet per minute oil return will be decreased An oil trap should be installed every 6m 20ft of vertical...

Страница 20: ...the pipe at a downward angle to prevent burrs from falling into the pipe 2 Using a reamer or deburring tool remove all burrs from the cut section of the pipe Pipe Reamer Point down 6 Place flaring to...

Страница 21: ...al cable with any other wiring 7 Thread this pipeline through the wall and connect it to the outdoor unit 8 Insulate all the piping including the valves of the outdoor unit 9 Open the stop valves of t...

Страница 22: ...qualified technician must use an approved circuit breaker or switch 14 The unit must be connected to the main outlet Normally the power supply must have a impedance of 32 ohms 15 No other equipment s...

Страница 23: ...e to reveal approximately 15cm 5 9 of wire c Strip the insulation from the ends d NOTE The cographs are for explanation purpose only Your machine may be slightly different The actual shape shall preva...

Страница 24: ...7 Clamp field supply Magnetic ring if supplied and packed with the accessories 1 2 3 Pass the belt through the hole of the Magnetic ring to fix it on the cable Slim models Wire outlet Control box Con...

Страница 25: ...lectric box cover VOLT VOLT VOLT VOLT MODEL Btu h 12K 18K 24K 36K POWER indoor PHASE 1 Phase 1 Phase 220 240V 220 240V CIRCUIT BREAKER FUSE A 15 10 15 10 POWER outdoor PHASE 1 Phase 1 Phase 1 Phase 1...

Страница 26: ...east 15 minutes or until the Compound Meter reads 76cmHG 105 Pa 2 3 4 Flare nut Cap valve body valve stem 6 Close the Low Pressure side of the manifold gauge and turn off the vacuum pump 7 Wait for 5...

Страница 27: ...oor unit Total pipe length standard pipe length x15g 0 16oZ m ft Total pipe length standard pipe length x30g 0 32oZ m ft R32 orifice tube in the outdoor unit Total pipe length standard pipe length x 1...

Страница 28: ...nge between the main body and the panel reduces to 4 6mm 0 2 0 3 The edge of the panel should be in contact with the ceiling well Adjust the panel by turning it to the arrowed direction so that the ce...

Страница 29: ...t from the main body Step 2 Install the panel Align the indicate on the decoration panel to the indicate on the unit Attach the decoration panel to the unit with the supplied screws as shown in figure...

Страница 30: ...gistered correctly d Ensure the indicators on the remote control and the display panel on the indoor unit work properly e Ensure the manual buttons on the indoor unit works properly f Check to see tha...

Страница 31: ...Page 31...

Страница 32: ...sult with the sales agency or manufacturer for details ATTENTION Le design et les donn es techniques sont donn s titre indicatif et peuvent tre modifi s sans pr avis AIRWELL RESIDENTIAL SAS 10 rue du...

Отзывы: