ADDITIONAL OPTIONS FOR 4-6HP (10-14kW) DCI UNITS ONLY

1.  FEATURES SETUP 

1.1. DISPLAY BOARD GENERAL DESCRIPTION 

The display board serves as interface between the installer/technician and the 

A/C unit. 

Buttons description:

Up & Down - used to scroll between options (up and down)

Select - used to select an option 

Escape - Will go up one level in the menu

1.2. SET-UP 

There are 2 types of current limitation for the maximum current drawn by the outdoor unit, one is to set maximum limit to the 
current and the other is to set power shedding limit. For both actions follow the below described procedure. 

Mode (Cl/Ht/Sb) 

Technician Test (tt)   

Technician Test Cool (ttC)  

Technician Test Heat (ttH)

Diagnostics (dIa)   

Outdoor Unit (Odu)  

Indoor Unit (Idu)     

Set Up (Set)

-

Indoor Unit Supply (IdSU)

-

Max Current Limit (CurL) 

Up

Down

Esc

Select 

1. Scroll down the “Down” button until setup is displayed

(Set) and than press the “Select” button. 

2. Scroll down the “Down” button to choose the option 

required and press the “Select” button. 

-

Power Shedding (PSC)

1.2.1   Maximum Current Limit

The maximum operating current of the unit can be selected by the table in order to reduce/increase the circuit braker value.
This operation will affect the maximum capacity of the unit. 
The defualt values are: indoor unit supplied from outdoor unit (“OUT”) and the current is 30A for 12.5kW unit and 25A for
10.0 kW unit. 

Display

Max. Current 

setting

Circuit braker

30_A 

30A 

32A

27_A

27A 

30A/32A

23_A

23A

25A

18_A 

18A

20A

Enter the Set Up menu by Scrolling down to “Set” and set the indoor 
unit supply (IdSU) parameter to either “Out” for external power supply 
for Indoor unit (via Outdoor unit) or “In” for suppling the indoor unit from
seperate internal circuit braker. 
Escape one time and scroll to “CURL”.
Enter the value corresponding the max current as per the table.

14_A 

14A 

16A

1.2.2  Power Shedding Current Limit 

The maximum operating current of the unit can be limited by setting the unit into power shedding mode which will control the 
unit up to pre-defined current percentage (out the max current). This operation will reduce the maximum capacity of the unit.

Up

Down

Esc

Select

1. Scroll

Down

2. Select

12

Содержание CD DCI Series

Страница 1: ...CENTRAL AIR CONDITIONER WITH ELECTRONIC CONTROL SPLIT SYSTEM SERIES CD DCI INSTALLATION INSTRUCTION...

Страница 2: ...on the terminal If connection or xing is not perfect it will cause heat up or re at the connection 5 Wire routing must be properly arranged so that control board cover is xed properly If control boar...

Страница 3: ...Therefore during installation work be sure that water dust former refrigerant or refrigeration machine oil does not enter into the new type refrigerant R410A air conditioner circuit To prevent mixing...

Страница 4: ...4 3 8 5 8 3 8 5 8 3 8 3 4 NOMINAL CAPACITY TUBES O D LENGTH A HEIGHT B 25 70 25 7 0kW 37 80 37 8 0kW 37 90 37 10 0kW 50 100 50 14 0kW MIN MAX NOMINAL NOMINAL CAPACITY A B The indoor unit can be insta...

Страница 5: ...er tube for draining c Install a draining siphon close to the unit see figure RU DVVXULQJ D FRUUHFW RSHUDWLRQ RI WKH GUDLQLQJ V VWHP SD DWWHQWLRQ WR WKH IROORZLQJ SRLQWV D UDLQLQJ WXEHV VKRXOG EH VODQ...

Страница 6: ...ension brackets c Position the shock absorbers add washers and scr ew the nuts until the unit is firmly supported d In case of a gap between the unit and the ceiliing put a rubber or a neoprene sheet...

Страница 7: ...intake side t n o r F o t t n o r F k c a B o t k c a B n o i t a l l a t s n I w o R Front to Back OUTDOOR UNIT SEVERAL OUTDOORS INSTALATION When installing several outdoors units please take into ac...

Страница 8: ...2 Use the torque wranch to tighten the valves firmely according to table EVACUATION OF PIPES AND INDOOR UNIT 1 Connect the charging hoses with a push pin to the low and high sides of the charging set...

Страница 9: ...ical requirements 1PH Units Power upply to outdoor and indoor units 1PH Units Power upply to outdoor unit 1 Indoor Unit 2 Power Supplay Cable 3 Main Power Breaker 4 Outdoor Unit 5 Interconnecting Cabl...

Страница 10: ...he termostat kit is a factory option no need to perform this action 4 Connect the other end of the cable to the the indoor unit main controller using the RM extension cable 5 Connect the grounding for...

Страница 11: ...ol Unit Connect the quick connector to the appropriate socket on the main control board in the indoor unit electrical box DISPLAY CONTROL UNIT WARNING The plug should not be cut off the communication...

Страница 12: ...he Select button Power Shedding PSC 1 2 1 Maximum Current Limit The maximum operating current of the unit can be selected by the table in order to reduce increase the circuit braker value This operati...

Страница 13: ...nclude a switch or a relay should be used for closing the internal circuit to indicate that some change is required A wire of up to 1 5mm2 is recommended to be used Note NO external power should be us...

Страница 14: ...o be used 1 5 ACCESSORIES SET UP 1 5 1 BASE HEATER BH Base Heater is an heating element designed to melt any ice that is accumulated on the outdoor unit base during heating operation The unit will aut...

Страница 15: ...ped firmly Is the drainage OK Refer to Check the drainage section Is the earth wire connection properly done CHECK ITEMS CARE AND MAINTENANCE Caution Before any maintenance operation the unit should b...

Страница 16: ...5 7 5 66 7XUQ RII WZR VFUHZV DQG UHOHDVH D DLU ILOWHU VXSSRUW 3XOO GRZQ WKH DLU ILOWHU IRU IXUWKHU WUHDWPHQW Caution The Air Conditioner should not be activated without air filters mounted in place 16...

Отзывы: