12.14
Temperature compensation
All the indoor units which PCB is 0151800113, 0151800161, 0151800161B, 0151800141, 0151800141A,
0010451751AE or 0010451751AF use the default value which in the EEPROM (in heating mode, the temperature
compensation value is 3°C, it means when the indoor temperature sensor detect the temperature more than target
temperature 3°C the fan of the indoor unit will stop; in cooling mode, the temperature compensation value is 0°C), it
can be changed by controller.
Controller setting method:
1. Setting by remote controller (RCV01)
For the unit which controlled by remote controller, the temperature compensation dip switch is unavailable, It can be
changed by remote controller, and the operation as bellow:
(1) In heating/cooling mode: press the "ON/OFF" to start up.
(2) Set the standard temperature 28°C, press the "SLEEP" button 7 times in 5s, after 2 times buzzer enter to the
heating/cooling temperature compensation setting mode.
(3) By adjusting the temperature value to set temperature compensation value.
For example: adjust the temperature to 25°C, the temperature compensation value is 3°C; adjust the temperature
to 29°C, the temperature compensation value is -1°C. And so on, you can set the temperature compensation valve
that you need.
The temperature compensation range is 12°C~-2°C.
(4) Power off the unit, the temperature compensation set successfully.
Adjusting the setting temperature to 28°C will cancel temperature compensation setting.
2. Setting by wired controller (RWV05, RWV04, RWV01)
For the indoor unit which controlled by wired controller, first you need select the indoor temperature sensor position
by wired controller dip switch.
When the selected sensor in wired controller, the indoor temperature compensation value will be set by wired
controller (RWV01 is unavailable, RWV04 and RWV05 is available, the detailed operation please refer to the
appendix)
When the selected sensor in indoor unit, the temperature compensation be set by indoor dip switch. But for
0151800161(used for slim duct indoor units) and 0151800161B (will used for two-way cassette indoor unit) PCB,
there are no temperature compensation dip switch, so the compensation value will be set by remote controller.