Airwell AWSI-DCV048-N11 Скачать руководство пользователя страница 35

33

Before Test Run

Fault Remedies

When any fault appears, refer to

Inquiry of fault records of indoor units

at the previous page, consult

the fault code of line control or the flashing times for LED5 of computer panel of indoor units/health
lamp of receiving window of remote control and find out the faults as shown in the following table
to remove all faults.
Indoor Unit Faults

Checkup of Installation

check if the mains voltage is matching
check if there is air leakage at the piping
joints
check if the connections of mains power
and indoor & outdoor units are correct
check if the serial numbers of terminals are
matching

Before switching it on, test the supply terminal tier (L, N terminals) and grounding points with 500V
megaohm meter and check if the resistance is above 1

M

"

. It can

t be operated if it is below 1

M

"

.

Connect it to the power supply of outdoor units to energize the heating belt of the compressor. To
protect the compressor at startup, power it on 12 hours prior to the operation.

Check if the arrangements of the drainpipe and connection line are correct.

The drainpipe shall be placed at the lower part while the connection line placed at the upper part.
Heat preservation measures should be taken such as winding the drainpipe esp. in the indoor units
with heating insulating materials.
The drain pipe should be made a slope type to avoid protruding at the upper part and concaving at
the lower part on the way.

check if the installation place meets the requirement

check if the water is drained to the outside

check if there is too much noise
check if the connecting line is fastened
check if the connectors for tubing are heat insulated

check if the indoor units are positioned

Ways of Test Run

Do ask the installation personnel to make a test run. Take he testing procedures according to the
manual and check if the temperature regulator works properly.
When the machine fails to start due to the room temperature, the following procedures can be taken
to do the compulsive running. The function is not provided for the type with remote control.

Set the wired controller to refrigerating/heating mode, press

ON/OFF

 button for 5 seconds to enter

into the compulsive refrigerating/heating mode. Repress

ON/OFF

button to quit the compulsive

running and stop the operation of the air conditioner.

Test Run & Fault Code

Wired

Controller Fault

Code

PCB LED5(Indoor

Units)/ Receiving

Window Health Lamp

(Remote Controller)

Fault Descriptions

Fault of indoor unit pipe temp. transducer TC1

Fault of indoor unit pipe temp. transducer TC2

02

2

03

3

Fault of indoor unit dual heat source temp. transducer

04

4

Fault of indoor unit EEPROM

05

5

Fault of communication between indoor & outdoor units

06

6

Fault of communication between indoor unit and wired control

07

7

Fault of indoor unit water drainage

08

8

Fault of duplicate indoor unit address

09

9

Fault of duplicate central control address

0A

10

Corresponding faults of outdoor units

Outdoor Unit Code

20

Fault of indoor unit ambient temp. transducer TA

01

1

Содержание AWSI-DCV048-N11

Страница 1: ...AWSI DCV048 N11 No 0150513923 Indoor Unit Operation Installation Manual Please read this manual carefully before using Keep this operation manual for future reference...

Страница 2: ...DB 15 WB 23 WB 14 WB 26 Operating Range of Air Conditioner User Manual Parts and Functions 1 5 Safety Considerations 6 7 17 Fault Checkup 18 25 Installation Procedures 26 31 Electrical Wiring 32 Funct...

Страница 3: ...1 Parts and Functions indoor unit air outlet port air inlet port flue flue Condensated water pan...

Страница 4: ...ed for inspection service Air change switch It is used to open and close air change function The mode is as follows No display air change automatic air change RECOVERY air change NORMAL Clock timing a...

Страница 5: ...rature setting temperature and unit number Air volume display Display the setting speed Inspection status display Air change display Health function display Unit number display Centralized adress disp...

Страница 6: ...th operation function 5 HEALTH Button 21 FILTER Display When the filter need be cleaned you can press the FILTER button for 3s to up down function 20 TIMER Display 19 TIME Display 28 29 30 31 32 33 34...

Страница 7: ...ler and the receiver should be max 7m and there should be no obstacle between them Do not throw the remote controller to prevent it from being damaged Battery loading Batteries are fitted as follows R...

Страница 8: ...ht cause the dropdown of the machine which may lead to personal injuries The installation should be ensured against typhoons and earthquakes etc The installation unconformable to the requirements will...

Страница 9: ...oximately 2 10 min During defrosting the fan of the indoor unit runs at a low speed or stops while that of the outdoor unit stops running Do not use water heater or like next to the indoor unit and th...

Страница 10: ...wind screen 6 Press ON OFF switch off The light on the line controller is off 2 Choose operation mode Press mode switch to change to AUTO FAN ONLY COOL DRY HEAT Remarks Avoid pressing ON OFF switch fr...

Страница 11: ...d CLOCK flickers and the time displayed is the real time If not in timing the screen displays the real time If in timing the screen displays the timing time If you want to know the real time go to the...

Страница 12: ...d OFF timing are the same the setting is invalid Even in timing condition you may start or close the unit through pressing ON OFF switch Note parts of wired controller explanation 1 The unit starts or...

Страница 13: ...re controller is powered off If the wire controller is powered on the above operations will be invalid 2 Function difference between master wire controller and slave one Master wire controller Slave w...

Страница 14: ...her than temperature setting unit will run intermittently at LOW speed regardless of FAN setting When room temperature is lower than temperature setting unit will only run FAN operation In HEAT mode w...

Страница 15: ...ON OFF button to stop unit 4 Unit stop 3 Adjust fan speed Press FAN button Each press the fan speed changes as follows Air conditioner will run at the selected fan speed When in AUTO mode the unit wil...

Страница 16: ...lt in air conditioner s abnormally running If the louver work abnormally stop unit restart and adjust the louver by remote controller In COOL or DRY mode do not leave the louver in downward position f...

Страница 17: ...s time adjustment buttons If the button is kept pressed the time will changes quickly It can be adjusted within 24 hours at will Hints After replacing batteries or if a power failure occurs TIMER sett...

Страница 18: ...still consume power Air cleaner and shell must be mounted after cleaning Cleaning Air Cleaner Don t rinse the air cleaner with hot water of above to avoid fading and distorting Don t put the air clea...

Страница 19: ...e shutdown indoor units refrigerant flows in the short time and make the sounds of refrigerant flowing Otherwise when other indoor units performs heating operation white steam may occur during refrige...

Страница 20: ...bear the weight of the indoor unit where enough space can be ensured for maintenance The outside air should be input from the outdoor directly from the blast pipe If the blast pipe can t be jointed th...

Страница 21: ...inspection hole the ceiling might be reinforced to keep the evenness of the ceiling and avoid the vibration of the ceiling For details please consult the construction contractor notch grapping notch p...

Страница 22: ...application d b When connecting the drainpipe to the equipment don t apply too much force on one side of the equipment Meanwhile the piping should be positioned as close to the equipment as possible 1...

Страница 23: ...the electrical system test the drainage system b During testing make sure that the water flow passes the piping correctly without any water leakage at the connection c In the condition of new house te...

Страница 24: ...120 B A unit with filter purchased additionally static pressure box 300m3 h 300m3 h 1200m3 h 1200m3 h simple duct selection Note 1Pa m flux item shape square pipe m3 h m3 min 100 200 300 400 500 600 1...

Страница 25: ...uter side of the blast pipe The humidity is high even if the inner side of the suspended ceiling isn t used as a blast pipe in new concrete buildings At this time the whole body should use the thermo...

Страница 26: ...ubing Materials Specifications Refrigerant Filling Amount Connecting Procedures of Refrigerant Tubing Outer Diameter of Tubing mm Mounting Torque 78 4 98 0N m 9 52 32 7 39 9N m 15 88 Dual wrenches mus...

Страница 27: ...indoor and wire controller And be earthed on one side or the unit will not work normally because of interference Note Confirm the terminal connection firmly and do not get in tough with shielded wire...

Страница 28: ...ed to the terminal tier the tubing should be curved into be a U type elbow and fastened with the pressing clip Controller wiring and refrigerant tubing can be arranged and fixed together The machine c...

Страница 29: ...A One line control controls multiple units i e 2 16 indoor units as shown in the above figure 1 5 indoor units The indoor unit 5 is the line controlled main unit and others are the ine controlled sub...

Страница 30: ...well as the wiring between indoor units Note DCV models are set to wired controlled type before delivery Setting Mode Wireless Remote Controller Socket Dip switch SW01 1 2 3 4 CN21 Socket Null Connec...

Страница 31: ...ntrol address the other corresponding address can change automatically meeting as follows Central control address equals to physical address plus 0 or 64 Dip switch setting In the following table 1 is...

Страница 32: ...ff correction valve in AUTO mode SW07_1 SW07_2 Tdiff correction valve in AUTO mode 1 SW07_3 26 lock 4 0 0 1 1 Normally without 26 degree lock function defaulted 26 degree lock function is availble In...

Страница 33: ...Normal mode TES is unavailable default TES is available 1 0 1 0 1 1 0 0 1 0 1 Run at Mid speed when Hi Speed is selected Quiet running mode Indoor and outdoor 90 meters drop selection Reserved Indoor...

Страница 34: ...15 seconds it will automatically quit and keep the last setting Inquiry of fault records of indoor units In the state of startup or shutdown press CHECK button to go into the mode of inquiring faults...

Страница 35: ...lower part on the way check if the installation place meets the requirement check if the water is drained to the outside check if there is too much noise check if the connecting line is fastened check...

Страница 36: ...ronic waste can be disposed of ate least free of charge to the user b When buying a new product the retailer will take back the old product at least free of charge c The manufacturer will take back th...

Страница 37: ......

Отзывы: