TROUBLESHOOTING
Malfunction
2
x
7
Seg
men
ts
IDU LEDs
Possible causes / Actions
System High Pressure
Protection
E1
OPER Indicator OFF 3s and blink once
1. Refrigerant was superabundant
2. Poor heat exchange
(including filter blockage of heat
exchanger and bad
radiating environment)
3.Ambient temperature is too high.
Indoor Coil Defrost
Protection
E2
OPER Indicator OFF 3S and blink twice
1. Poor air-return in indoor unit
2. Fan speed is abnormal
3. Evaporator is dirty.
System block or
refrigerant leakage
E3
OPER Indicator OFF 3S and blink 3 times
1.Low-pressure protection
2.Low-pressure protection of system
3.Low-pressure protection of
compressor
Compressor over Heating
Protection
E4
OPER Indicator OFF 3S and blink 4 times
1. EEV connection problem or
damage
2. Refrigerant leakage
3. Poor heat exchange
AC Over Current
E5
OPER Indicator OFF 3S and blink 5 times
1. Supply voltage is unstable
2. Supply voltage is too low and
load is too high
3. Evaporator is dirty.
Communication
Malfunction
E6
OPER Indicator OFF 3 Sand blink 6 times
1. Wiring mistakes
2. IDU or ODU PCB problem
Indoor/Outdoor Coil Over
Heating Protection
E8
OPER Indicator OFF 3S and blink 8 times
1. Too high ambient temperature
2. Poor heat exchange (including
blockage and bad radiating
environment )
EEPROM problem
EE
HEAT Indicator OFF 3Sand blink15
times
Outdoor main board damaged
Stop rise/HZ down due to
HST over heating
protection
EU
1. Insufficient grease on heatsink or
poor connection of heatsink to PCB
2. Outdoor PCB problem.
Jumper Cap Malfunction
C5
OPER Indicator OFF 3S and blink 15 times
1. No jumper cap insert on main
board.
2. Incorrect insert of jumper cap.
3. Jumper cap damaged.
4. Abnormal detecting circuit of
main board.
Gathering refrigerant
F0
Normal function
RAT Failure
F1
COOL Indicator OFF 3S and blink once
1. Sensor connection is not good
2. Indoor ambient temp. sensor
damaged.(check with sensor
resistance
value chart)
3. Main board damaged.
ICT Failure
F2
COOL Indicator OFF 3S and blink twice
OAT Failure
F3
COOL Indicator OFF 3Sand blink3 times
OCT Failure
F4
COOL Indicator OFF 3Sand blink4 times
CTT Failure
F5
COOL Indicator OFF 3S and blink 5
times
HZ down due to overload
F6
COOL Indicator OFF 3S and blink for 6 times
1. Too high ambient temperature
2. Poor heat exchange (including
blockage and bad radiating
environment )
Hz down due to over
current
F8
COOL Indicator OFF 3S and blink 8 times
1.The input supply voltage is too low
2.System pressure is too
high and overload
Hz down due to CTT over
heating
F9
COOL Indicator OFF 3S and blink 9 times
1.Overload or temperature is too
high;
2.Refrigerant is insufficient
3.Malfunction of electric expansion
valve
(EEV)
Stop rise/HZ down due to
IDU defrosting protection
FH
1. Poor air-return in indoor unit
2. Fan speed is abnormal
3. Evaporator is dirty.
13-2
SM HDDE 1-A.1 GB
13.1.3
Judgment by Indoor/Outdoor Unit Diagnostics
If the malfunction still exists 4min later after stop of unit due to compressor protection, error code will be
directly displayed though indoor display. In other situations, error code can be displayed by pressing
LIGHT button 6 times within 4s.
Содержание AWAU-YDDE009-H11
Страница 14: ...OUTLINE DIMENSION SM HDDE 1 A 1 GB 4 2 4 2 Outdoor YDDE009 4 3 Outdoor YDDE012...
Страница 15: ...4 3 SM HDDE 1 A 1 GB SOUND LEVEL CHARACTERISTICS 4 4 Outdoor YDDE018 4 5 Outdoor YDDE024...
Страница 16: ...PERFORMANCE DATA SM HDDE 1 A 1 GB 5 1 5 PERFORMANCE DATA...
Страница 17: ...SOUND LEVEL CHARACTERISTICS SM HDDE 1 A 1 GB 6 1 6 PRESSURE CURVES...
Страница 18: ...SOUND LEVEL CHARACTERISTICS SM HDDE 1 A 1 GB 7 1 7 SOUND LEVEL CHARACTERISTICS 7 1 Sound Pressure Level...
Страница 19: ...SOUND LEVEL CHARACTERISTICS HDDE 1 A 1 GB 7 2 7 2 Sound Pressure Level Spectrum Measured as Figure 1...
Страница 21: ...SM HDDE 1 A 1 GB 9 1 WIRING DIAGRAM 9 WIRING DIAGRAM 9 1 HDDE009 HDDE012 9 2 HDDE018...
Страница 22: ...WIRING DIAGRAM SM HDDE 1 A 1 GB 9 2 9 3 HDDE024 9 4 YDDE009...
Страница 23: ...9 3 SM HDDE 1 A 1 GB WIRING DIAGRAM 9 5 YDDE012 9 6 YDDE018 YDDE024...
Страница 40: ...12 15 SM HDDE 1 A 1 GB 12 14 Test Mode TO BE CONFIRMED...
Страница 47: ...14 2 SM HDDE 1 A 1 GB CHARACTERISTICS OF SENSOR 14 1 3 CTT CTT R T Chart...
Страница 51: ...EXPLODED VIEW SPARE PART LIST 15 4 SM HDDE 1 A 1 GB 15 4 Exploded view of indoor unit HDDE018...
Страница 55: ...EXPLODED VIEW SPARE PART LIST 15 8 SM HDDE 1 A 1 GB 15 8 Exploded view of outdoor unit YDDE009 YDDE012...
Страница 58: ...SM HDDE 1 A 1 GB 15 11 SERVICING 15 11 Exploded view of outdoor unit YDDE018...
Страница 60: ...SM HDDE 1 A 1 GB 15 13 SERVICING 15 13 Exploded view of outdoor unit YDDE024...
Страница 63: ...SM HDDE 1 A 1 GB a APENDIX APPENDIX...
Страница 64: ...SM HDDE 1 A 1 GB 15 15 SERVICE MANUAL HDDE009 012 018 024...