4.4. LIMItING FoR UNDERFLooR HEAtING APPLICAtIoNS
the temperature calculated by the above heat curve is limited according to the outdoor air temperature to prevent
the compressor working outside acceptable operating conditions.
a separate limiting parameter (h12) is used only when the unit is configured (h09=1) for underfloor heating. the
default value is 45°c maximum.
Outdoor temp (H14)
Proportional band (H15)
Max correction (H16)
OAT
Radiator or Underfloor
Heating
Correction coefficient
(S10)
Room setpoint
Room temperature
Correction coefficient
(S12)
Room setpoint
Room temperature
Max value (H31)
OAT Outdoor air temp
Limitation coefficients
(S08) (S09)
Water Curve
Room setpoint base point = 20°C.
For each degree of setpoint
change the water setpoint is
corrected by 2K for underfloor
and 3K for radiators.
Room temperature
setpoint change
PI calcultain
Correction min -10°C max +10°C
Automatic Correction
Maximum value depending on OAT
OAT Limitation
WATER SETPOINT
AFTER CORRECTION
HER
Maximum water temperature
for underfloor heating
Max floor temperature
HEA