24
6.1 Electronic Card Control
Keyboard
Display
Meaning
Min value
Max value
Step
Default value
410A
1.
OPEr
Cooling/Heating mode selection
COOL
HEAt
---
COOL
2.
CSP
Cooling Setpoint
CSPL
23
0.5
12
3.
HSP
Heating setpoint
20
47
1
40
4.
wtc
Control Mode Operation
ewt
lwt
---
Ewt
5.
nB
Neutral Band valid in LWT control
1
6
0.5
2
OPEr : parameter used to select operative mode between Cool and Heat. Active only if unit is heatpump.
Other parameters to be used only by authorized technician.
SM1 Switch
6 - AQL/AQH Control
SM1 switch :
– Position
0
: machine OFF. The electrical heaters and pump may
be enabled.
– Position
1
: machine ON.
button :
makes it possible to horizontally scroll through the MENUS and to
display the parameter values.
button :
makes it possible to vertically scroll through the MENUS and SUB-
MENUS and to increase the numerical value of the parameters.
Test switch (internal)
Starts an automatic testing procedure for all the main functions of
the unit.
Two levels of menu are used, standard and factory. The factory level
requires a 3 digit code for access.
At any time the standard parameter level menu can be entered by
pressing simultaneously the test button and both display buttons for
5s.
In either parameter level menu if no button is pressed for 10s the
display reverts back to normal mode.
The parameters are scrolled using the
button and selected
using the
button.
When selected the values can be changed by using the
button
to scroll from the present value to max then min and can be selected
by pushing the
button. After selection the menu will return to
the beginning of the same parameter level menu.