                                AIRZONE UNO – INSTALLATION MANUAL 

 

Blue Cable:

 To clamp Y of the receiver with the Y of the control panel.  

Black Cable

: To clamp “-” of the receiver with the “-” of the control panel.  

Brown Cable:

 To clamp W of the receiver with the W of the control panel. 

Red Cable:

 To clamp “+ ” of the receiver with the “+ ” of the control panel. 

Green Cable:

 To clamp V of the receiver with the V of the control panel. 

Yellow Cable:

 To clamp I  of the receiver with the I  of the control panel. 

 

Airzone Tacto 
Airzone Plus 

 

To install an Airzone Tacto Thermostat or an Airzone Plus Thermostat, carefully open the 
thermostat by pushing the flap on the bottom of it and separate both parts of the thermostat. 
Extract the cable through the cable duct at the bottom and fix the rear part to the wall with 
screws. 
Plus or Tacto thermostats are connected with A type Airzone Cable in the following way: 

 
Blue Cable:

 To clamp Y of the receiver with the Y of the control panel.  

Black Cable

: To clamp “-” of the receiver with the “-” of the control panel.  

Brown Cable:

 To clamp W of the receiver with the W of the control panel. 

Red Cable:

 To clamp “+ ” of the receiver with the “+ ” of the control panel. 

Green Cable:

 To clamp V of the receiver with the V of the control panel. 

Yellow Cable:

 To clamp I  of the receiver with the I  of the control panel. 

 

Important:  

Control cabling should run through a separate duct from that of the power cables and, in any 
case, the meshes of the type A cables will be connected to the earth in the electronic control 
panel. I f standard Airzone cable is not used, a shielded cable should be used with a cross-
section no lower than 0,22mm2. 

Airzone offers a 3-year guarantee for its systems if Airzone cable is used. 

 

4. MOTORIZED DISTRIBUTION ELEMENTS 

 

Airzone I ntelligent Grille 
Grill +  Motorized Hatch  

 

 

With the electronic Control Panel Airzone Type-B two-color cable will be used for connection 
or, if not, a cable with a 0,75mm2 cross-section, to the corresponding M outlet, with the 
following polarity: 

 

Red Cable:

 From clamp “-” of the control panel to clamp “-” of the grille. 

Black Cable

: From clamp “+ ” of the control panel to clamp “+ ” of the grille. 

 

Special conditions for connecting motorized distribution: 

 

Zone with Two Motorized Grills: 2 motorized grills may be connected to the same Control 
Panel.  
Cordless Zone with Two Motorized Grills:  Only one of the motorized elements may have the 
Cordless receiver fitted. The other distribution element will be connected in parallel, and it 
will not have an integrated receiver.  

 

Check that the system is correctly connected: Pay particular attention to the 12V direct 
current inlet. When the direct electrical current is connected, the control panel is reset, 
switching the red led on for 4 seconds and activating closure of the motors. 
 

 
 
 

 