CONTROLS AND OPERATING LOGIC
B. PCBA / CONTROL PARAMETERS
Tab. 4
Code
Function
Range
Factory setting
F11
Water set temperature
90-135 F
130
F12
Heat pump kick-in differential*
1-54 F
20
F13
Max ambient temp for heat pump operation
42-130 F
110
F14
Min ambient temp for heat pump operation
0-40 F
32
F15
Heat pump re-start ambient temp differential** 1-20 F
9
F19
T1/T2 adjustment
-9-9 F
0
F21
Compressor start delay
0-10 mins
3
F31
Defrost start A2 temp
-20-77 F
28
F32
Defrost stop A2 temp
0-122 F
77
F33
Defrost start delay
1-999 mins
20
F34
Max defrost time
1-99 mins
5
F41
Fan speed c
0/1/2 (Low/High/Auto)
1
F50
Pressure alarm***
0/2 (Off/On)
2
F51
Auto recovery attempts from F50 alarm
0-10 times
3
F52
Auto recovery max time from F50 alarm
0-999 mins
60
F54
Primary heater overheating alarm****
0/2 (Off/On)
2
F55
Auto recovery attempts from F54 alarm
0-10 times
3
F56
Auto recovery max time from F54 alarm
0-999 mins
60
F57
High compressor discharge temp alarm*****
0/1 (Off/On)
1
F58
Compressor discharge high temp limit
50-257 F
230
F59
Compressor re-start temp differential
1-54 F
18
F60
Condensate drain blockade alarm****** +
0/1 (Off/On)
1
F61
Activate memory to retain settings
Yes/No
Yes
F69
Communication band
24/48 BPS
24
F80
Set password
Off/Set value
Off
F89
Heater Mode max operating time
12-999 hours
48
F98
Force defrost
Null/ADF
Null
*Heat pump on if T2<=F11-F12; Electric heater on when T1<=F11-F12-10
**HP will restart when A4>=F14+F15 and A4<=F13-F15
***Error code A5 will display
****Error code A6 will display
*****Error code A7 will display
******Error code A8 will display
+ Applicable to product Version 2.01 or later
A
LA
R
M
S &
ERR
O
R
S CO
DES
M
A
INT
EN
A
NCE
DU
CT
ING
CO
NT
R
O
LS &
O
PER
A
TI
N
G
LO
G
IC
SP
EC
IFI
CA
TI
O
N
FA
Q
s
A
PP
EN
DI
X
Содержание ATI50
Страница 1: ...Technical Manual AirTap Hybrid Water Heater ATI T3 0 1...
Страница 2: ......