Internal Switches

Internal switches are located on the inside of the front cover.

#

OFF

ON

1

UNLOCKED PARAMETERS

LOCKED PARAMETERS

2

FAHRENHEIT DEGREES

CELSIUS DEGREES

3

SUMMER PROGRAM

WINTER PROGRAM

4

DISABLE TEMPERATURE ALARMS

ENABLE TEMPERATURE ALARMS

5

NO TEMPERATURE PROBE

TEMPERATURE PROBE PRESENT

6

SLAVE UNIT

PRIMARY UNIT

7

NO RESET

AUTO RESET THE INLET POSITION

8

RESET MIN POSITION ONLY

RESET TOWARD THE NEAREST POSITION

9

STOP THE MANUAL RESET

START THE MANUAL RESET

10

AM/PM TIME FORMAT

24 HOUR FORMAT

11

OPENING = TIME VALUE

OPENING = %

12

INLET MODE

TUNNEL MODE

31

TC5-ITA  rev.02

TROUBLESHOOTING GUIDE

PROBLEM

THERE IS NO

DISPLAY.

THE CIRCUIT BREAKER AT THE SERVICE PANEL IS OFF OR

TRIPPED.

THE WIRING IS INCORRECT.

THE F10 INPUT FUSE IS OPEN.

THE VOLTAGE SELECTOR SWITCH IS IN THE WRONG

POSITION.

THE DISPLAY BOARD INTERCONNECT CABLE IS UN-

PLUGGED FROM THE POWER SUPPLY BOARD.

A VARIATION IN RESISTANCE IS INDUCED ON THE

SENSOR CONNECTED TO THE TC5-ITA

- BE SURE THE SENSOR IS DRY AND MOVE IT AWAY

FROM DRAFTS AND FROM ANY SOURCE OF RADIANT

HEATING.

THERE IS ELECTRICAL NOISE NEAR THE CABLE OF THE

SENSOR CONNECTED TO THE TC5-ITA.

- DO NOT RUN THE SENSOR CABLE NEXT TO OTHER

POWER CABLES.  WHEN CROSSING OTHER POWER

CABLES, CROSS AT 90°.

THE F9 ALARM FUSE IS OPEN.

THE DISPLAY BOARD INTERCONNECT CABLE IS UN-

PLUGGED FROM THE POWER SUPPLY BOARD.

THE WIRING IS INCORRECT.

THE TC5-ITA ALARM IS DEFECTIVE.

THE TC5-ITA IS DEFECTIVE.

- LISTEN TO SEE IF THERE IS A CLICKING SOUND WHEN

THE ALARM PILOT LIGHT TURNS ON.  IF THERE IS NO

CLICKING SOUND, THE TC5-ITA IS DEFECTIVE. CONTACT

YOUR DISTRIBUTOR TO REPAIR THE CONTROLLER.

THE ROOM

TEMPERATURE

DISPLAYED BY

THE TC5-ITA

SHOWS SUDDEN

VARIATIONS.

THE TC5-ITA

ALARM PILOT

LIGHT IS ON BUT

THE ALARM IS

NOT ACTIVATED.

SOLUTION

Содержание TC5-ITA

Страница 1: ...TC5 ITA Inlet Controller USER S MANUAL M 890 00047 rev 02 REV 00...

Страница 2: ...ying Primary and Slave Units 13 Seasonal Programs 14 Verify TC5 ITA Operation Manual Mode 14 TC5 ITA OPERATION 15 Basic Principle of Operation 15 Calibration 18 CONTROLLER FUNCTIONS 20 Clock Settings...

Страница 3: ...rev 02 Fuses at the input and outputs of the controller adequately protect its circuitry in the case of an overload or overvoltage However we rec ommend that you install an additional protection devi...

Страница 4: ...ted to the TC5 ITA to centralize information management and provide monitoring and datalogging possibilities FEATURES 33 TC5 ITA rev 02 A Actuator see Inlet Alarms Conditions 29 Connection 9 Readout 2...

Страница 5: ...troller is located MUST ALWAYS REMAIN BETWEEN 32o AND 104o F 0o AND 40o C For indoor use 5 TC5 ITA rev 02 LOCATION OF THE CONTROLS Status Leds DIGITAL SCREEN DISPLAY FUNCTION SELECTION BUTTONS SUB MEN...

Страница 6: ...ELECTOR SWITCH IS IN THE WRONG POSITION THE DISPLAY BOARD INTERCONNECT CABLE IS UN PLUGGED FROM THE POWER SUPPLY BOARD A VARIATION IN RESISTANCE IS INDUCED ON THE SENSOR CONNECTED TO THE TC5 ITA BE SU...

Страница 7: ...ting with the let ters Lo 7 TC5 ITA rev 02 INSTALLATION PROCEDURE Equipment List Integrating an air inlet control system into your ventilation system requires the following equipment A Comlink 2 commu...

Страница 8: ...s on the alarm pilot light The alarm readout function displays all currently outstanding alarm situations Select ALARM READOUT using the function selection buttons The following codes can be displayed...

Страница 9: ...without a temperature sensor in this case the ROOM TEMPERATURE menu will not be a available To extend the probe This probe can be extended up to 500 ft 150 m Use a shielded cable of outside diameter b...

Страница 10: ...es jumper JP5 and the computer line uses JP4 Use pins 2 and 3 for YES and pins 1 and 2 for NO The following diagram shows a typical connection with the appro priate jumper configurations END OF LINE J...

Страница 11: ...e adjustment buttons to set the hour to the desired value Press the right arrow key once The minutes flash on the display Use the adjustment buttons to set the minutes to the desired value Press the r...

Страница 12: ...t is required to fully open close the inlet panel in order to reset the inlet position The reset delay of an inlet must be greater than its total opening time This ensures the inlet panel to be comple...

Страница 13: ...e opening of the panel Set internal switch 8 to ON to use this reset method This resetting method requires the pres ence of limit switches at both ends of the actuator ON OFF ON OFF 13 TC5 ITA TC5 ITA...

Страница 14: ...he air inlet then put a limit switch at this position to prevent the actuator from opening any further ON OFF 23 TC5 ITA TC5 ITA rev 02 The cummulative opening times of an air inlet cannot ex ceed the...

Страница 15: ...row key to select the next step Use the adjustment buttons to specify the opening time that needs to be added to the previous opening or to specify the inlet opening in associated with the selected st...

Страница 16: ...diate step is enabled the inlet opens during half the variable stage s opening when the stage s speed is of 75 it reaches the stage s HI opening position when the fan speed is 100 The three following...

Страница 17: ...STALLATION PROCEDURE chapter To display the identification number Select IDENTIFICATION NUMBER using the function selection buttons The identification number is displayed alternating with ID and PRI o...

Страница 18: ...you want to program with internal switch 3 19 TC5 ITA TC5 ITA rev 02 CALIBRATION SETTINGS 1 Select CALIBRATION using the function selection buttons 2 Press and hold the right arrow key for 2 seconds o...

Страница 19: ...you want to program with internal switch 3 19 TC5 ITA TC5 ITA rev 02 CALIBRATION SETTINGS 1 Select CALIBRATION using the function selection buttons 2 Press and hold the right arrow key for 2 seconds o...

Страница 20: ...STALLATION PROCEDURE chapter To display the identification number Select IDENTIFICATION NUMBER using the function selection buttons The identification number is displayed alternating with ID and PRI o...

Страница 21: ...diate step is enabled the inlet opens during half the variable stage s opening when the stage s speed is of 75 it reaches the stage s HI opening position when the fan speed is 100 The three following...

Страница 22: ...row key to select the next step Use the adjustment buttons to specify the opening time that needs to be added to the previous opening or to specify the inlet opening in associated with the selected st...

Страница 23: ...he air inlet then put a limit switch at this position to prevent the actuator from opening any further ON OFF 23 TC5 ITA TC5 ITA rev 02 The cummulative opening times of an air inlet cannot ex ceed the...

Страница 24: ...e opening of the panel Set internal switch 8 to ON to use this reset method This resetting method requires the pres ence of limit switches at both ends of the actuator ON OFF ON OFF 13 TC5 ITA TC5 ITA...

Страница 25: ...t is required to fully open close the inlet panel in order to reset the inlet position The reset delay of an inlet must be greater than its total opening time This ensures the inlet panel to be comple...

Страница 26: ...e adjustment buttons to set the hour to the desired value Press the right arrow key once The minutes flash on the display Use the adjustment buttons to set the minutes to the desired value Press the r...

Страница 27: ...es jumper JP5 and the computer line uses JP4 Use pins 2 and 3 for YES and pins 1 and 2 for NO The following diagram shows a typical connection with the appro priate jumper configurations END OF LINE J...

Страница 28: ...without a temperature sensor in this case the ROOM TEMPERATURE menu will not be a available To extend the probe This probe can be extended up to 500 ft 150 m Use a shielded cable of outside diameter b...

Страница 29: ...s on the alarm pilot light The alarm readout function displays all currently outstanding alarm situations Select ALARM READOUT using the function selection buttons The following codes can be displayed...

Страница 30: ...ting with the let ters Lo 7 TC5 ITA rev 02 INSTALLATION PROCEDURE Equipment List Integrating an air inlet control system into your ventilation system requires the following equipment A Comlink 2 commu...

Страница 31: ...ELECTOR SWITCH IS IN THE WRONG POSITION THE DISPLAY BOARD INTERCONNECT CABLE IS UN PLUGGED FROM THE POWER SUPPLY BOARD A VARIATION IN RESISTANCE IS INDUCED ON THE SENSOR CONNECTED TO THE TC5 ITA BE SU...

Страница 32: ...troller is located MUST ALWAYS REMAIN BETWEEN 32o AND 104o F 0o AND 40o C For indoor use 5 TC5 ITA rev 02 LOCATION OF THE CONTROLS Status Leds DIGITAL SCREEN DISPLAY FUNCTION SELECTION BUTTONS SUB MEN...

Страница 33: ...ted to the TC5 ITA to centralize information management and provide monitoring and datalogging possibilities FEATURES 33 TC5 ITA rev 02 A Actuator see Inlet Alarms Conditions 29 Connection 9 Readout 2...

Страница 34: ...rev 02 Fuses at the input and outputs of the controller adequately protect its circuitry in the case of an overload or overvoltage However we rec ommend that you install an additional protection devi...

Страница 35: ...ying Primary and Slave Units 13 Seasonal Programs 14 Verify TC5 ITA Operation Manual Mode 14 TC5 ITA OPERATION 15 Basic Principle of Operation 15 Calibration 18 CONTROLLER FUNCTIONS 20 Clock Settings...

Страница 36: ...TC5 ITA Inlet Controller USER S MANUAL M 890 00047 rev 02 REV 00...

Отзывы: