When connected to Apply voltage terminals of multiple indoor units with a connected unit, 

be sure to make a branch outside the indoor unit using a pull box, etc. as shown on below 

example.

CNA01

CNA01

CNA01

DC power supply 

12 to 24V

Connected unit

Load  

resistance

P.C.B

P.C.B

P.C.B

In

pu

de

vi

ce 1

In

pu

de

vi

ce 2

In

do

or u

ni

t

In

do

or u

ni

t

In

do

or u

ni

t

Load  

resistance

● Dry contact terminal ([CNA02], [CNA04])

When a power supply is unnecessary at the input device you want to connect, use the Dry 

contact terminal ([CNA02], [CNA04]).

CNA02

*c

*c

*c

*d

CNA04

P.C.B

GND

Ch 1

Ch 3

Ch 2

Connected unit

*c: Select very low current use contacts (usable at DC 12 V, DC 1 mA or less).

*d: The wiring is different from Apply voltage terminals. Be sufficiently careful when wiring.

When connected to Dry contact terminals of multiple indoor units with a connected unit, 

insulate each indoor unit with relay, etc. as shown on below example.

K1

CNA02

CNA02

CNA02

K2

K3

K4

K5

K6

P

ow

er s

up

pl

y f

or r

el

ay

In

do

or u

ni

t

In

do

or u

ni

t

In

do

or u

ni

t

Input device 2

Input device 1

K1 - K6: Relay

(Device for DC Current)

P.C.B

P.C.B

P.C.B

NOTE :

When connected to multiple indoor units directly, it will cause breakdown.

Operation behavior

● Input signal type

The input signal type can be selected.

It is switched by DIP switch on the indoor unit PCB.

Pulse

Edge

The width of pulse must be 

longer than 200 msec.

DIP switch [Set 2 SW2]

Input signal type

OFF (Factory setting)

Edge

ON

Pulse

● When function setting is “Operation/Stop” mode.

[In the case of “Edge” input]

Connector

Input signal

Command

Ch1 of CNA01 or CNA02

OFF → ON

Operation

ON → OFF

Stop

[In the case of “Pulse” input]

Connector

Input signal

Command

CNA01 or CNA02

Ch1

OFF → ON

Operation

Ch2

OFF → ON

Stop

*  The last command has priority.

*  The indoor units within the same remote controller group operates in the same mode.

● When function setting is “Emergency stop” mode.

[In the case of “Edge” input]

Connector

Input signal

Command

Ch1 of CNA01 or CNA02

OFF → ON

Emergency stop

ON → OFF

Normal

[In the case of “Pulse” input]

Connector

Input signal

Command

CNA01 or CNA02

Ch1

OFF → ON

Emergency stop

Ch2

OFF → ON

Normal

*  All indoor units of same refrigerant system stops when Emergency stop operates.

● 

When function setting is “Forced stop” mode.

[In the case of “Edge” input]

Connector

Input signal

Command

Ch1 of CNA01 or CNA02

OFF → ON

Forced stop

ON → OFF

Normal

[In the case of “Pulse” input]

Connector

Input signal

Command

CNA01 or CNA02

Ch1

OFF → ON

Forced stop

Ch2

OFF → ON

Normal

*  When the forced stop is triggered, indoor unit stops and Operation/Stop operation by a 

remote controller is restricted.

*  When forced stop function is used with forming a remote controller group, connect the 

same equipment to each indoor unit within the group.

• 

Selection method of functions

“Operation/Stop” mode or “Emergency stop” mode, “Forced stop” mode can be selected 

with function setting of indoor unit.

● 

Forced thermostat off function

[“Edge” input only]

Connector

Input signal

Command

Ch3 of CNA03 or CNA04

OFF → ON

Thermostat off

ON → OFF

Normal

6.5.2  External output

• 

A twisted pair cable (22AWG) should be used. Maximum length of cable is 25m.

• 

Use an external input and output cable with appropriate external dimension, depending 

on the number of cables to be installed.

• 

Output voltage: Hi DC12V±2V, Lo 0V.

• 

Permissible current: 50mA

Output select

● 

When indicator etc. are connected directly

Operation 

indicator

Error 

indicator

Indoor unit Fan 

status indicator

connected unit

P.C.B

CNB 

01

● 

When connecting with unit equipped with a power supply

CNB 

01

P.C.B

Connected 

device 1

Connected 

device 2

Connected 

device 3

connected unit

Relay (Locally purchased)

9371022475_IM.indb   9

2/2/2017   14:58:11

Содержание AUXK018GLAH

Страница 1: ...NUEL D INSTALLATION MANUAL DE INSTALACI N UNIT INT RIEURE type cassette UNIDAD INTERIOR Tipo casete Pour le personnel agr uniquement nicamente para personal de servicio autorizado Italiano MANUALE DI...

Страница 2: ...ontains no user serviceable parts Always consult authorized service person nel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THIS P...

Страница 3: ...that they do not topple or fall CAUTION Do not install the unit in the following areas Area with high salt content such as at the seaside It will deteriorate metal parts causing the parts to fail or t...

Страница 4: ...or unit 200 130 50 A B 50 to 100 10 40 140 to 145 Type Dimension mm A B AUXM 246 256 AUXK 288 298 Refrigerant piping and drain piping positions unit mm Drain pipe Connect the attached drain hose 342 2...

Страница 5: ...ation location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant piping If the expected humidity level is 70 to 80 use heat insulation that is 15 mm or...

Страница 6: ...PIPES WARNING Do not insert the drain piping into the sewer where sulfurous gas occurs Heat ex change erosion may occur Insulate the parts properly so that water will not drip from the connection par...

Страница 7: ...ce agent or similarly qualified persons in order to avoid a hazard CAUTION Earth Ground the unit Do not connect the earth ground cable to a gas pipe water pipe lightning rod or a telephone earth groun...

Страница 8: ...1 Use ring terminals with insulating sleeves as shown in the figure below to connect to the terminal block 2 Securely clamp the ring terminals to the cables using an appropriate tool so that the cable...

Страница 9: ...cy stop or Forced stop by using indoor unit PCB CNA01 or CNA02 Operation Stop mode Emergency stop mode or Forced stop mode can be selected with function setting of indoor unit Indoor unit can be Force...

Страница 10: ...as priority The indoor units within the same remote controller group operates in the same mode When function setting is Emergency stop mode In the case of Edge input Connector Input signal Command Ch1...

Страница 11: ...nit address Rotary switch IU AD 1 Factory setting 0 Rotary switch IU AD 10 Factory setting 0 When connecting multiple indoor units to 1 refrigerant system set the address at IU AD SW as shown in the T...

Страница 12: ...d stop Error report target 47 00 All Change the target for reporting errors Errors can either be re ported in all locations or only on the central remote controller 01 Display only on central remote c...

Страница 13: ...mmunica tion circuit wired remote controller error 4 1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 4 4 Human sensor error 5 1 Indoor unit fan motor 1 error 5 2...

Отзывы: