6.3. Unit wiring

Before attaching the cable to terminal block.

6.3.1. Power supply cable

Adjust the length of power supply cable to avoid excessive tension with referring 

fi

 gure 

below.

For U.S.A. and Canada

 

31/32 in. 
(25 mm)

31/32 in. 
(25 mm)

3-3/4 in. 
(95mm)

3-3/4 in. 
(95mm)

Earth 
(Ground) 
wire

Conduit 
connector

For Others

19/32 in. (15 mm)

2-3/4 in. (70 mm)

Earth 

(Ground)

wire

A. For solid core wiring

(1)  To connect the electrical terminal, follow the below diagram and connect after looping 

it around the end of the cable.

(2)  Use the speci

fi

 ed cables, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(3)  Use an appropriate screwdriver to tighten the terminal screws. Do not use a 

screwdriver that is too small, otherwise, the screw heads may be damaged and 
prevent the screws from being properly tightened.

(4)  Do not tighten the terminal screws too much, otherwise, the screws may break.
(5)  See the table for the terminal screw tightening torques.
(6)  Please do not 

fi

 x 2 power supply cables with 1 screw.

Loop

Screw with 
special washer

Screw with 
special washer

Cable end (Loop)

Cable end (Loop)

Cable

Cable

Terminal block

Strip 31/32 in.

(25 mm)

 

WARNING

When using solid core cables, do not use the ring terminal. If you use the solid core 
cables with the ring terminal, the ring terminal’s pressure bonding may malfunction 
and cause the cables to abnormally heat up.

B. For strand wiring

(1)  Use ring terminals with insulating sleeves as shown in the 

fi

 gure below to connect to 

the terminal block.

(2)  Securely clamp the ring terminals to the cables using an appropriate tool so that the 

cables do not come loose.

(3)  Use the speci

fi

 ed cables, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(4)  Use an appropriate screwdriver to tighten the terminal screws. Do not use a 

screwdriver that is too small, otherwise, the screw heads may be damaged and 
prevent the screws from being properly tightened.

(5)  Do not tighten the terminal screws too much, otherwise, the screws may break.
(6)  See the table for the terminal screw tightening torques.
(7)  Please do not 

fi

 x 2 power supply cables with 1 screw.

 Sleeve

Screw with 
special washer

Screw with 
special washer

Ring terminal

Cable

Cable

Terminal block

Ring terminal

Ring terminal

Strip 13/32 in.

(10 mm)

 

WARNING

Use ring terminals and tighten the terminal screws to the speci

fi

 ed torques, otherwise, 

abnormal overheating may be produced and possibly cause heavy damage inside the 
unit.

Tightening torque

M4 screw 

(Power supply/L1, L2 (N), GND)

11 to 16 lbf·in 

(1.2 to 1.8 N·m)

6.3.2. Transmission and Remote controller cable

Shielded wire 

(no 

fi

 lm)

1-3/16 in. (30 mm)

1-31/32 in. (50 mm)

Transmission cable

1-3/16 in. (30 mm)

Remote controller cable

•  Connect remote controller and transmission cables as shown in Fig. B.

•  When the 2 cables are attached.

Fig. B

Good

Prohibited

Prohibited

Different diameter

Connect to 1 side

 

WARNING

Tighten the terminal screws to the speci

fi

 ed torques, otherwise, abnormal overheating 

may be produced and possibly cause heavy damage inside the unit.

Tightening torque

M3 screw 

(Transmission/X1, X2)

(Remote controller/Y1, Y2, Y3)

4.4 to 5.3 lbf·in 

(0.5 to 0.6 N·m)

 

CAUTION

To peel the 

fi

 lm from the lead cable, use a dedicated tool that will not damage the 

conductor cable.

When installing a screw on the terminal block, do not cut the cable by overtightening 
the screw. On the other hand, an under tightened screw can cause faulty contact, 
which will lead to a communication failure.

9367701094-02_IM.indb   Sec1:9

9367701094-02_IM.indb   Sec1:9

12/29/2011   10:50:35 AM

12/29/2011   10:50:35 AM

Содержание ABUA12RLAV

Страница 1: ...type APPAREIL INT RIEUR Type sol plafond UNIDAD INTERIOR Tipo piso techo UNIDADE INTERIOR Tipo ch o teto For authorized service personnel only Uniquement r serv aux techniciens agr s S lo para person...

Страница 2: ...o provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause drip ping and water damage to walls and floors In an Area with High Winds Securely a...

Страница 3: ...y vacate the premises and thoroughly ventilate the area If the refrigerant comes in contact with a flame it produces a toxic gas 1 2 2 Special tool for R410A WARNING To install a unit that uses R410A...

Страница 4: ...ns suspended carbon fibers or flammable dust or volatile inflammables such as paint thinner or gasoline If gas leaks and settles around the unit it can cause a fire Area where animals may urinate on t...

Страница 5: ...l set the suspension bolts Note that anchor bolts are M10 bolts to be obtained locally Anchor Bolt Strength 220 to 330 lbf 980 to 1470 N M10 Anchor bolt Field supply Ceiling 25 32 to 1 31 32 20 to 50...

Страница 6: ...ditioner using R410A incurs pressure higher than when using conventional R22 refrigerant it is necessary to choose adequate materials Thicknesses of copper pipes used with R410A are as shown in the ta...

Страница 7: ...l from getting into the system as this would reduce the lifetime of the units If necessary cut the silencer pipe and use it Silencer pipe Accessories CAUTION Hold the torque wrench at its grip keeping...

Страница 8: ...e is no space Drain pan Side view Applying area of adhesive Hard PVC side Joint pipe Field supply Drain pipe Field supply 3 4 in 19 mm I D 1 1 16 in 27 mm O D 5 32 in 4 mm or less Wrap the Drain hose...

Страница 9: ...miss operation or breakdown When handling PCB static electricity charged in the body may cause malfunction of the PCB Follow the cautions below Establish an earth ground for the indoor and outdoor un...

Страница 10: ...specified cables connect them securely and fasten them so that there is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that...

Страница 11: ...ponent box cover Remove the 3 tapping screws Electric component box cover Base CAUTION Be careful not to pinch the lead cables between the electric component box and base 4 Wiring When there is 1 tran...

Страница 12: ...Wiring methods and specifications A twisted pair cable 22AWG should be used Maximum length of cable is 492 ft 150 m Use an external input and output cable with appropriate external dimension dependin...

Страница 13: ...s 492 ft 150 m Use an external input and output cable with appropriate external dimension depending on the number of cables to be installed 3 Connection methods Wire modification Remove insulation fro...

Страница 14: ...7 0 7 7 0 7 8 0 8 8 0 8 9 0 9 9 0 9 10 1 0 10 1 0 11 1 1 11 1 1 12 1 2 12 1 2 99 9 9 63 6 3 Do not set the indoor unit address IU AD SW at 64 to 99 It may result in failure 3 Remote controller address...

Страница 15: ...t start and stop the indoor unit by this function in normal operation Be sure to operate by the control unit converter or external input device 01 Disable External control 46 00 Start Stop Allow an ex...

Страница 16: ...ver the take off part with material putty or the like that will block it off UNDER CEILING TYPE Top Right Rear FLOOR CONSOLE TYPE 1 8 2 Mount the cover plate Right 1 Cut a pipe exit hole in the right...

Страница 17: ...r burn damage Is the indoor unit earthed grounded Short circuit Is the connection cable the specified thickness No operation heat or burn damage Are the inlets and outlets free of any obstacles No coo...

Отзывы: