background image

En-8

 

WARNING

  Install an earth leakage breaker. In addition, install the earth leakage breaker so that 

the entire AC main power supply is cut off at the same time. Otherwise, electric shock 
or 

fi

 re could result.

  Always connect the earth (ground) cable.

Improper earthing (grounding) work can cause electric shocks.

  Install the remote controller cables so as not to be direct touched with your hand.

  Perform wiring work in accordance with standards so that the air conditioner can be 

operated safely and positively.

  Connect the connection cable 

fi

 rmly to the terminal board. Imperfect installation may 

cause a 

fi

 re.

  If the supply cable is damaged, it must be replaced by the manufacturer, its service 

agent or similarly quali

fi

 ed persons in order to avoid a hazard.

 

CAUTION

  Earth (Ground) the unit.  
  Do not connect the earth (ground) cable to a gas pipe, water pipe, lightning rod, or a 

telephone earth (ground) cable. 

  Improper earthing (grounding) may cause electric shock.

  Do not connect power supply cables to the transmission or remote controller 

terminals, as this will damage the product.

  Never bundle the power supply cable and transmission cable, remote controller cable 

together.

  Separate these cable by 50 mm or more.
  Bundling these cables together will cause miss operation or breakdown.

  When handling PCB, static electricity charged in the body may cause malfunction of 

the PCB. Follow the cautions below:

•  Establish an earth (ground) for the indoor and outdoor units and peripheral devices.

• Cut power (breaker) off.

• Touch metal part of the indoor unit for more than 10 seconds to discharge static 

electricity charged in the body.

• Do not touch terminals of parts and patterns implemented on PCB.

1

6.1. Electrical requirement

Voltage rating

230 V

Operating range

198 to 264 V

• Select the power cable type and size in accordance with relevant local and national 

regulations.

• Speci

fi

 cations for local wiring power cord and branch wiring are in compliance with local 

code.

• Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the wire 

diameter when the wire length is long.

Refer to the table for the breaker speci

fi

 cations of each installation condition. Perform 

the power crossover wiring within the range of the same refrigerant system. When the 
crossover wiring is done, make a connection for indoor units to satisfy conditions A and B 
below.

A. Current breaker requirements

Model

MCA

MFA

AB

A30GATH

0.52 A

20 A

AB

A36GATH

0.66 A

AB

A45GATH

0.98 A

AB

A54GATH

1.32 A

MCA: Minimum Circuit Ampacity
MFA: Main Fuse Ampacity
When the power crossover wiring is done, make it so that the total of the MCA of the 
connected RB units and indoor units does not exceed the 15 A. For RB unit MCA, refer to 
the RB unit installation manual.
If the capacity of connected RB units and indoor units exceeds the upper limit, either add 
breakers or use a breaker with a greater capacity.

B. Earth leakage breaker requirements

Breaker capacity

* Maximum connectable “indoor units” or 

“indoor units + RB units”

30 mA, 0.1 sec or less

44 or less **

100 mA, 0.1 sec or less

45 to 128

*  Heat pump type: indoor units, Heat recovery type: indoor units and RB units.
**  If the total number of units connected to the breaker exceeds 44, either add a 30mA 

breaker, or use breakers with a greater capacity.

6.1.1. Cable speci

fi

 cations

Follow the speci

fi

 cations below for the power supply, transmission and remote controller 

cable.

Recommended 

cable size (mm

2

)

Cable type

Remark

Power 

supply cable

2.5

Type245 IEC57 

or equivalent

1ø 50 Hz 

198 to 264 V

2 Cable + earth (ground)

Transmission cable

0.33

LONWORKS 

compatible cable

22 AWG 

LEVEL 4 (NEMA) 

non-polar 2 core, 

twisted pair solid core 

diameter 0.65 mm

Remote controller 

cable

(2-wire type)

0.33 to 1.25

Sheathed PVC cable*

Non polar 2 core

Remote controller 

cable

(3-wire type)

0.33

Sheathed PVC cable*

Polar 3 core

*:  Use shielded cable in accordance with local rules for 
  remote controller cable.

]1

6.2. Wiring method

(EXAMPLE)

*1: When connecting to the Heat Recovery System, refer to the installation manual of 

the RB unit.

*2: Earth (Ground) the remote controller if it has an earth (ground) cable.

*3: When connecting the 2-wire type remote controller, Y3 is not used.

Outdoor unit or RB unit *1

Transmission

Power supply

Remote controller 

(Master)

Remote controller 

(Slave)

Remote 

controller

(Crossover wiring of power supply)

Power supply

Breaker

Indoor unit

Power supply

Pull box

Power supply

Pull box

Power supply

Power supply

Indoor unit

Indoor unit

Breaker

Breaker

Remote 

control

*2

*2

*2

*3

*3

*3

Indoor unit

Indoor unit

Indoor unit

Transmission

Breaker

*  Earth (Ground) the remote controller if it has an earth (ground) wire.
Connect the earth (ground) wire of the remote controller to the earth (ground) terminal of 
transmission.

1

6.3. Unit wiring

Before attaching the cable to terminal block.

6.3.1. Power supply cable

Adjust the length of power supply cable to avoid excessive tension with referring 

fi

 gure 

below.

Earth (Ground) cable

20 mm

45 mm

A. For solid core wiring

(1)  To connect the electrical terminal, follow the below diagram and connect after looping it 

around the end of the cable.

(2)  Use the speci

fi

 ed cables, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(3)  Use an appropriate screwdriver to tighten the terminal screws. Do not use a 

screwdriver that is too small, otherwise, the screw heads may be damaged and 
prevent the screws from being properly tightened.

(4)  Do not tighten the terminal screws too much, otherwise, the screws may break.

9367702107-02_IM.indb   Sec1:8

9367702107-02_IM.indb   Sec1:8

1/25/2013   3:51:36 PM

1/25/2013   3:51:36 PM

Содержание ABHA30GATH

Страница 1: ...TÉRIEURE type plafonnier UNIDAD INTERIOR tipo techo Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado MANUALE DI INSTALLAZIONE UNITÀ INTERNA tipo a soffitto A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΕΣΩΤΕΡΙΚΗ ΜΟΝΑΔΑ Τύπος οροφής Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO UNIDADE INTERIOR Tipo de tecto Apenas para...

Страница 2: ...e parts Always consult authorized service personnel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THE UNIT 1 2 1 Precautions for using R410A refrigerant WARNING Do not introduce any substance other than the prescribed refrigerant into the refrigeration cycle If air enters the refrigeration cycle the pressure in the refrigeration ...

Страница 3: ...door unit in the following areas Area with high salt content such as at the seaside It will deteriorate metal parts causing the parts to fail or the unit to leak water Area filled with mineral oil or containing a large amount of splashed oil or steam such as a kitchen It will deteriorate plastic parts causing the parts to fail or the unit to leak water Area that generates substances that adversely...

Страница 4: ...sh air intake refer to 8 FRESH AIR INTAKE Side cover B Right side Air filter Intake grille Tapping screw INDOOR UNIT Side cover B Left side Side cover A Right side 3 3 2 Indoor unit installation You can use the accessory template to help you install the indoor unit The template helps you determine the appropriate locations for suspension bolts and pipe openings drain pipe and connection cable Dril...

Страница 5: ...hat have clean external and internal sides without any contamination which may cause trouble during use such as sulfur oxide dust cutting waste oil or water For 4 Left rear piping 5 Left piping Transfer the Drain cap and Drain cap seal Drain cap seal Drain cap Indoor unit Drain pan Drain cap seal Drain cap Push cap all the way on as far as it will go knockout hole for drain hose Indoor unit CAUTIO...

Страница 6: ...er a prolonged period causing refrigerant to leak and generate a hazardous gas if the refrigerant comes into contact with a flame 4 3 1 Flaring Use special flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs 3 Insert the flare nut always use the flare nut attached ...

Страница 7: ...it pipe Body side Tighten with 2 wrenches Holding wrench Flare nut Flare nut mm in Tightening torque N m kgf cm 6 35 1 4 dia 16 to 18 160 to 180 9 52 3 8 dia 32 to 42 320 to 420 12 70 1 2 dia 49 to 61 490 to 610 15 88 5 8 dia 63 to 75 630 to 750 19 05 3 4 dia 90 to 110 900 to 1 100 CAUTION Be sure to install the pipe against the port on the indoor unit and the outdoor unit correctly If the centeri...

Страница 8: ...on cables and power cables or ones specified by the manufacturer Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire For wiring use the prescribed type of cables connect them securely making sure that there are no external forces of the cables applied to the terminal connections Improperly connected or secured cables can cause serious ac...

Страница 9: ...and indoor units does not exceed the 15 A For RB unit MCA refer to the RB unit installation manual If the capacity of connected RB units and indoor units exceeds the upper limit either add breakers or use a breaker with a greater capacity B Earth leakage breaker requirements Breaker capacity Maximum connectable indoor units or indoor units RB units 30 mA 0 1 sec or less 44 or less 100 mA 0 1 sec o...

Страница 10: ...ighten the terminal screws to the specified torques otherwise abnormal overheating may be produced and possibly cause heavy damage inside the unit Tightening torque M4 screw Power supply L N GND 1 2 to 1 8 N m 12 to 18 kgf cm 6 3 2 Transmission and Remote controller cable Shielded cable no film 30 mm 40 mm Remote controller cable 30 mm Y1 Y2 Y3 40 mm For 3 wire type 30 mm For 2 wire type Connect r...

Страница 11: ...he Apply voltage terminal CNA01 CNA03 Input device 1 Input device 2 Input device 3 Load resistance Load resistance Load resistance 1 DC power supply 12 to 24V connected unit a a a P C B CNA01 CNA03 b 1 Make the power supply DC12 to 24V Select a power supply capacity with an ample surplus for the connected load Do not impress a voltage exceeding 24V across pins 1 2 and 1 3 a The allowable current i...

Страница 12: ...ch indoor unit within the group Selection method of functions Operation Stop mode or Emergency stop mode Forced stop mode can be selected with function setting of indoor unit Forced thermostat off function Edge input only Connector Input signal Command Ch3 of CNA03 or CNA04 OFF ON Thermostat off ON OFF Normal 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25...

Страница 13: ...N Use an insulated screwdriver to set the DIP switches Rotary switch Example 0 Rotary switch Example 0 Setting Setting range Type of switch Indoor unit address 0 to 63 Setting example 2 IU AD 10 IU AD 1 Refrigerant circuit address 0 to 99 Setting example 63 REF AD 10 REF AD 1 1 Indoor unit address Rotary switch IU AD 1 Factory setting 0 Rotary switch IU AD 10 Factory setting 0 When connecting mult...

Страница 14: ... Service tool Web monitoring tool DIP switch setting Set the DIP switch SET 4 SW3 referring to the Table C DIP switch SET4 OFF ON SW SW SW SW 1 2 3 4 Table C DIP switch SET 4 SW3 Cooling temperature setting range OFF Factory setting Standard 18 to 30 C ON Extension 18 to 32 C NOTE Please do not make a standard setup and an extension setup intermingled in remote controller group FUNCTION SETTI 1 7 ...

Страница 15: ...sary 01 Stop 7 4 1 Button name and function TIMER indicator lamp Orange MANUAL AUTO button OPERATION indicator lamp Green FILTER indicator lamp Red 7 4 2 Checking the function settings Press and hold the MANUAL AUTO button on the indoor unit for 3 seconds to check the function settings It is necessary to disconnect the power in order to return to normal operation mode 1 Indoor unit and refrigerant...

Страница 16: ...alf concealed orientation only install side cover A 7 Install the air filters 10 TEST RUN 1 10 1 Test run using Outdoor unit PCB Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit is to be used for the test run 10 2 Test run using remote controller Refer to the Installation Manual for the remote controller to perform the test run using the remote controller When ...

Страница 17: ...Indoor unit power supply abnormal 3 2 Indoor unit main PCB error 3 10 Indoor unit communication circuit wired remote controller error 4 1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor unit miscellaneous error 13 1 RB unit error Displa...

Отзывы: