Airport Lighting Company
9
Current Brightness Step & Local or Remote Indication
Note: This line will not scroll
Vin
–
Input (Source) Voltage Measurement
Iin
–
Input Current Measurement, if
equipped. If not equipped, this line will show:
“Iin=
-----"
Vout
–
The voltage reading of the connected
field output circuit
Iout
–
The current reading of the connected
field output circuit
kVAo
–
The kVA calculation of the connected
field output circuit
kWo
–
the kW calculation of the connected
field output circuit
*
kVAi
–
The kVA calculation of the supply
*
kWi
–
The kW calculation of the supply
*
PFIn
–
Power factor calculation of the
supply
*
PFOut
–
Power factor calculation of the
output
Lamps Out
–
Current count of lamps out,
must be configured, enabled, and calibrated.
If not equipped, this line will show:
“Lamps Out=
---"
Hz
–
The configured AC voltage frequency
Temperature
–
Displays the current
temperature reading at the DCMU in
centigrade
Mgr
–
Displays the current megger reading (if
equipped). Until a megger test is run, this line
will show: “Mgr=?????”
HwVer
–
Hardware version of the DCMU
SwVr
–
Software version of the DCMU
Table 3: Main Screen Information
Note: The kVAi, kWi, PFIn, and PFOut options only appear on the screen if the CCR is equipped
with an input CT.
4.2.2 Navigating Menus
The menus of the CCR are set up as a collection of folders within folders, similar to a file cabinet.
By using the UP, DOWN, and DOT buttons, it is possible to scroll through folder selections, and
open a folder with its own options and sub-folders.