OWNERS MANUAL

FOR AIRPAX DIMENSIONS

INVERTERS

Model ADI-12/800N

  Model ADI-12/1200N

       Table of Contents

                                                   Page

1.  General . . . . . . . . . . .

2

2.  Description . . . . . . . .

2

3.  Installation  . . . . . . . .

2

4.  Start Up/Operation. . .

4

5. Troubleshooting. . . . .

4

6.  Installation Figure 1 . .

5

7.  Limited Warranty . . . .

6

 1.  GENERAL
    1.01 Dimensions inverters have been designed
and manufactured for many user applications and
long life.  They utilize patented construction meth-
ods and high technology electronic parts and
circuitry.
    1.02

 CAUTION:  Inverters produce hazardous

voltages, to avoid  risk of harm or fire the unit must
be properly installed. There are no user service-
able parts inside, do not remove the cover.
CAUTION:  The inverter should not be mounted in
a location that may be exposed to rain or spray.
CAUTION:  The inverter should not be installed in
a zero clearance enclosure.
CAUTION:  Damage to the inverter will occur if
correct polarity is not observed when installing the
DC input cables.
CAUTION:  Damage to the inverter will occur if an
external AC power source is applied to the inverter’s
AC output or its hardwire output.
CAUTION:  The inverter contains a circuit breaker
and capacitor that may produce a spark. Do not
mount in a confined battery or  gas compartment.
CAUTION:   Working in the vicinity of lead-acid

batteries is dangerous. Batteries generate explo-
sive gases during operation.  There is a risk of acid
exposure. There is also a risk of high  current
discharge from shorting the battery that can cause
fire and explosion.
CAUTION:  Be sure the inverter's circuit breaker or
fuse are turned off during installation.

    2.  DESCRIPTION
      2.01    The inverter converts 12 VDC to 120
VAC, 60 HZ, having a pure sine wave form.
       2.02 The inverter has a controlled frequency
at 60 HZ + 0.05%.
     2.03     The inverter has internal protection
against output short circuit, output overload and
high temperature conditions.  Also, there is a
thermally controlled cooling fan.
      2.04 The inverter is designed to operate any
120 VAC,  60 HZ single phase appliance, equip-
ment or tool within its power ratings.

                     Inverter Rating
    Inverter       Input               Output___
    Model      (VDC)   (ADC)   (VAC) (Watts)
    12/800N   12.6   Up to 80    120     800
    12/1200N  12.6  Up to 120  120    1200

    3.  INSTALLATION
     3.01    The following instructions should be
thoroughly read and understood before installa-
tion.
      3.02

   CAUTION: Inverters produce hazard-

ous voltages, to avoid risk of harm or fire the unit
must be properly installed.
CAUTION:   Damage to the inverter will occur if
correct polarity is not observed when installing

 

the

DC input cables.
 

CAUTION:  Damage to the inverter will occur if an

external AC power source is applied to the inverter’s
AC outlet or its hardwire output.
CAUTION:  Be sure  the inverter's circuit breaker
or fuse are turned “OFF”during installation.