manualshive.com logo in svg
background image

6

The valves should be sized according to 

the capacity of the outdoor unit. Failure to 

install the right valve can lead to poor per-

formance and possible compressor damage.

CAUTION

!

Ensure that the TXV bulb is in direct con-

tact with the suction/vapor line. Gap be-

tween the bulb and tube should be avoid-

ed. Failure to do so will impair the proper functioning of the 

TXV valve.

CAUTION

!

I. TXV Bulb Horizontal Mounting

The orientation and location of the TXV bulb has a major influence 

on the system performance.

If the TXV sensing bulb is mounted verti-

cally; the capillary MUST be directed up-

wards. The bulb must be mounted on the 

wall opposite to that being directly hit by the refrigerant and

oil leaving the distributor tubes.

CAUTION

!

II. TXV Bulb Vertical Mounting

Fig 8B-3.  Recommended location 

for vertical TXV bulb mount

As recommended in Section 

8B-I,      the  TXV  sensing  bulb 

should be mounted in a hori-

zontal plane in relation to the 

suction/vapor line. However, 

some  installation  configura

-

tions may require that the 

sensing bulb be mounted ver-

tically.  In this instance, place 

the bulb opposite the piping 

wall being hit by refrigerant 

and oil leaving the distributor 

tubes, and with capillary tubes 

directed upwards as shown in 

Fig. 8B-3.

III-3.

 Replace the Teflon O-ring 

seal in place (located between 

the halves).

O-ring

III-2.

 Remove the existing flow

-

rator piston using a small wire 

or pick.

Note: Photos are for basic illustration purposes only.  Actual equip-

ment configuration may differ from that shown.

III. Field-Installed TXV Retrofit

When installing an expansion valve, it is not necessary to slide the 

coil out of the housing.

III-1.

 Disassemble the flowrator 

body using two wrenches. Un-

screw the body with a counter-

clockwise motion.

Ensure that the TXV selected is compat-

ible with the refrigerant used in the out-

door system (R22 or R410A). TXV caps are 

painted green for R22 or pink for R410A. In absence of col-

or, the caps will be marked with the compatible refrigerant.

CAUTION

!

The sensing bulb and TXV body MUST be 

protected from overheating during braz-

ing.  The sensing bulb and TXV body must 

be covered using a quench cloth or wet cloth when brazing. 

Pointing the brazing flame away from the valve and sensing 

bulb provide partial protection only.

!

WARNING

It  is  recommended  that  the  TXV  bulb  be  installed  parallel  to  the 

ground  (on  a  horizontal  plane).  The  bulb  position  should  be  at                   

2 o’clock or 10 o’clock. Fig. 7B-2 shows the recommended position 

for the TXV bulb installation in the horizontal plane.

The TXV sensing bulb SHOULD be mounted on the suction line ap

-

proximately 6” from the TXV or coil housing using the metal clamp 

provided. In order to obtain a good temperature reading and correct 

superheat control, the TXV sensing bulb must conform to ALL of the 

following criteria:

 

1. The sensing bulb MUST be in direct and continuous 

 

contact with the suction line.

 

2. The sensing bulb should be mounted horizontally on 

 

the suction line.

 

3. The sensing bulb MUST be mounted at the 2 o’clock or         

 

10 o’clock position on the circumference of the suction line.

 

4. The sensing bulb MUST be insulated from outside air.

A properly mounted sensing bulb will prevent false readings caused 

by liquid refrigerant that may have formed inside the suction/vapor 

line. Insulation will protect the sensing bulb from false readings due 

to contact with warm air.

Fig 7B-2.  Recommended location for horizontal TXV bulb mount

Bulb position at

2 o’clock or

10 o’clock

Содержание GBW Series

Страница 1: ...rsonal product or property caused due to installations violating regula tions In absence of local state codes refer to National Elec tric Code NFPA 90A 90B Uniform Mechanical Code WARNING When this unit is installed in an enclosed area such as a garage or utility room with any Carbon Monoxide producing devices i e automobile space heater water heater etc ensure that the enclosed area is properly v...

Страница 2: ...om of the drain pan Fig 4C 1 Since coil is upstream of the blower all drains MUST be trapped or sealed Failure to do so will result in condensate overflow from the drain pan Airmark will NOT be responsible for any damages resulting from failure to follow these instructions CAUTION The drain pan has primary red and secondary white drain connec tions If a secondary drain line is required it should b...

Страница 3: ...and have an out side vapor barrier to prevent formation of condensation 5 Installation Ensure that the unit is adequately sized The tonnage of the outdoor unit should never exceed the tonnage of this unit CAUTION The coil was manufactured with a dry ni trogen pre charge Release the pressure through the Schrader valve test port prior to installation If holding pressure is not present return coil to...

Страница 4: ...ended by the outdoor unit manufacturer whenever pos sible The piston should be sized accord ing to the capacity of the outdoor unit CAUTION Fig 8A 1 Flowrator assembly components Failure to install the proper piston can lead to poor system performance and possible compressor damage WARNING I Installation I 1 Disassemble flowrator body using two wrenches and un screwing with a counterclockwise moti...

Страница 5: ... MUST go into the distributor body towards the coil Failure to ensure this orientation will cause the piston to be bypassed during operation which might damage the outdoor unit CAUTION II 6 Replace the piston with one of the correct size Do not force the new piston into the body Make sure the piston moves freely in body II 1 Evacuate the system as per manufacturer guidelines and rec ommendations I...

Страница 6: ... housing III 1 Disassemble the flowrator body using two wrenches Un screw the body with a counter clockwise motion Ensure that the TXV selected is compat ible with the refrigerant used in the out door system R22 or R410A TXV caps are painted green for R22 or pink for R410A In absence of col or the caps will be marked with the compatible refrigerant CAUTION The sensing bulb and TXV body MUST be pro...

Страница 7: ... port of the TXV A Remove the valve stem from the Schrader port mounted on the suction line B Screw flare nut on TXV equal ization tube on to the Schrader valve stem III 10 Tighten all connections taking care to use proper back up III 12a Some Airmark coils come with a Schrader valve on the suc tion line If a Schrader port is present III 12b In some cases a suction line schrader port may not be pr...

Страница 8: ...lb once the piping has cooled 7 Flow nitrogen through the piping when brazing 8 Braze both refrigerant line connections using proper brazing pro cedures 9 When all line connections are brazed perform a proper system evacuation procedure per the outdoor unit manufacturer instructions 10 Seal the penetration open ings where the lineset piping en ters the air handler cabinet 1 Following outdoor unit ...

Страница 9: ...delay relay will send out a 24 volt signal to the low voltage terminal on the motor See Schematic Fig 22 1 Fan time delay periods are 30 seconds ON delay and 120 seconds OFF delay The Y wire from the thermostat is not connected at the air handler This wire goes directly to the outdoor unit 24 volt wiring to turn on the outdoor condensing unit when a call for cooling takes place The 24 volt common ...

Страница 10: ...d be placed in the return air duct near the entrance to the air handler The factory provided air filter should be in place inside of the air handler 13 Air Volume Adjustment Table 13 1 Fig 13 1 1 Select a starting speed tap from the CFM table The blower motor has selectable speed taps labeled 1 thru 5 Fig 13 2 The speed taps are energized by 24 volts received from the time delay relay When two sta...

Страница 11: ...ge the compressor After installation of the coil refer to the outdoor unit manufacturer for charging techniques and amount of charge If outdoor unit manufacturers charging instructions are unavailable then refer to instructions below to charge the system CAUTION Hot water flowing to the coil should be in the range of 120º 180º F Water at these temperatures can cause first degree burns Use of prope...

Страница 12: ...ter temperature entering the hot water coils is 120 180ºF depending on the amount of heat required by the structure This is done with the unit energized and operating long enough for all temperatures to stabilize After all connections are made start up and check up must be per Table 16 1 CFM Delivered at Various External Statics CFM OUTPUT BTUH TEMP RISE 1 08 Note BTUH output should be computed by...

Страница 13: ...a nently lubricated bearings and do not require further lubrication 7 Air filter replacement An air filter can restrict the airflow of air to the fan coil if it is not cleaned or replaced periodically When replac ing the air filter always replace with the same type and size as origi nally furnished with the unit 4 a Do not store combustible materials or use gasoline or other flammable liquids or v...

Страница 14: ...l pump timer to circulate the hydronic loop independent of the thermostat 1 Noisy Pump System may not be totally purged of air Purge the system again as described in the start up section above 2 T P valve on water heater weeps This normally occurs when a backflow preventer has been installed in the cold water supply line to the water heater An expansion tank may be necessary to correct this proble...

Страница 15: ...15 22 Wiring diagram for GFW models HIGH VOLTAGE disconnect all power sources prior to servicing Failure might lead to safety hazard Fig 21 1 ...

Страница 16: ...16 23 Massachusetts Applicable Installation Diagram ...

Страница 17: ...17 24 Wiring diagram for GBW models HIGH VOLTAGE disconnect all power sources prior to servicing Failure might lead to safety hazard Fig 22 1 ...

Страница 18: ...18 25 Massachusetts Applicable Installation Diagram ...

Страница 19: ...19 ...

Страница 20: ...19 AirMark All Rights Reserved Revised 01 18 19 Subject to change without notice and without incurring obligation 373 Atascocita Rd Humble TX 77396 Phone 281 441 6500 Toll Free 800 423 9007 Fax 281 441 6510 www airmark ac com ...

Отзывы: