background image

Use bolts to secure the unit to a flat, solid floor. 
When mounting the unit on a wall or the roof, make 
sure the support is firmly secured so that it cannot 
move in the event of intense vibrations or a strong 
wind.

Do not install the outdoor unit in pits or air vents

Installing the pipes

Use suitable connecting pipes and equipment for the 
refrigerant R410A.

The refrigerant pipes must not exceed the maximum 

lengths 10m.

Wrap all the refrigerant pipes and joints.

Tighten the connections using two wrenches working 
in opposite directions.

INSTALLER

Humid air left inside the refrigerant circuit can cause com-
pressor malfunction. After having connected the indoor 
and outdoor units, bleed the air and humidity from the 
refrigerant circuit using a vacuum pump.

(1) Unscrew and remove the caps from the 2-way and 3-

way valves.

(2) Unscrew and remove the cap from the service valve.
(3) Connect the vacuum pump hose to the service valve. 
(4) Operate the vacuum pump for 10-15 minutes until an 

absolute vacuum of 10 mm Hg has been reached.

(5) With the vacuum pump still in operation, close the 

low-pressure knob on the vacuum pump coupling. Stop 
the vacuum pump.

(6) Open the 2-way valve by 1/4 turn and then close it 

after 10 seconds. Check all the joints for leaks using 
liquid soap or an electronic leak device.

(7) Turn the body of the 2-way and 3-way valves. Discon-

nect the vacuum pump hose.

(8) Replace and tighten all the caps on the valves.

BLEEDING

INSTALLER

INDOOR

UNIT

Install the drain fitting and the drain hose (for

model with heat pump only)

Condensation is produced and flows from the outdoor unit 

when the appliance is operating in the heating mode. In order 
not to disturb neighbours and to respect the environment, 
install a drain fitting and a drain hose to channel the conden-
sate water. Install the drain fitting and rubber washer on the 
outdoor unit chassis and connect a drain hose to it as shown 
in the figure.

6

Vacuum pump

 

Vacuum pump

Connect to the

indoor unit

Pompa a vuoto

INSTALLING THE OUTDOOR UNIT

Location

Twisting moment (N.m)

35-40

60-65

45

-

50

70

-

75

ø 

ø 

12

19

Diameter (mm)

ø 

ø 

9.52

16

15

-

20

ø 

6

12

12K and  18K unit need to be installed the indoor unit

connection pipe with the "conversion joint"

12K and  18K MODE:

conversion joint

Caution: Installation Must be Performed in Accordance

with the NEC/CEC by Authorized Personnel Only.

Refrigerant fluid direction of flow

3-way valve

2-way valve

Service 
inlet

(2) Turn
(8) Secure

(7) Turn to open fully

(2) Turn

(8) Secure

Valve cap

(6) Open by 1/4 turn

(7) Turn to open fully

(2) Turn

(8) Secure

Valve cap

Содержание GWHD(28)ND3AO

Страница 1: ... e n o i t i d n o C r i A t i l p S g n i t a r e p o e r o f e b y l l u f e r a c l a u n a m s r e n w o s i h t d a e r e s a e l P e c n e r e f e r r o f y l l u f e r a c t i p e e k d n a L A U N A M S R E N W O 66129903295 R E T R E V N I AIRLUX GWHD 28 ND3CO GWHD 28 ND3AO ...

Страница 2: ...AL INFORMATION GENERAL INFORMATION 1 2 3 3 3 4 6 6 7 7 8 9 Technical Data Electrical Connections Installing The Outdoor Unit Maintenance Installation Dimension Diagram Check After Installation Fault Indication Bleeding Conformity And Range The Instructions Befor Use Name Of The Parts Outdoor Unit Working Temperature Range GENERAL INSTALLER INFORMATION Please read this owner s manual carefully befo...

Страница 3: ...switch protection and assure it has enough capacity The unit will be turned on or off according to your requirement automatically please do not turn on or turn off the unit frequently otherwise disadvantage effect may be caused to the unit Rated voltage of this air conditioner 220 240V 60Hz The compressor will vibrate sharply if the voltage is too low resulting in damage to refrigerating system El...

Страница 4: ...utdoor side DB WB 43 26 T1 21 24 18 5 6 OUTDOOR UNIT WORKING TEMPERATURE RANGE GENERAL INFORMATION 1 2 GENERAL INFORMATION 3 220 240V 60 V Hz GWHD 28 ND3AO 1 2 L W H Be sure to cut off the power supply before cleaning the air conditioner otherwise electric shock might happen Wetting of air conditioner may cause the risk of electric shock Make sure not to wash your air conditioner in any case Volat...

Страница 5: ...r unit Fix power connection wire by wire clamp Ensure wire has been fixed well Install the handle cable with the terminal at the row of connection and fix consistent with the indoor unit terminal of line bank ELECTRICAL CONNECTIONS INSTALLER 4 The connection pipes and the connectiong wirings of the unit A unit B and unit C must be corresponding to each other respective The appliance shall be insta...

Страница 6: ...stent with the indoor unit terminal of line bank ELECTRICAL CONNECTIONS INSTALLER 5 The connection pipes and the connectiong wirings of the unit A unit B unit C and unit D must be corresponding to each other respective The appliance shall be installed in accordance with national wiring regulations Do not install the outdoor unit where it is exposed to the sunlight HANDLING After having removed the...

Страница 7: ...by 1 4 turn and then close it after 10 seconds Check all the joints for leaks using liquid soap or an electronic leak device 7 Turn the body of the 2 way and 3 way valves Discon nect the vacuum pump hose 8 Replace and tighten all the caps on the valves BLEEDING INSTALLER INDOOR UNIT Install the drain fitting and the drain hose for model with heat pump only Condensation is produced and flows from t...

Страница 8: ...MENSION DIAGRAM The installation must be done by trained and qualified service personnel with reliability according to this manual Contact service center before installation to avoid the malfunction due to unprofessional installation When picking up and moving the units you must be guided by trained and qualified person Ensure that the recommended space is left around the appliance 7 ...

Страница 9: ...ecified on the nameplate The unit may bread down or the components may be burned out Are the lines and pipelines correctly installed The unit may bread down or the components may be burned out Has the unit been safely grounded Risk of electrical leakage Are the models of lines in conformity with requirements The unit may bread down or the components may be burned out Are there any obstacles near t...

Страница 10: ...indoor middle temp sensor malfunction B unit indoor middle temp sensor malfunction A unit indoor outlet pipe temp sensor malfunction B unit indoor outlet pipe temp sensor malfunction A unit indoor inlet pipe temp sensor malfunction B unit indoor inlet pipe temp sensor malfunction A unit indoor ambient temp sensor malfunction B unit indoor ambient temp sensor malfunction A unit modes conflict B uni...

Страница 11: ...18K 7K 7K 7K 9K 9K 12K 7K 12K 12K 12K 7K 18K 9K 18K 7K 7K 7K 7K 9K 9K 9K 9K 9K 7K 7K 9K 7K 9K 12K 9K 9K 12K 7K 7K 12K 7K 12K 12K 9K 12K 12K 7K 7K 18K 7K 9K 18K 9K 9K 18K 7K 12K 18K 9K 12K 18K 12K 12K 18K 2 models 3 models 4 models 9K 9K 12K 18K 7K 7K 7K 9K 9K 12K 7K 12K 12K 12K 7K 18K 9K 18K 7K 7K 7K 7K 9K 9K 9K 9K 9K 7K 7K 9K 7K 9K 12K 9K 9K 12K 7K 7K 12K 7K 12K 12K 9K 12K 12K 7K 7K 18K 7K 9K 18K...

Отзывы: