3.2.  Intended 

use

Duplexvent

 Flexi-V series ventilation units with heat recovery are intended for the comfort ventilation 

and

 

possibly hot-air heating and cooling of flats and houses, small plants, workshops, schools, 

restaurants,

 

cooking facilities and industrial halls or for similar applications with a basic environment. 

The use of

 

the unit must be in compliance with the Regulation of the Commission (EU) 1253/2014.

4 .

I n s t a l l a t i o n

4.1.  Safety 

instructions

During installation make sure no damage or deformation is caused to the case of the appliance
(e.g. as a result of handling operations).

After setting the appliance in place check it for stability and secure it in this position against
moving.

During handling and installation observe all rules of safe work (including work at heights and work
with suspended loads) and use appropriate work and safety equipment.

Lifting and binding equipment may only be operated by trained personnel.

4.2. 

Hygienic instructions and requirements

If installation is interrupted or heavy dusting occurs, cover all openings of the appliance in such a

 

way so as to ensure that surfaces to be in contact with transported air remain protected against

 

the 

weather and stay clean and dry.

If long-term high relative humidity (short-term more than 90 % or more than 80 % for three

 

consecutive days) is likely to occur with the subsequent moistening of filters (e.g. in areas with

 

frequent fogs, frequent and long rains, flying snow etc.), suitable measures must be taken to

 

prevent microbiologic growth. Recommended measures include more frequent hygienic checks as

 

per VDI 6022 or shorter filter replacement intervals. Another option is the preheating of air using

 

an 

appropriate control devices, or the appliance must be put out of operation for the period when

 

filters are at the risk of moistening (if the type of operation allows this).

Should such weather conditions occur at the site of installation that would cause the dew point to

 

be exceeded in the supply air region of the heat recovery exchanger, or an independent cooling

 

system is installed in ventilated rooms, 

Duplexvent

 Flexi-V units may only be used provided that it

 

has been arranged via appropriate measures that the dew point will not be exceeded in the heat

 

recovery exchanger. The typical weather of central Europe makes this condition almost

 

impossible.

The e1/ODA air supply chamber has no water drain. An accessible and cleanable chamber with a

 

drain of precipitated water must be installed upstream the outdoor air inlet into the appliance.

The HVAC network of appliances operated in an environment with Class ETA 2 extract air must

 

be 

arranged for operation in such a way so that positive pressure is on the supply air side

 

downstream 

the heat recovery unit; in an environment with Class ETA 3 extract air the HVAC

 

network must be 

arranged for operation in such a way so that positive pressure is on the supply

 

side against the 

exhaust side. This must be ensured under all operating conditions of the system.

 

For details see 

EN 13779.

Ü

In compliance with hygienic standard VDI 6022 HVAC systems must be equipped with shut-off

 

dampers to ensure the automatic closure of the system so that no air can flow freely through the

 

system. Shut-off damper of the fresh air supply (ODA) must be thermally insulated. It is

 

recommended using shut-off dampers available as an accessory. It is the responsibility of the

 

planner / specialist installation firm to comply with this requirement.

Ü

Duplexvent

 series appliances have a single-stage filtration system. Appliances in a hygienic version

 

in compliance with hygienic standard VDI 6022 must have at least Class ISO ePM1 50% (F7) filter

 

fitted on the inlet (applies to outdoor air e1/ODA Class ODA 1 and ODA 2). When outdoor air is

 

Class 3, a Class ISO ePM10 50% (M5) filter must be fitted in the duct upstream the outdoor air

 

inlet into the HVAC unit; alternatively, a Class ISO ePM10 50% (M5) filter may be installed in the

 

HVAC unit and a Class ISO ePM1 50% (F7) filter in the duct at the e2/SUP outlet from the unit.

 

Note: air filters ISO ePM10 50% (M5) and ISO ePM1 55% (F7) are separately supplied

 

accessories.

Ü

Appliances in a hygienic version in compliance with hygienic standard VDI 6022 may be operated

 

only if the use of recirculating air is suitable for hygienic reasons or the arrangement of operation

Содержание Duplexvent Flexi-V DV1800

Страница 1: ...Installation use and maintenance manual Installation use and maintenance manual for Duplexvent Flexi V DV500 900 1800 2800 3500...

Страница 2: ...h the design technical conditions specified by the manufacturer and applicable legislation and technical standards in effect The appliance may not be installed and operated in an aggressive environmen...

Страница 3: ...12 4 10 Installing mixing valve of hot water air heater 13 4 11 Installing shut off dampers e1 i1 13 4 12 Installing flexible flanges 13 4 13 Installing and connecting water chiller to the cool sourc...

Страница 4: ...esistance or it must be drained for the period during which outdoor temperature might fall below 5 C We recommend draining water from the chiller with pressurized air not using a gravity flow Applianc...

Страница 5: ...wered fans with flexibly mounted engines a highly efficient heat recovery exchanger assembled from thin walled plastic boards for the recovery of heat cool a by pass damper slide out filters and drain...

Страница 6: ...m is installed in ventilated rooms Duplexvent Flexi V units may only be used provided that it has been arranged via appropriate measures that the dew point will not be exceeded in the heat recovery ex...

Страница 7: ...nel will display the message Orientation is not set 4 Proceed back to the default screen click on the cogwheel in the bottom left corner 5 Click on the Settings symbol in the top right corner 6 Enter...

Страница 8: ...included in delivery 4 pieces in sizes 500 and 900 6 pcs in size 1800 2800 and 3500 Level the appliance horizontally on both longer and shorter side Use adjustable stand feet Adjustable bases must be...

Страница 9: ...g must be firmly connected to extraction ports to achieve a uniform flow rate in the whole cross section of extraction ports A duct being at least 2 m long must be always connected to fan outlets to p...

Страница 10: ...Filter with the class ISO ePM1 55 F7 is the filter of outdoor air and it is placed in the compartment e1 ODA Filter with the class ISO ePM10 50 M5 is the filter of extracted air and it is placed in th...

Страница 11: ...o collection points on the unit s surface using tubes Connect the tube to the top of the manometer and run it to the metal bushing on the unit s surface also see a separate manometer installation manu...

Страница 12: ...tings in both directions Unscrew the FILL plug the top knob and keep filling the machine with measuring liquid included in delivery until the liquid is visible near the zero mark on the scale Use the...

Страница 13: ...tion SW of Duplexvent units tab Controls Wiring diagram 4 10 Installing mixing valve of hot water air heater During the mechanical installation and connection of the mixing valve of the hot water air...

Страница 14: ...rained technician following the separate documentation set included The controls are described in a separate guide on operating the control system The unit is to be protected using a breaker with char...

Страница 15: ...ommissioning if stricter hygienic requirements apply wiping disinfection must be carried out After disinfecting make sure that no toxicologically suspicious or odour active substances enter supply air...

Страница 16: ...arameters including error messages Browse the unit s operational history Set e mail notification with Alarm or Warning messages for up to three e mail addresses You will find more information in the G...

Отзывы: