![Airflow Instruments ProHood PH730 Скачать руководство пользователя страница 35](http://html1.mh-extra.com/html/airflow-instruments/prohood-ph730/prohood-ph730_owners-manual_2876833035.webp)
Chapter 4: Menu Setup and Navigation
27
Data Logging
Measurements
Measurements to be logged to memory are independent of measurements on the display, and must
therefore be selected under
DATA LOGGING
Measurements
.
When set to
ON
, measurement will be logged to memory.
When set to
DISPLAY
, measurement will be logged to memory if it is visible on the main running
screen.
When set to
OFF
, measurement will not be logged to memory.
MENU
Pressure Tool
Display Setup
Flow Setup
Actual/Std Setup
Settings
Data Logging
Bluetooth Functions
Applications
Cf Selection
Calibration
DATA LOGGING
Measurements
Log Mode/Display Mode Manual/RunAvg
Log Settings
Choose Test Test 001
Name Test
View Data
Delete Data
% Memory
MEASUREMENTS
Pressure
ON
Baro Pressure
OFF
Velocity (Pitot)
DISPLAY
Flow (Pitot round duct)
DISPLAY
DISPLAY
ON
Log Mode/Display Mode
The instrument can be programmed to store measurements to memory in several different
logging formats:
Log Mode/
Display Mode
Display
Data Logging
Recommended Usage
Manual/Single
Single
measurement
Single sample initiated
and manually saved by
user
Pressure Tools
Manual/RunAvg
Continuous
measurement
Running average readings
manually saved by user
Pressure Tools
*Default for Capture Hood
tool
Auto-save/RunAvg
Continuous
measurement
Samples are automatically
logged to memory at the
end of the sampling period
Thermoanemometer
Cont-key/Run/Avg
Continuous
measurement
Unattended logging to
track trends
Thermoanemometer,
Pressure Only
Cont-time/RunAvg
Continuous
measurement
Unattended logging to
track trends
Thermoanemometer,
Pressure Only
Содержание ProHood PH730
Страница 2: ......
Страница 8: ...vi This page intentionally left blank...
Страница 14: ...6 Airflow Instruments ProHood Capture Hoods PH730 PH731 This page intentionally left blank...
Страница 28: ...20 Airflow Instruments ProHood Capture Hoods PH730 PH731 This page intentionally left blank...
Страница 50: ...42 Airflow Instruments ProHood Capture Hoods PH730 PH731 This page intentionally left blank...
Страница 62: ...54 Airflow Instruments ProHood Capture Hoods PH730 PH731 This page intentionally left blank...
Страница 66: ...58 Airflow Instruments ProHood Capture Hoods PH730 PH731 This page intentionally left blank...
Страница 70: ...62 Airflow Instruments ProHood Capture Hoods PH730 PH731 This page intentionally left blank...
Страница 74: ...66 Airflow Instruments ProHood Capture Hoods PH730 PH731 This page intentionally left blank...
Страница 78: ...70 Airflow Instruments ProHood Capture Hoods PH730 PH731 This page intentionally left blank...