6.

 

Use in Airways 

In large airways the presence of the instrument will have a negligible 
effect, but in small airways the blockage caused by the instrument, hand 
and arm will cause the airstream to accelerate slightly as it passes the 
rotating vane.  This effect is somewhat variable depending on the size of 
the airway and the distance from the duct walls.  The error can be virtually 
eliminated by mathematical correction to allow for the reduction of free 
area caused by the obstruction.  For this purpose the effective front area of 
the instrument (not including hand or arm) can be taken as 0.019m

2

 

(0.204ft

2

).  The effect can be ignored completely if the duct exceeds about 

500mm diameter (1’ 9”). 

 
 

7.

 

Possible sources of error 

The above method ignores the effects of the reduced velocity at the duct 
walls. A more precise method is shown in BS1042 Part 2.1 Log 
Tchebycheff method.   
 
This procedure is satisfactory for use in ducts, and at unobstructed 
apertures. 
 
Significant errors may occur if the aperture is covered by a grille, 
particularly if this is of the type having adjustable direction vanes and/or 
dampers. The airstream issuing from such a grille is invariably very 
disturbed, consisting of many small areas of high velocity interspersed with 
areas of low velocity. 
 
The transitions between these areas are highly turbulent, and there may 
even be some reversed flow. If maximum accuracy is required, it is 
advisable to make up a short length of test ducting which is just larger than 
the overall dimensions of the grille. This duct can be of any convenient 
rigid material (eg stiff cardboard) and should have a length about twice the 
diagonal measurement of the grille. The duct should be placed over the 
grille, and sealed to the wall with adhesive tape. Measurements of flow can 
now be conducted, as already described, at the unobstructed end of the test 
duct. Use the cross sectional area of the duct (not the grille) for the 
calculations. 
 
It should be noted that using an AV30 instrument to take spot readings 
across a duct as described earlier can result in an exaggerated velocity 
indication in applications where there is a significant variation in velocities 
across the test area. This is caused by the inability of the rotating vane to 

Содержание AV 30

Страница 1: ...1 AV30 OPERATING INSTRUCTIONS Please read these instructions carefully before using the instrument Shortform instructions appear on the back of the instrument 9021435 A 0805...

Страница 2: ...DC offset which should be taken into account when taking readings The cable connected to the 0 1 volt output should not be more than 3 metres long 2 BATTERY INFORMATION 2 1 The AV30 is supplied with...

Страница 3: ...battery symbols at both ends of the top line of the display The instrument will still operate correctly but only for a limited time so the batteries should be replaced as soon as possible Also use of...

Страница 4: ...to 100 in steps of ten Use the and keys to select the level of averaging desired then press the key to confirm selection 3 1 5 Backlight Turns on and off the screen backlight press the key to toggle...

Страница 5: ...e Comments under section 7 Possible sources of error Avoid intrusion of the hand arm or handle of the instrument into the face area of the grille The blockage effect created by this would cause artifi...

Страница 6: ...lle particularly if this is of the type having adjustable direction vanes and or dampers The airstream issuing from such a grille is invariably very disturbed consisting of many small areas of high ve...

Страница 7: ...G ALTERING THE CALIBRATION WILL INVALIDATE TSI INSTRUMENTS LTD RESPONSIBILITY FOR CALIBRATION UNDER WARRANTY The unit will monitor each time the calibration is effected If the calibration routine is i...

Страница 8: ...ephone 001 651 490 2811 Fax 001 651 490 3824 WWW http www tsi com The statements and opinions contained in this document are made in good faith Whilst every effort has been made to provide reliable in...

Страница 9: ...ding 1 digit Volume Flow Ranges Accuracy 35mm Head 0 02 1800 m sec 2 1 800 000 l sec 2 6 480 000 m3 hr Calibrated to better than 2 of reading 1 digit 2 3 700 000 ft3 min Calibrated to better than 2 of...

Страница 10: ...tandards EN50081 1 Radiated Emissions and EN50082 1 Radiated and ESD Immunities QUALITY ASSURED TO ISO 9001 TSI Instruments Ltd August 2005 Lancaster Road Part No 9021435 Rev A Cressex Business Park H...

Отзывы: