![AIREDALE TCC11R04S-30 Скачать руководство пользователя страница 109](http://html.mh-extra.com/html/airedale/tcc11r04s-30/tcc11r04s-30_technical-manual_2876555109.webp)
Technical Data
Ecodesign - TCF (R)
Notes: Units
TCF1
1R06S-42
TCF1
1R08S-42
TCF1
1R06L-43
TCF1
1R08L-44
TCF1
1R10L-45
TCF12R08S-46
SEPR
1,3,5
8.6
8.8
7.6
7.8
8.4
6.8
SEPR Tier
Tier 2
(2021)
Tier 2
(2021)
Tier 2
(2021)
Tier 2
(2021)
Tier 2
(2021)
Tier 2
(2021)
Annual Electricity Consumption
kWh/a 223034.9 235657.7 354220.6 379081.4 358036.4 477315.2
Rated Refrigerant Capacity P
A
1,3,5
kW
259.5
279.5
364.4
399.4
404.4
439.3
Rated Power Input D
A
kW
80.4
84.9
133.8
150.1
137.3
147.3
Rated EER
DC,A
3.23
3.29
2.72
2.66
2.94
2.98
Declared Refrigerant Capacity P
B
1,3,5
kW
242.2
260.8
340.0
372.7
377.4
410.0
Declared Power Input D
B
kW
53.1
55.5
85.5
92.2
86.0
98.1
Declared EER
DC,B
4.56
4.70
3.98
4.04
4.39
4.18
Declared Refrigerant Capacity P
C
1,3,5
kW
224.8
242.1
315.7
346.1
350.4
380.7
Declared Power Input D
C
kW
34.4
36.1
54.4
57.9
54.5
63.0
Declared EER
DC,C
6.53
6.70
5.81
5.98
6.43
6.04
Declared Refrigerant Capacity P
D
1,3,5
kW
207.5
223.5
291.4
319.4
323.4
351.3
Declared Power Input D
D
kW
12.5
13.5
19.8
21.1
20.2
35.8
Declared EER
DC,D
16.58
16.61
14.75
15.14
15.97
9.80
SSCEE
2,3,5
%
1.9
2.0
1.7
1.9
2.0
1.9
SSCEE Tier
Tier 2
(2021)
Tier 2
(2021)
Tier 2
(2021)
Tier 2
(2021)
Tier 2
(2021)
Tier 2
(2021)
Rated Cooling Capacity P
rated,c
2,4,5
kW
260.0
280.0
365.0
400.0
405.0
440.0
Declared Cooling Capacity 35°C Pdc 2,3,5
kW
259.5
279.5
364.4
399.4
404.4
439.3
Declared EER
d
35°C
3.23
3.29
2.72
2.66
2.94
2.98
Declared Cooling Capacity 30°C Pdc 2,3,5
kW
191.1
205.8
268.3
294.1
297.8
323.5
Declared EER
d
30°C
4.28
4.50
3.75
3.97
4.25
3.83
Declared Cooling Capacity 25°C Pdc 2,3,5
kW
122.7
132.1
172.3
188.9
191.2
207.8
Declared EER
d
25°C
5.57
5.86
4.76
5.20
5.50
5.47
Declared Cooling Capacity 20°C Pdc 2,3,5
kW
68.9
69.2
127.6
125.9
124.8
69.1
Declared EER
d
20°C
6.41
6.49
6.07
6.62
6.78
6.18
Sound Power Level
dB(A)
87
87
90
90
89
91
Air Volume
m³/h
102219
120542
123975
164183
175352
159198
Off mode P
OFF
kW
0.249
0.249
0.249
0.249
0.249
0.249
Thermostat-off mode P
TO
kW
1.781
1.965
2.777
2.428
2.639
2.953
Standby Mode P
SB
kW
0.330
0.340
0.350
0.340
0.350
0.360
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
0.000
0.000
0.000
Ec
od
esi
gn
109
Chiller Technical Manual 9635376 V1.0.0_01_2019
Chillers
TurboChill™ R513A Air Cooled and FreeCool
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside configuration.