Precision Air Conditioning
SmartCool
TM
– D
Precision Air Conditioning
71
Installation, Maintenance and Commissioning Manual :6877419 02/2013
Electrical Data – X2X2 Continued
SC25D080-X2X2
SC25D090-X2X2
SC25D100-X2X2
Standard Condenser Match -
2 x CR65
2 x CR65
2 x CR80
Unit Data Full Function - X2X2
(1)
Nominal Run Amps
A
90.5
89.9
100.7
Maximum Start Amps
A
177.3
169.1
213.7
Recommended Mains Fuse Size
A
125
125
125
Max Mains Incoming Cable Size
mm²
70
70
70
Mains Supply
V
400V / 3PH + N / 50Hz
Control circuit
VAC
24
24
24
Unit Data Cooling Only – X2X2
Nominal Run Amps
A
74.3
73.7
84.5
Maximum Start Amps
A
161.1
152.9
197.5
Recommended Mains Fuse Size
A
100
100
100
Evaporator Fan - Motor - Per Fan
Motor Type
AC
AC
AC
Quantity x Motor Size
(2)
kW
3 x 2.38
3 x 2.38
3 x 2.38
Full Load Amps
A
5
5
5
Locked Rotor Amps
A
17.5
17.5
17.5
Compressor 1 , Circuit 1 & 2
(3)
Motor Size
kW
6.31
7.19
7.19
Nominal Run Amps
A
13.27
12.87
12.87
Locked Rotor Amps
A
100
92
92
Type of Start
Direct On Line
Compressor 2, Circuit 1 & 2
(3)
Motor Size
kW
6.31
7.19
9.46
Nominal Run Amps
A
13.27
12.87
16.93
Locked Rotor Amps
A
100
92
130
Type of Start
Direct On Line
Standard Condenser Match - AC Motor Per Fan
Quantity x Motor Size
kW
2 x 0.6
2 x 0.6
3 x 0.6
Full Load Amps
A
2.62
2.62
2.62
Electric Heating
Stage of Reheat
2
2
3
Number of Elements
6
6
9
Rating (Total)
kW
21
21
31.5
Current Per Phase
A
30.31
30.31
45.47
Humidifier
Capacity
kg/hr
15
15
15
Rating
kW
11.25
11.25
11.25
Full Load Amps
A
16.2
16.2
16.2
Standard Size Fan Motor - EC Motor –Per Fan
Quantity x Motor Size
kW
2 x 2.2
2 x 2.2
2 x 2.2
Full Load Amps
A
3.3
3.3
3.3
Locked Rotor Amps
A
3.3
3.3
3.3
Larger Size Motor - EC Motor - Per Fan
Quantity x Motor Size
kW
2 x 3.1
2 x 3.1
3 x 3.1
Full Load Amps
A
4.8
4.8
4.8
Locked Rotor Amps
A
4.8
4.8
4.8
Standard Condenser Match - EC Motor-Per Fan
Quantity x Motor Size
kW
2 x 0.73
2 x 0.73
3 x 0.73
Full Load Amps
A
3.3
3.3
3.3
SCAF Condenser Match - Motor-Per Fan
Quantity x Motor Size
kW
2 x 1.4
2 x 1.4
3 x 1.4
Full Load Amps
A
6
6
6
(1) Values given for function units with standard selections for heating, humidification, supply air fans and matched condenser
at 7°C evaporating and 54.4°C condensing
(2) Stated motor power is based on maximum electrical power absorbed
(3) Values are per compressor
X
2
X
2