CU/CFCU
Condensing Units
16
Condensing Units
Installation & Maintenance Manual : 6259626 IM V1.6.0 04/16
Electrical Information
ELECTRICAL DATA - CFCUS 5
– 10
5
6
7.5
10
Unit Data
Nominal Run Amps
(1)
A
14.0
16.1
19.3
24.5
Maximum Start Amps
A
91.7
124.2
119.9
168.3
Control Circuit
VAC
24
24
24
24
Mains Supply
V
400/3/50
Rec. Mains Fuse
A
25
32
35
40
Max Incoming Mains
mm²
10
10
10
10
Compressor
Motor Rating
kW
4.50
5.90
8.14
9.70
Nominal Run Amps
(1)
A
8.90
11.00
12.73
16.10
Locked Rotor Amps
A
62.50
95.00
98.00
120.00
Crankcase Heater Rating
W
65
65
50
50
Type of Start
Direct on Line
Condenser Fan
Motor Rating
kW
2.20
2.20
3.00
4.00
Full Load Amps
A
5.10
5.10
6.70
8.40
Locked Rotor Amps
A
29.15
29.15
41.40
48.30
(1)
Nominal data based on 5
C evaporating temperature and a 30
C ambient.
INTERCONNECTING WIRING
Microprocessor
Controlled (AD05)
L1
N
Mains Incoming 230/1/50
E
S1A
Communication Connection
S1B
To Indoor Unit (Microprocessor Only)
COOL
COM
HEAT
External Control of Cool/Heat mode (Volt Free)
(1)
A3
Optional Auxiliary Alarm
A3
Volt Free Input (Normally Closed = Healthy)
DS1
Defrost Status Indication
DS2
Volt Free Contact (Normally Closed = Defrosting)
CCA
Common
CA1
Normally Closed Contact
CONDENSING UNIT
CA2
Normally Open Contact
Common Alarm Changeover
Volt Free Contacts
System Field
Connections for AD05
Controlled Units
L1
L1
N
N
E
E
S1A
S1A
INDOOR UNIT
S1B
S1B
AD05 CONTROLLED
OUTDOOR UNIT
(1)
The microprocessor (AD05) controlled condensing unit may be matched to non
Airedale indoor air handling units.
A contact can be closed across either the Cool and Common or Heat and
Common terminals. Ensure that the cooling and heating cannot be
initialised simultaneously.