Therm-X MVHRU HRFL II
Technical Manual
Page 34 of 46
Version 2.3, 24/06/2020
PLEASE NOTE:
-
The heater is supplied as a standalone product
-
Heater supplied loose for fitting and wiring on site by others
-
Power and control to the heater must be provided by an external source
-
The Therm-X integral control panel is capable of modulating the heater output and guarantees that it only
operates when airflow is present. It also ensures the heater is cooled down when the unit is turned off. All other
emergency and safety functions (minimum airflow, high temp limit, etc....) must be ensured by an external control
system.
-
A duct temperature sensor supplied with the heater must be installed downstream by others to allow the Therm-
X unit or other controller to modulate the heater
-
It is possible to control the heater from the Therm-X unit controller in certain scenarios, contact our office for
more information
-
Heater not suitable for external installation
-
For additional information please consult the
Therm-X MVHRU Accessories Technical Manual