AIREDALE AIR 1-550.30 Скачать руководство пользователя страница 5

AIR 1-550.30

water systems, include a balancing valve in return line for 

water flow regulation. A drain valve should also be provided 

below each unit heater to allow removal of water from the 

heating coil if located in an area subject to freezing.

3.  In steam or hot water systems, rapid air removal is required 

because entrained air is a cause of corrosion. Hot water 

systems should be equipped with suitable air vent valves for 

rapid and complete removal of air at the high points and ends 

of both supply and return mains. Proper air venting for steam 

systems can be achieved by use of a steam trap with an 

internal air vent.

4.  Traps must be located below the outlet of the unit. Consult 

trap manufacturer for specific recommendations. Each steam 

unit heater should be provided with a trap of sufficient size 

and capacity to pass a minimum of two times the normal 

condensate released by the unit at the minimum differential 

pressure in the system. Trap capacity is based on the 

pressure differential between supply and return mains. Steam 

systems should be equipped with a float and thermostatic trap 

or an inverted bucket trap with an air bypass.

5.  It is advisable to use a pipe line strainer before each steam 

trap draining a unit heater. This protection will reduce the 

maintenance of the steam trap. When strainers are used they 

should be installed between the unit heater and the trap and 

be the same size as the trap tapping. In order to catch dirt 

and scale, the strainer should have a screen perforation size 

smaller than the trap orifices.

6.  On systems where the steam supply to the unit heater is 

modulated or controlled by a motorized valve, a vacuum 

breaker should be installed between unit outlet and the trap. 

If a vacuum breaker is used, it should be in conjunction with a 

float and thermostatic trap.

7.  Install a scale pocket at bottom of unit heater to collect dirt 

and scale as shown in illustrations. Pipe diameter must be the 

same size as unit connections and about 6" long.

8.  Provide adequate pipe hangers, supports, or anchors to 

secure the piping system independently of the unit heater.

Electrical Connections

1.  Installation of wiring must conform with local building codes, 

or in the absence of local codes, with the National Electric 

Code ANSI/NFPA 70 - Latest Edition. Unit must be electrically 

grounded in conformance to this code. In Canada, wiring must 

comply with CSA C22.1, Electrical Code.

Figure 5.1 - Unit Suspension

UNIT SUSPENSION / INSTALLATION

 WARNING

1.  Disconnect power supply before making wiring connections 

to prevent electrical shock and equipment damage.

2.  All appliances must be wired strictly in accordance with 

wiring diagram furnished with the appliance. Any wiring 

different from the wiring diagram could result in a hazard 

to persons and property.

3.  Any original factory wiring that requires replacement must 

be replaced with wiring material having a temperature 

rating of at least 105°C.

4.  Ensure that the supply voltage to the appliance as indicated 

on the serial plate is not 5% greater than the rated voltage.

5

 CAUTION

1.  Do not install units below 8 feet measured from the bottom  

  of the unit to the floor.
2.  Do not reuse any electrical component which has been  

  wet. Replace component.
3.  Ensure that the supply voltage to the appliance, as indicated  

  on the serial plate is not 5% less than the rated voltage.

Piping - See Figure 6.1

1.  Branch piping to and from unit heater should include swing 

joints to allow for expansion and contraction of the piping 

without placing a strain on the unit heater element. On steam 

systems, the branch piping should be taken off and returned 

above the centerline of the supply and return lines.

2.  Install pipe unions and shut-off valves in lines to and from 

each unit heater to allow maintenance or replacement of unit 

without shutting down and draining entire system. For hot 

UNIT SUSPENSION

Horizontal delivery units, Model WTC/WSC Series.

 All 

horizontal delivery units, except Models WTC 18 and WTC 24, 

have two tapped holes in the top for unit suspension. WTC 18 

and WTC 24 models do not require independent suspension and 

are installed directly on their supply piping. Models WTC 33-86 

and WSC 18-86 have 3/8"-16 tapped holes, model sizes 108 

and larger have 1/2"-13 tapped holes. Piping support hangers 

or clamps are recommended and should be placed as close 

to the unit heater as possible. For other models, independent 

suspension can be made with threaded rods, pipes, or ceiling 

hanger brackets. See Figure 5.1.

Vertical delivery units. 

Vertical delivery Models WVC/WVN 

42 through WVC/WVN 279 have four tapped holes (1/2"-13) 

in the top cover for unit suspension. Unit suspension for these 

models can be made with threaded rods, pipes or ceiling hanger 

brackets. Models WVC/WVN 333 through WVC/WVN 952 are 

equipped with an angle-iron mounting bracket that has eight 5/8" 

diameter hanger holes permitting hook-hoisting and suspension 

with cables, if desired. A 1/2" x 3" center U-bolt can be inserted 

in the two holes at each end of the bracket to accommodate 

suspension with four threaded rods, pipes or hanger brackets.

“Power-Throw” horizontal delivery units. 

“Power-Throw” 

units are designed for horizontal air delivery and are equipped 

with hanger brackets for suspension. Three hanger brackets are 

supplied for Model WPC/WPN 279, one on the front, and two 

on the rear panel for three-point suspension. Only two hanger 

brackets are furnished on the front panel of Models WPC/WPN 

333 through WPC/WPN 952 (for required four-point suspension 

use the two hanger brackets on the front panel and the two 

holes on the ends of the upper angle supports at the rear of the 

unit). Each hanger bracket has a 5/8" diameter mounting hole 

for hook-hoisting and suspension with threaded rods, pipes, or 

cables.

Note: 

A pipe hanger adapter kit as illustrated in Figure 5.1 

is available as an accessory from Modine. The kit consists of 

two drilled 3/4" I.P.S. pipe caps and two capscrews to facilitate 

threaded-pipe suspension. One kit will mount applicable WTC or 

WSC models, two kits are required for WVC/WVN models.

WVC/WVN 42 Thru WVC/WVN 279

WSC 18 Thru WSC 340

WTC 33 Thru WTC 340

Threaded Pipe

Suspension

Method

Threaded Rod

Suspension

Method

Pipe Hanger

Adapter Kit

WVC/WVN 333 Thru WVC/WVN 952

Содержание AIR 1-550.30

Страница 1: ... rating for national electric code ignition temperature rating T3B for grain dust Motors are designed for continuous duty They can operate in a maximum ambient temperature of 104 F 40 C The unit heaters are listed by the Canadian Standards Association as certified and Canadian Registered heat exchangers CRN OH 9234 5C Does not apply to WVC WPC 952 Steam horizontal and vertical delivery unit heater...

Страница 2: ... atmosphere WARNING 1 Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage 2 All appliances must be wired strictly in accordance with wiring diagram furnished with the appliance Any wiring different from the wiring diagram could result in a hazard to persons and property 3 Any original factory wiring that requires replacement must be replaced wi...

Страница 3: ...re listed in Table 4 1 and the height dimensions are shown in Figures 4 3 through 4 7 Maximum mounting heights for vertical models are given for units with or without optional air deflectors The data in Table 4 1 is based on operating conditions of 2 lbs steam or 220 F entering water with 60 F entering air When operating conditions are other than those above refer to Figure 4 2 for maximum mountin...

Страница 4: ...m pressures other than 2 pounds or with water at other than average temperature of 220 F Table 4 1 Maximum Mounting Heights UNIT MOUNTING Figure 4 2 Maximum Mounting Heights Correction Factors H Figure 4 6 Vertical Truncone Horizontal Type Power Throw Type Vertical Type with Deflectors No Deflector Cone Jet Truncone Louvers Model No Height ft Model No Height ft Model No Height ft Height ft Height ...

Страница 5: ...5 greater than the rated voltage 5 CAUTION 1 Do not install units below 8 feet measured from the bottom of the unit to the floor 2 Do not reuse any electrical component which has been wet Replace component 3 Ensure that the supply voltage to the appliance as indicated on the serial plate is not 5 less than the rated voltage Piping See Figure 6 1 1 Branch piping to and from unit heater should inclu...

Страница 6: ...nd must be connected according to wiring diagram with each controller Prior to Operation 1 Make sure fuses are installed in fused disconnect switches 2 Check all electrical connections to assure they are secure 3 Check rigidity of unit mounting Tighten all fasteners if necessary 4 Inspect piping strainers traps fittings etc Initial Start Up 1 Set thermostat to lowest position 2 Turn on power suppl...

Страница 7: ...ptional Casings Electrostatically applied gray green polyester powder coat paint finish is applied over rust and corrosion treated steel for long life Motor Cooling Cone Shields motor from coil heat prolongs life of insulation windings and lubricant Prolongs motor life Coil Aluminum fins mechanically bonded to tubes for maximum heat transfer All steam and water carrying passages between heavy stee...

Страница 8: ...15 112 631 1 1 2 1 140 WPC 952 952 000 3 967 21 145 12 170 2 321 139 985 2 1 140 Vertical Delivery WVC WVN 42 42 000 175 11 15 17 11 950 825 103 43 1 30 1 050 WVC WVN 59 59 000 246 14 19 21 14 1 155 1 005 111 61 1 30 1 050 WVC WVN 78 78 000 325 15 20 23 15 1 590 1 065 109 81 1 15 1 050 WVC WVN 95 95 000 396 15 20 23 15 1 665 1 120 118 98 1 15 1 050 WVC WVN 139 139 000 579 18 24 27 18 2 660 1 285 1...

Страница 9: ... 53 5 040 805 94 214 1 2 1 075 WTC WSC 340L 255 000 1 063 23 53 5 575 775 102 264 1 2 1 075 Power Throw WPC WPN 610L 470 000 1 958 22 154 2 400 2 445 97 486 1 1 2 1 140 Vertical Delivery WVC 42L 33 000 138 13 17 20 13 960 835 94 34 1 30 1 050 WVC 59L 44 000 183 16 22 24 16 1 190 1 035 96 45 1 30 1 050 WVC 78L 62 000 258 19 26 29 19 1 740 1 070 95 65 1 15 1 050 WVC 95L 71 000 296 19 26 29 19 1 760 ...

Страница 10: ... 279 192 300 20 0 0 2 4 5 60 0 17 108 5 460 2 165 94 1 2 1 075 WPC WPN 333 238 500 24 8 0 4 4 5 100 0 18 117 5 980 2 165 99 3 4 1 140 WPC WPN 385 276 100 28 8 0 6 4 5 100 0 18 124 7 680 1 860 95 1 1 140 WPC WPN 500 358 000 37 3 0 5 6 0 100 0 19 138 10 390 2 520 93 1 1 2 1 140 WPC WPN 610 450 400 46 9 1 0 6 0 100 0 22 151 11 750 2 315 97 1 1 2 1 140 WPC 952 721 600 75 2 1 1 14 0 200 0 23 150 12 166...

Страница 11: ... 89 1 2 1 075 WTC WSC 290L 161 100 16 8 3 7 2 5 70 0 25 57 5 040 800 89 1 2 1 075 WTC WSC 340L 200 900 20 9 6 6 2 5 70 0 25 57 5 575 760 93 1 2 1 075 Power Throw WPC WPN 610L 344 900 35 9 0 6 6 0 100 0 24 158 12 400 2 445 86 1 1 2 1 140 Vertical Delivery WVC 42L 23 000 2 4 0 4 0 5 10 0 14 18 21 14 960 835 83 1 30 1 050 WVC 59L 32 600 3 4 0 3 0 8 15 0 17 23 25 17 1 190 1 035 86 1 30 1 050 WVC 78L 4...

Страница 12: ... 34 WSC 47 15 17 1 2 8 3 4 8 12 1 4 11 3 5 8 6 10 3 4 12 35 WSC 63 18 1 2 21 1 2 8 3 4 8 12 3 4 15 3 5 8 6 14 3 4 12 48 WSC 86 18 1 2 21 1 2 8 3 4 9 12 3 4 15 3 5 8 6 14 3 4 14 52 WSC 108 22 1 2 25 1 2 9 1 2 8 11 1 2 18 3 5 8 6 3 8 18 3 4 18 74 WSC 121 22 1 2 25 1 2 9 1 2 7 1 2 11 18 3 5 8 6 3 8 18 3 4 18 76 WSC 165 26 1 2 29 1 2 9 1 4 9 1 2 14 21 1 4 3 5 8 6 3 8 22 3 4 22 92 WSC 193 30 1 2 32 1 2...

Страница 13: ... 1 1 2 1 70 WVC WVN 161 34 3 4 8 3 8 18 3 8 2 1 8 3 19 1 2 19 1 1 2 1 80 WVC WVN 193 34 3 4 9 7 8 18 3 8 2 1 8 3 19 1 2 19 1 1 2 1 86 WVC WVN 212 34 3 4 12 7 8 18 3 8 2 1 2 3 19 1 2 19 2 1 1 4 94 WVC WVN 247 34 3 4 12 7 8 18 3 8 2 1 2 3 21 1 2 21 2 1 1 4 108 WVC WVN 279 34 3 4 14 3 8 18 3 8 2 1 2 3 21 1 2 21 2 1 1 4 112 WVC WVN 333 43 1 4 14 5 8 31 1 2 2 7 8 3 1 8 22 1 2 18 1 5 22 2 1 2 1 1 2 166 ...

Страница 14: ...otor damage Check plant voltage conditions A separate manual starter with thermal overload protection device is recommended for those units that do not have motors with built in overload protection Coils 1 Clean coil at least once a year more often under unfavorable conditions Unless coil is kept reasonably free of dirt lint and grease its original heating capacity will be reduced possibly to a se...

Страница 15: ...ing in too high air temperature 6 Restricted air flow due to clogged coil or closed louvers 7 Fan out of balance 8 Unbalanced voltage on 3φ power Coil Failure Unit Leaks 1 Severe internal corrosion from feedwater 2 Type of boiler treatment 3 Entrained air causing water hammer 4 Continuous operation above 150 PSI 375 F steam systems 5 Loose connection Table 15 1 Troubleshooting Replacement Parts Wh...

Страница 16: ...UIPMENT MANUFACTURED BY BUYER BUYER S REMEDY FOR BREACH AS LIMITED HEREIN SHALL BE LIMITED TO ONE YEAR FROM DATE OF SHIPMENT FROM SELLER FOR GAS FIRED PRODUCTS INSTALLED IN HIGH HUMIDITY APPLICATIONS AND UTILIZING STAINLESS STEEL HEAT EXCHANGERS BUYER S REMEDY FOR BREACH AS LIMITED HEREIN SHALL BE LIMITED TO TEN YEARS FROM DATE OF SHIPMENT FROM SELLER These warranties are issued only to the origin...

Отзывы: