Airec Cross 30 Скачать руководство пользователя страница 2

 

 

20

16

-0

4-

29

 

The maximum allowable connection loads given below are valid 
for low cycle fatigue. If high cycle fatigue is involved, a special 
analysis should be carried out. The following limits for moment 
should not be exceeded.

 

 

Max. Bending moment 

Torque moment 

Connections 

20 Nm 

70 Nm 

 
 
 
 
 
 

Maximum moments onto connections

 

System assembly 

The Cross 30 may be installed as a single module or in a system 
including several Cross 30 units. In systems, the Cross 30 units 
can be mounted in parallel or serial configuration for liquid flow 
and gas flow. To obtain the calculated performance, it is im-
portant that heat exchangers are installed in accordance with 
the configuration in AirecCalc. See the calculation report. Note: 
Wrongly installed piping will jeopardize the performance of the 
installation.

 

 

Flow direction may be:

  

Cocurrent

 = fluids flow in the same direction through the heat 

exchanger 
or 

Countercurrent

 = fluids flow in opposite directions through the 

heat exchanger.  

 

 
 
 

              

 

 
 
    

             

Countercurrent                                              Cocurrent

 

Housing the Cross 

The Cross design has open sides to allow gas to enter and 
leave. It must have a housing to be functional. The Cross heat 
exchanger must be mounted in the housing according to the 
Cross design guidelines.  
When mounting the Cross in the housing, treat the heat 
exchanger with care. Do not use excessive force, or bend or 
weld the heat exchanger. Never expose the housing to 
excessive pulsations (i.e. cyclic pressure or temperature 
changes) or vibrations, because there is a risk that these are 
transferred to the Cross heat exchanger unit. If there is any risk 
of excessive pulsation or vibration, install vibration absorbers / 
muffler on the housing. 
The water connections should not be directly welded to the 
housing, because thermal expansion may cause severe damage 
to the heat exchanger. Material deformation due to differences 
between the internal and external pressures may also damage 
the heat exchanger

.  

Operating conditions 

The Cross is used with a liquid on the circuit with connections 
and a gas on the open side. The heat exchanger must operate 
in line with approved design parameters: temperatures, 
pressures and flow rates. 

 
Liquid side

 

Typical medias are ethylene/propylene glycol, thermal oil, water 

or other liquid non-corrosive to stainless steel. It is important 
that the liquid is of good quality without contamination or 
corrosive substances. The medias should not contain particles 
or any other undissolved matter, we recommend that a strainer 
with a size of 16-20 mesh (

number of openings per inch) 

is 

installed before the Cross 30. The particles could otherwise 
block the channels, causing bad performance, increased 
pressure drop and the risk of boiling. 
Systems with water or another evaporating liquid must be 
equipped with the necessary bleed valve mounted in a position 
higher than the heat exchanger. Air/gas inside the liquid 
channels will reduce heat transfer and water circulation, which 
also could cause boiling. 
The liquid flow must be constant and with sufficient pressure to 
keep its evaporating/boiling temperature above the plate 
temperature. Local evaporation/boiling will adversely affect 
heat transfer and water circulation, and may lead to a risk of 
serious damage to the heat exchanger. Note: The pressure at 
the coolant outlet must be high enough to avoid boiling. 
 
The Cross must always have the cooling fluid circulating fully 
before the hot gas enters the heat exchanger. 
The coolant must NEVER be allowed to freeze. 
Never expose the Cross heat exchanger to excessive liquid 
pulsations (i.e. cyclic pressure or temperature changes). 

 
Gas side 

The gas media should not be corrosive to the heat exchanger.

 

The gas flow must be started after, or simultaneously to, the 
start of the liquid flow. If the liquid flow is interrupted, the gas 
must be stopped or caused to by-pass the Cross heat 
exchanger to avoid boiling on the liquid side.  
The Cross heat exchanger must not be operated in such a 
manner that stagnant condensate is allowed to accumulate.

 

Never expose the Cross heat exchanger to excessive gas 
pulsations (i.e. cyclic pressure or temperature changes). 
The heat exchanger must NEVER be operated without a coolant 
flow.  

 

Operational start-up 

Make sure that:  

-

 

If there is a risk of high temperatures, the unit is insulated as 
a precaution to avoid injuries. 

-

 

Installation has been carried out according to the flow 
schedule / drawing and recommendations. 

-

 

Connections are tight. 

-

 

No vibrations or pulsations are transferred to the Cross 30. 

-

 

The liquid side is filled and deaerated. 

-

 

The flow rate and pressure on the liquid side are correct 
before gas flow is started. 

-

 

The temperature and flow rates are according to 
specification. 

-

 

There is appropriate drainage to deal with any condensation. 
 

Maintenance 

The Cross has no moving parts or electrical components. 
 
The following should be inspected regularly: 

-

 

Operational design conditions for the system being 
maintained, and meeting the calculated / design values 
(leaving temp., pressure drop).  

-

 

Increased pressure drop and decreased thermal efficiency 
over time are signs of possible fouling. 

-

 

Connections for tightness.  

-

 

Gas channels for accumulated dirt. 

-

 

Plate surfaces for corrosion. 

-

 

Seal and gaskets. 

-

 

External components such as valves, dampers and controls. 
 

 

Gas 

Gas 

Liquid 

Liquid 

Отзывы: