Installation and Maintenance Manual 

Cross product family 

 

General information

 

The Airec Cross exchanger is an asymmetric brazed plate heat 
exchanger consisting of stainless steel plates brazed together 
with copper or nickel. The Cross design has open sides to allow 
gas to enter and leave. It must have a housing in order to be 
functional.

 

 
 
 
 

 

 

Principle sketch of Cross 30  

 

Denomination / Product identification

 

All Airec heat exchangers are equipped with an adhesive label 
that includes information about the unit. 
 

 

 Cross 30-C-140 

 

Product type: Cross 30 

 

Brazing material: N (nickel) / C (copper) 

 

Number of plates: 140

 

 Item number 

 Serial number

 

 Operating conditions: 

 

TS: Material temperature min/max 

 

PS: Operating pressure min/max bar (a) side A at max 

 

temperature 

 

PT: Test pressure Side A 

 

Volume: side A (Litre) 

 

Fluid group: according to approving organization 

 Pressure vessel classification 

 Label for CE-certified item 

Pressure vessels

 

The Cross product type is manufactured according to the 
European Directive for Pressure Equipment (PED 97/23/EEC). 
Note: The gas temperature may be considerably higher than 
the material temperature provided there is sufficient coolant 
temperature and flow. 
For divergent operating conditions, please contact Airec. 
For approved units, the data on the label must not be exceeded 
under any circumstances. The heat exchangers are designed for 
use with fluids according to groups 1 and 2 in PED 97/23/EEC. 
For operating conditions relating to the European approval PED, 
please see Product sheets on www.airec.com. For more infor-
mation about approvals, please contact Airec. 

Installation

 

 

Personal protection

 

Suitable protective clothing, i.e. goggles, gloves and shoes, must 
be worn during the installation and/or maintenance of heat 
exchangers. Caution: filled heat exchangers may be heavy; heat 
exchangers may be hot from high-temperature operation; 
condensate may be corrosive/caustic.

 

Mounting the Cross 

The Cross 30 can be installed with either vertical or horizontal 
gas flow. 

 

 

 

 

                              

Horizontal gas flow                                         Vertical gas flow 

Note: For condensing applications, installation must be vertical 
with the gas flow from the top and down through the heat 
exchanger. Condensate is then collected under the heat 
exchanger.

 

Never expose Cross heat exchangers to excessive pulsations 
(i.e. cyclic pressure or temperature changes). It is also important 
that no vibrations are transferred to the unit. If there is a risk of 
this, install vibration absorbers / muffler. If the installation 
allows, it is also suggested that a buffer is installed between the 
Cross and the support. 
 
Whether the heat exchanger is mounted with horizontal or 
vertical gas flow, it must be fully supported. 

 

    

        

     

Support from the bottom

 

 

The Cross 30 must have a housing in order to be functional. The 
Cross module should be installed in the housing in such a 
manner that it is easy to connect the coolant piping. 
 
Note: Never expose the Cross 30 to excessive thermal or me-
chanical forces.  
 

Connections

 

The Cross is available with threaded liquid connections,         
ISO-G 1” or 1.25” with length 22 mm or 44 mm. 

                

 

 

Available connections

 

 

 

 

 

 

 

G 1                                                                   G1.25 

 

 

 