6. On field supplied terminations, a minimum distance
between the end of the exhaust pipe and the end of
the intake pipe without a termination elbow is 8” and a
minimum distance of 6” with a termination elbow. See
Figures 33 and 34.
7. If intake and exhaust piping must be run up a side wall to
position above snow accumulation or other obstructions,
piping must be supported every 24” (610 mm) as shown
in Figures 33 and 34.
When exhaust and intake piping must be run up an
outside wall, the exhaust piping must be terminated
with pipe sized per Table 9. The intake piping may be
equipped with a 90° elbow turndown. Using turndown
will add 5 feet (1.5 m) to the equivalent length of the
pipe.
8. Based on the recommendation of the manufacturer, a
multiple furnace installation may use a group of up to
four terminations assembled together horizontally, as
shown in Figure 37
Figure 31
Flush Mount Side Wall Termination
Содержание 95G2DFE
Страница 3: ...507206 01 Page 3 of 59 Issue 1337 Figure 1 ...
Страница 17: ...507206 01 Page 17 of 59 Issue 1337 A95DF2E 95G2DFE Table 7A ...
Страница 18: ...507206 01 Page 18 of 59 Issue 1337 A95DF2E 95G2DFE Table 7B ...
Страница 19: ...507206 01 Page 19 of 59 Issue 1337 A95DF2E 95G2DFE Table 7C ...
Страница 27: ...507206 01 Page 27 of 59 Issue 1337 Figure 32 ...
Страница 34: ...507206 01 Page 34 of 59 Issue 1337 Figure 48 TRAP DRAIN ASSEMBLY USING 1 2 PVC or 3 4 PVC ...
Страница 36: ...507206 01 Page 36 of 59 Issue 1337 Figure 50 Table 10 ...
Страница 40: ...507206 01 Page 40 of 59 Issue 1337 TYPICAL WIRING DIAGRAM Figure 54 ...
Страница 42: ...507206 01 Page 42 of 59 Issue 1337 Field Wiring Applications With Conventional Thermostat Table 15 ...
Страница 43: ...507206 01 Page 43 of 59 Issue 1337 Table 15 Field Wiring Applications With Conventional Thermostat Continued ...
Страница 56: ...507206 01 Page 56 of 59 Issue 1337 Start UP Performance Check List ...