background image

Page 3

STEP 2 – REFRIGERANT PIPING – Flushing 

Existing Line Set and Indoor Coil

 IMPORTANT

If this unit is being matched with an approved line set 

or indoor unit coil that was previously charged with 

mineral oil, or if it is being matched with a coil which 

was manufactured before January of 1999, the coil and 

line set must be flushed prior to installation. Take care to 

empty all existing traps. Polyol ester (POE) oils are used 

in units charged with HFC-410A refrigerant. Residual 

mineral oil can act as an insulator, preventing proper 

heat transfer. It can also clog the expansion device 

and reduce system performance and capacity. Failure 

to properly flush the system per this instruction and the 

detailed Installation and Service Procedures manual will 

void the warranty.

Flush the existing line set per the following instruc-

tions. For more information, refer to the Installation 

and Service Procedures manual.  CAUTION - DO NOT 

attempt to flush and re-use existing line sets or indoor 

coil when the system contains contaminants (i.e., 

compressor burn out).

If a new line set is being installed, size the piping per table 2.

NOTE

 - 

When  installing  refrigerant  lines  longer  than  50 

feet, refer to the Refrigerant Piping Design and Fabrica

-

tion Guidelines manual or contact the Technical Support 

Department Product Application group for assistance.

NOTE

 - 

For new or replacement line set installation, refer 

to Service and Application Note - Corp. 9112-L4 (C-91-4)

 WARNING

When using a high pressure gas such as 

nitrogen to pressurize a refrigeration or air 

conditioning system, use a regulator that can 

control the pressure down to 1 or 2 psig (6.9 

to 13.8 kPa).

 WARNING

Refrigerant can be harmful if it is inhaled. Refrigerant 

must be used and recovered responsibly.
Failure to follow this warning may result in personal 

injury or death.

 WARNING

Fire, Explosion and Personal Safety hazard. 

Failure to follow this warning could result in 

damage, personal injury or death.
Never use oxygen to pressurize or purge 

refrigeration lines. Oxygen, when exposed 

to a spark or open flame, can cause fire and/

or an explosion, that could result in property 

damage, personal injury or death.

 WARNING

Polyol ester (POE) oils used with HFC-410A refrigerant 

absorb moisture very quickly. It is very important that the 

refrigerant system be kept closed as much as possible. 

DO NOT remove line set caps or service valve stub caps 

until you are ready to make connections.

LIQUID LINE FILTER DRIER INSTALLATION

4AC14L(S)36 to 60 Units only. 

NOTE

 – 

The 4AC14LS18 to 30 units have a factory in-

stalled suction filter drier. A liquid line filter drier is not re

-

quired on the 4AC14LS18 to 30 units.

The liquid line filter drier, when provided, must be field in

-

stalled in the liquid line between the outdoor unit’s liquid 

line service valve and the indoor coil’s metering device 

(fixed orifice or TXV) as illustrated in figure 4. This filter 

drier must be installed to ensure a clean, moisture-free 

system.  Failure  to  install  the  liquid  line  filter  drier,  when 

provided, will void the warranty. A replacement filter drier 

is available. See Brazing Connections page 6 for special 

procedures on brazing filter drier connections to the liquid 

line. 

OUTDOOR

UNIT

LIQUID LINE

SERVICE VALVE

LIQUID LINE

FILTER DRIER

LINE

LIQUID

LINE

BRAZE CONNECTION POINTS

4AC14L(S)36 - 60 units only.

(Not required on 4AC14LS18 - 30 units.)

FIGURE 4. Typical Liquid Line Filter Drier Installation 

FIXED ORIFICE (RFC) LIQUID LINE SOLENOID 

VALVE INSTALLATION 

4AC14LS18 to 30 units equipped with a fixed orifice (RF

-

CIV) metering device require installation of liquid line so-

lenoid valve kit #17A09. Refer to liquid line solenoid valve 

kit installation instructions 507807-01.

Содержание 4AC14L48P

Страница 1: ...ct Specifications bulletin EHB for approved indoor component match ups These instructions are intended as a general guide and do not supersede local codes in any way Consult authorities having jurisdiction before installation NOTICE Charging information is given on the charging procedure sticker on the unit access panel For more in depth information consult the Installation and Service Procedures ...

Страница 2: ...ust gases and the chemicals contained within them may cause condensation to form on the steel cabinet and other metal components of the outdoor unit This will diminish unit performance and longevity WARNING To prevent personal injury as well as damage to panels unit or structure observe the following While installing or servicing this unit carefully stow all removed panels so that the panels will ...

Страница 3: ...nsibly Failure to follow this warning may result in personal injury or death WARNING Fire Explosion and Personal Safety hazard Failure to follow this warning could result in damage personal injury or death Never use oxygen to pressurize or purge refrigeration lines Oxygen when exposed to a spark or open flame can cause fire and or an explosion that could result in property damage personal injury o...

Страница 4: ...20 feet 6 1 m 89J56 L15 41 30 30 feet 9 1 m 89J57 L15 41 40 40 feet 12 2 m 89J58 L15 41 50 50 feet 15 2 m 89J59 4AC14L48P 4AC14LS36P 4AC14LS42P 3 8 10mm 7 8 22mm L15 65 30 30 feet 9 1 m 89J60 L15 65 40 40 feet 12 2 m 89J61 L15 65 50 50 feet 15 2 m 89J62 4AC14L60P 3 8 10mm 1 1 8 29mm Field fabricated N A N A Applicable to all minor revision numbers unless otherwise specified Some applications may r...

Страница 5: ...nnect the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLINDER CONTAINING CLEAN HCFC 22 TO BE USED FOR FLUSHING Positioned to deliver liquid refrigerant LIQUID LINE SERVICE VALVE INLET DISCHARGE TANK RETURN CLOSED OPENED RECOVERY CYLINDER RECOVERY MACHINE NEW OUTDOOR UNIT VAPOR LINE SERVICE VALVE VAPOR LIQUID 1 A HCFC 22 cylinder with c...

Страница 6: ... ends The pipe must remain round Do not crimp end of the line Remove service cap and core from both the vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERVICE PORT CAP SERVICE PORT CORE SERVICE PORT CAP CUT AND DEBUR LINE SET SIZE MATCHES SERVICE VALVE CONNECTION DO NOT CRIMP SERVICE VALVE CONNECTOR WHEN PIPE IS SMALLER THAN CONNECTION 3 VAPOR LINE SERVICE VALV...

Страница 7: ... cloths WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated cloths around service valve bodies and copper tube stubs Use additionalwater saturated cloths underneath the valve body to protect the base paint 4 FLOW NITROGEN Flow regulated nitrogen at 1 to 2 ...

Страница 8: ...FOR FURTHER DETAILS SENSING LINE EQUALIZER LINE CHECK EXPANSION VALVE TEFLON RING Uncased Coil Shown Sensing bulb insulation is required if mountedexternal to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR ASSEMBLY 3 Install one of the provided Teflon rings around the stubbed end of the check expansion valve and l...

Страница 9: ... 150 psig 1034 kPa Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector F After leak testing disconnect gauges from service ports After the line set has been connected to the indoor and ...

Страница 10: ...nifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylinder of HFC 410A positioned to deliver liquid refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following Close manifold gauge valves Shut off HFC 410A cylinder Rein...

Страница 11: ...ay result in property damage Size wiring and circuit breaker s per Product Specifications bulletin EHB and unit rating plate WARNING ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Take care during unit installation and service to protect the unit s electronic controls Precautions will help to avoid control exposure to electrostatic d...

Страница 12: ...d secure with provided wire tie B Make 24VAC thermostat wire connections Locate the two wires from the contactor and make connection using field provided wire nuts Yellow to Y1 Black to C common ROUTING HIGH VOLTAGE GROUND AND CONTROL WIRING WIRE RUN LENGTH AWG INSULATION TYPE LESS THAN 100 30 METERS 18 TEMPERATURE RATING MORE THAN 100 30 METERS 16 35ºC MINIMUM HIGH VOLTAGE GROUND WIRES FIELD CONT...

Страница 13: ...ort which has a factory installed valve stem Figures 15 and 16 provide information on how to access and operate both angle and ball type service valves Torque Requirements When servicing or repairing heating ventilating and air conditioning components ensure the fasteners are appro priately tightened Table 2 lists torque values for fasteners TABLE 1 TORQUE REQUIREMENTS Parts Recommended Torque Ser...

Страница 14: ...cated on the unit access panel Detailed information is provided in the 4AC14 Installation and Service Procedures manual Homeowner Information CAUTION Beforeattemptingtoperformanyserviceormaintenance turn the electrical power to unit OFF at disconnect switch In order to ensure peak performance your system must be properly maintained Clogged filters and blocked air flow prevent your unit from operat...

Страница 15: ...ect contactor contacts for pitting or burn marks Replace as necessary 7 Check outdoor fan motor for worn bearings bushings Replace as necessary 8 Inspect and clean outdoor coils if necessary and note any damage to coils or signs of leakage Indoor Unit Air Handler or Furnace 1 Inspect component wiring for loose worn or damaged connections Confirm proper voltage plus amperage of indoor unit 2 Inspec...

Страница 16: ...pply Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or installation instructions for required subcooling and approach temperatures Subcooling A B SUBCOOLING Saturated Condensing Temperature A minus Liquid Line Temperature B Approach A B APPROACH Liquid Line Temperature A minus Outdoor Air Temperature B Indoor Coil Te...

Отзывы: