background image

Page 6

 

    with silicone.

 

    Please Note: If water “pools” around the airconditioner (ie. The roof has

 

   sagged around the airconditioner) then the caravan manufacturer should be 

 

   consulted.

 

4: In high humidity areas, condensation may occur on the underside of the evaporator tray 

above the inside plenum. See fig 10 and 24.

This usually is associated with running the unit on low speed for a prolonged period. Under 

these conditions use the high or medium speeds and avoid “auto”

As it will cause the inside fan to drop to low speed as the set point temperature is 

approached.

Later production is fitted with more insulation on the underside to alleviate this problem. 

Quote part No 8001056……..

12: Water drips from the inside plenum only when it rains.

       Check condition 11 point 3 above.

Water ingress could also be due to rain entering the canopy/chassis  

joint and not being able to drain away to the outside. Check the limber holes in the nose

of the chassis. Refer fig 9 and check that the two drain holes are clear in the evaporator area.

13:Unit does not turn on. No display lights on the flip down display.

 

Proceed to check the following in order.

 

1: Check circuit breaker is on and the van has power.

2: Unscrew the inside plenum (4 screws) and disconnect plenum from control cable via the 

4 pin plug. With a multimeter, check power at inlet junction block. 240V AC. If OK, shift 

multimeter to 12V DC range.

 

         Check voltage across the control cable conductors. See Diag 1  & 1A

 

         If the correct voltages are detected as per Diag 1, then suspect a break 

between this plug and the display module. Inspect plug pins. Disassemble the display and 

check the plug to board is OK. (see fig 23)  If the voltages can be detected right up to the 

display, replace display.

3: If the voltages cannot be detected at the breakaway plug, then suspect the problem to be in 

the main control board enclosure.

 

 

Remove the canopy from the unit. Isolate the power to the aircon.

 

 

Remove lid of the RHS enclosure to gain access to the control board.

See Fig 1, 2 & 3. Firstly check the fuse on the board. If this fuse is blown it 

may

 

indicate a fan motor fault. If the fuse is ruptured, replace with a M205 S/Blow 5A  20 x 

5. If the fuse blows again, start investigating for a faulty condenser, evaporator motor or 

R/V.

If the fuse is not an issue, and the serial no of the unit is below IBSA02177. Then one 

needs to investigate the power supply driving the main board. If the board is powered 

from a transformer see fig1, then power up the unit, remove the 2 pin white plug that 

connects the transformer to board and with a multimeter set to 12V AC, check output. If 

no output, suspect a faulty transformer. Replace with a SMPS  Part No 8001039……..

For units below serial no IBSA 03280 and above 02177, these units will be fitted with 

an external switch mode power supply. See fig 2.

 

 

Here again remove the 2 pin white plug from the SMPS to board, set 

multimeter to 12V DC and check output. Earlier SMPS’s had an adjustment pot see fig 

20. It is worthwhile adjusting this pot if there is no output. 

If the power supply is deemed faulty then replace part No 8001039……

If the power supply is outputting OK, then change the main board.

Units Serial no above IBSA 03280 will have a main control board

with the power supply integrated on it. see fig 3

If there is no voltage output at the control cable with the integrated version, change the 

control board.

Содержание IBIS ROOFTOP CARAVAN

Страница 1: ... MANUAL for IBIS ROOFTOP AIRCONDITIONER ERROR CODES THEIR MEANING Aircommand Australia Pty Ltd 954 Port Road Albert Park South Australia 5014 Email reception aircommand com au Pantone Cool Grey 9U Pantone 301 U ...

Страница 2: ...opper pocket on the coil See fig 18 E3 Outside coil sensor fault Usually a faulty connection 2 plugs damaged lead or faulty sensor Action Check Red plug on main board and extension plug in bundled wiring usually located near capillary tube coils Check resistance of thermistor cable by measuring with a multimeter 10K ohm at 25C See fig 19 and table 1 If open circuit or out of calibration replace E4...

Страница 3: ...il temp using the Temp down button and Medium fan speed combination to display this temp NB if fans etc seem to be OK then measure thermistor resistance and refer to table 12 In case the problem is thermistor calibration Action If unit is in cooling mode examine both condenser fans are running If one is running then suspect a faulty motor If both fans not running then on units up to serial No IBSA...

Страница 4: ... Yellow If the Black or White conductors are broken then there will be no display If the Yellow or Red conductors are broken then the display will read 0 In addition if one or the other Yellow or Red conductors are broken then if the unit is in Auto change over mode then both the Green cooling LED and the Red heating LED will be flashing together This will be conclusive proof of a break in the con...

Страница 5: ...ed plug Should be 12V DC If no output change the SMPS Some SMPS have an adjustment pot fig 20 Try adjusting either direction to see if it regains output Units from IBSA 03280 have an integrated SMPS on the main board fig 3 Except for units IBSA 03482 to 03504 which had external SMPS s 3 Unit drops out the ECB breaker Use a 500V megger to check for ground leakage It is possible to unplug both conde...

Страница 6: ...ompressor studs are clear of the rubber Mount by 1 to 2 mm Adjust if necessary See fig 7 9 On heating the unit cycles regularly the temperature display indicates say 24 to 28C but the average temperature in the van is very much less Disassemble the facia from the inside plenum 4 screws and examine carefully the extension duct for leaks particularly where it joins the horizontal duct A leaking duct...

Страница 7: ...Disassemble the display and check the plug to board is OK see fig 23 If the voltages can be detected right up to the display replace display 3 If the voltages cannot be detected at the breakaway plug then suspect the problem to be in the main control board enclosure Remove the canopy from the unit Isolate the power to the aircon Remove lid of the RHS enclosure to gain access to the control board S...

Страница 8: ...frigerant recovered the leak repaired and checked and the unit evacuated and recharged 720 grams A unit that may have had a leak at an access valve and this has been rectified can have refrigerant added Add refrigerant until a good fit is made with the above parameters I e Suction pressure above 400 Kpa delta T greater than 14C and the inside coil below 14C The use of Independent generators or Inv...

Страница 9: ...isulu QHR 19E early production Or Sanyo C RH100H5B Pt No 0018290 Run capacitor 30 µf x 440 VAC 4101072 Start capacitor if used 64 µf x 330 VAC 8001040 Start relay Omron AMVL 300A 8001042 Or PTC relay GYE101A Condenser and Evap fan motors single speed to s n 001177 4402060 Fan Capacitor 1 5 µf Condenser Fan 3 speed s n 001178 upward 8001052 Fan Capacitor 2 µf Evaporator Fan 3 speed s n 001178 upwar...

Страница 10: ...tance in K Ω 10 45 9 43 8 41 7 39 6 37 5 36 4 34 3 32 2 31 1 30 0 28 1 27 2 26 3 25 4 24 5 23 6 22 7 21 8 20 9 19 10 18 11 17 5 12 17 13 16 14 15 5 15 15 16 14 3 17 13 7 18 13 19 12 6 20 12 2 21 11 7 22 11 2 23 10 8 24 10 4 25 10 26 9 6 27 9 2 28 8 9 29 8 6 30 8 3 31 8 32 7 7 33 7 4 34 7 1 ...

Страница 11: ... 75 63 2 7 64 2 6 65 2 5 66 2 45 67 2 4 68 2 3 Example The thermistor sensor is in free air and the free air temp is measured as 35C The resistance of the thermistor assy s measured at 6 8KΩ This indicates the thermistor assy is OK The thermistor assy in free air is 20 C The resistance is measured as 6 6KΩ which relates to 36C This indicates that the thermistor is defective and should be changed i...

Страница 12: ...Page 11 ...

Страница 13: ...Page 12 ...

Страница 14: ...Page 13 ...

Страница 15: ...Page 14 ...

Страница 16: ...Page 15 ...

Страница 17: ...Page 16 ...

Страница 18: ...Page 17 ...

Страница 19: ...Page 18 ...

Страница 20: ...Page 19 ...

Страница 21: ...Page 20 ...

Страница 22: ...Page 21 ...

Страница 23: ...Page 22 ...

Страница 24: ...Page 23 ...

Страница 25: ...Page 24 ...

Страница 26: ...Page 25 ...

Страница 27: ...Page 26 ...

Страница 28: ...Page 27 ...

Страница 29: ...Page 28 ...

Страница 30: ...Page 29 ...

Страница 31: ...Page 30 ...

Страница 32: ...Page 31 ...

Страница 33: ...Page 32 ...

Страница 34: ...Page 33 ...

Страница 35: ...Page 34 ...

Страница 36: ...Page 35 ...

Страница 37: ...Page 36 ...

Страница 38: ...Page 37 Diag 1 ...

Страница 39: ...Page 38 ...

Страница 40: ... 21 Control cable see wiring diags see figs 1 11 11a 14 pp3 Controller main see figs 1 2 2a Controller speed see pp4 see fig 5 D De Icing see pp5 Display see pp3 figs 22 23 pp3 Discharge temp see pp 7 Drain see fig 21 Duct extension see fig 24 Duct horizontal see figs 9 17 E Electrical faults see speci pp9 for fan motor data See pp5 for compressor data Enclosures see figs 1 2 3 21 Electrical data ...

Страница 41: ...ng see pp 7 Refigerant see speci pp9 Roof seal see pp 5 11 Return air see pp5 9 pp5 10 see fig 14 Return air sensor see pp 1 Return air filter see fig 14 Reversing valve see fig 21 Rubbers see fig 6 S Seal roof see pp 5 11 Sensor see pp 1 2 see figs 16 18 19 Table 1 Specifications see pp 9 Speed controller module see pp 4 fig 1 5 Springs see fig 6 Schrader valves see Access valves Suction pressure...

Страница 42: ...Page 41 T Thermistor see pp1 2 see figs 16 18 19 see table 12 U V Voltage see speci pp9 W Water ingress see pp6 Watts in see speci pp9 Wiring Diags see pp 10 11 12 ...

Отзывы: