Aircommand Heron Q Скачать руководство пользователя страница 6

AIR HANDLER INSTALLATION

If possible, the A/H should be installed at either end of the van, such that unimpeded air flow is obtained
down the length of the van.

If this is not possible, install the A/H in as central a position as possible.

5 MOST IMPORTANT POINTS THAT MUST BE SATISFIED

1.

The distance from the back of the cupboard to the back of the A/H

must not be less than 90mm

to

allow proper air entry to the fan. Insufficient gap will also increase the noise level.

2.

Three

separate return air grilles/filters are supplied, and

must

be installed. If only two are used, this

will reduce the air volume back to the fan and hence the capacity of the airconditioner.

3.

The airhandler must be fitted allowing a minimum space of 25mm between the right hand side of the
A/H and the wall. And likewise 25mm between the top of the A/H and the inside top of cupboard.

4.

The return air grilles/filters, should be fitted as far

back

as is possible to provide a more direct path for

air to flow back to the fan.

5.

The A/H has a condensate drain underneath. This drain must continuously “fall” from the outlet. It is
recommended that the bottom of the A/H be 70mm above the bottom of the cupboard, to allow
adequate fall.

A lesser amount is ok, provided

much

care is exercised to avoid “humps” that will result in airlocks

and backup & overflow of condensate.

The airhandler has been designed to operate in a cupboard or enclosure as described on page 5.

Under no circumstances is the resistance to airflow to be increased by ducting of the supply or return air.

It is recommended that the minimum cupboard dimensions be 525 wide x 320 high x 300 deep.

A. The Facia panel will be centrally located.

B. The right hand edge of the cutout will ensure that when the A/H is installed, a

minimum space of 25mm exists down the side of the A/H.

C. The left hand side of the A/H must be a minimum of 110mm from the LHS

of the cupboard to allow pipes to be connected. (Refer fig. 6)

D. The bottom of the cutout should be at least 70mm above the bottom of

cupboard to allow the condensate drain to “fall” away sufficiently.

6

Figure 6

Mark out the A/H cut out as per fig. 6a.

.

Ensure the choice of

location satisfies the following:

Figure 6a

338

455

Содержание Heron Q

Страница 1: ...icle the thickness and quality of thermal insulation the expected outside or ambient conditions The HERON Q is recommended for vans up to 7 0 meters overall but assumes that all walls and ceilings are insulated with a minimum of 25mm of insulation wool or foam The Heron Q may be used in vans up to 9 metres provided the insulation is a minimum 38mm thick and all windows are double insulated Windows...

Страница 2: ...th in the following description DESCRIPTION OF THE HERON SYSTEM The HERON Q is a split system utilizing a condenser set referred to throughout this text as a Con set and an airhandler referred to as an A H The Con set is designed for installation into a side wall of a van and will fit beneath the bench top or into the back of a wardrobe etc Ref to fig 1 for dimensions The A H is designed for fitme...

Страница 3: ... 765mm high off floor level and 454mm wide Caution This opening may interfere with wiring concealed in the wall cavity both 12v and 240v If the wiring layout is not known then proceed with caution Do not have the van plugged into a 240v supply during this stage of the installation The opening must now be framed with timber at least 25mm thick The Con set can now be lifted into the opening Before p...

Страница 4: ...es are equivalent to 1 4 and 3 8 respectively The 9 5 dia must be insulated with 10 x 10 foam rubber insulation Entry to the Con set Refer figures x y z Retain the red plastic blanking caps on the pipes before flaring These can be reinserted after the pipework is tightened up It is essential that a good airseal is made here Failure to do so will result in hot air being possibly leaked into the con...

Страница 5: ...s can follow the 6 4ø pipe 9 5ø tube insulated LEFT HAND ENTRY Figure Y REAR ENTRY Figure Z 5 9 5ø tube insulated 6 4ø tube Ensure tubes do not touch compressor 6 4ø tube pass out the power control cables thru this entry ...

Страница 6: ...5 The A H has a condensate drain underneath This drain must continuously fall from the outlet It is recommended that the bottom of the A H be 70mm above the bottom of the cupboard to allow adequate fall A lesser amount is ok provided much care is exercised to avoid humps that will result in airlocks and backup overflow of condensate The airhandler has been designed to operate in a cupboard or encl...

Страница 7: ...nel the A H will not need additional support If however the front panel is light ply then this must be strengthened after cutting out as per the template This framing should be 20mm thick to provide the necessary support and should tie in with the main cupboard members to support the weight of the Airhandler The front panel can now be fitted and screwed into place Installation of the refrigeration...

Страница 8: ...cess tube to be cut off and remove the A H to allow the flare nuts to be put on and the flares made Unscrew both flare nuts from the nipples of the A H ensuring the sealing caps are removed See page 6 for tips on making flares Having completed the flaring reinstall the A H remembering to shift it fully to the right after insertion Screw the flanges back to the front panel through the 4 holes provi...

Страница 9: ...9 ...

Страница 10: ...10 ...

Страница 11: ...11 ...

Страница 12: ...12 ...

Страница 13: ...13 ...

Страница 14: ...14 ...

Страница 15: ...15 ...

Страница 16: ...16 ...

Страница 17: ...17 ...

Отзывы: