10. Troubleshooting
Refer to the general safety rules indicated in paragraph 2.3. All the operations described in this
chapter must be performed only by qualified personnel according to that specified in paragraph
problem
possible cause
Recommended intervention
1.
The chiller fails
to start
No external consents
Check the presence of external consents.
Incorrect external consent connection
Check the external consent connections
The anti-circulation timer is on
Wait 5 minutes
2.
The
compressor
fails to start
Defective compressor
Use the testers to check the winding phases if they are in
short circuit and the correct impedance. Repair/replace the
motor.
The power circuit is open.
Check the power circuit
The compressor protection device is open
Check the compressor work conditions
3.
Compressor
repeated start
ups and stops
Defective compressor
Check and/or replace it
Minimum pressure switch intervention
See point 5
Defective compressor remote switch
Check and/or replace it
Incorrect thermostat configuration
Check and restore the original configuration, see point 7
No refrigerant
Check and/or replace it
4.
High pressure
switch
intervention
Defective pressure switch
Clean the filters and/or condenser
Clogged air filter and/or condenser
See point 6
Failed fan(s)
Make sure that the liquid indicator indicates the presence of
humidity in the system or of bubbles in the liquid indicator
during normal operation. Replace the gas filter.
Clogged refrigerant filter
Remove the refrigerant in excess. If the condensation pressure
is too high and if there are no additional anomalies in the
system, pay attention because zeotropic blends, as R407c,
allow you to discharge the circuit partially.
Excessive refrigerant gas charge
Check and/or replace it
5. Minimum
pressure switch
intervention
Defective pressure switch
See point 7
No refrigerant gas
Check and open the valves completely
Valves closed partially on liquid line
Check and/or replace it, see point 4
Clogged refrigerant filter
Check if the machine does not cool down and if the low
pressure side has a too low pressure. Replace it if required
Blocked thermostatic valve
Check if fluid circulates in the evaporator.
No thermal load
Add liquid
Insufficient tank liquid level
Check and/or replace it
6. The fan fails to
start
Defective fan remote switch
Check the fan motor insulation
Fan circuit breaker intervention
Check and/or replace it, see point 2
Defective fan motor
Pressurise the circuit at 10 bar. Identify the leak with a leak
detector.
7.
No refrigerant
Leak from the refrigerant circuit
Fill, repair, make the vacuum and refill.
8. Frost
thermostat
Blocked thermostatic valve
Check and/or replace it
No refrigerant gas
See point 7