38
Type of dryer:
Refrigerated
Power supply:
460, 575 VAC / three phase / 60Hz
Refrigerant type:
R-404A
All Models
R-404a
Parameter
Description
Air Pressure
Air Inlet
Temperature
Ambient
Temperature
Evaporator
Temperature
Suction Gauge
Reading
Discharge Gauge
Reading
Optimum
100 psig
100 (°F)
100 (°F)
35 - 42 (°F)
75 - 90 psig
290 - 400 psig
Maximum
200 psig
140 (°F)
120 (°F)
60 (°F)
130 psig
410 psig
Minimum
40 psig
40 (°F)
35 (°F)
32 (°F)
75 psig
160 psig
A.3 Tables of specifications - AES Series