5
AT 1200 HB(E/E2) EC
A
T
1200
HB
EC
A
T
1200
HBE
EC
A
T
1200
HBE
2
EC
Supply voltage [V/50 (60) Hz]
1~230
3~400
Maximum power consumption without electric heaters [W]
350
Preheater power [W]
-
6300
6300
Reheater power [W]
-
-
6300
Maximum unit current without electric heaters [
А
]
1.6
Maximum unit current with electric heaters [
А
]
-
9.6
18.7
Air flow [m
3
/h]
1240
Sound pressure level at 3 m distance [dBA]
24
Transported air temperature [°
С
]
-25...+40
Casing material
painted steel
Insulation
40 mm mineral wool
Extract filter
G4
Supply filter
G4 + optional F7
Connected air duct diameter [mm]
400
Weight [kg]
394
398
400
Heat recovery e
ffi
ciency [%]
84...96
Heat exchanger type
counter-flow
Heat exchanger material
polystyrene
SEC class
A+
Units without a drain pump are designed to operate in an electrical supply network with a frequency of 50(60) Hz,
with a drain pump — 50 Hz only.
TECHNICAL DATA
The unit is designed for indoor application with the ambient temperature ranging from +1 °C up to +40 °C and relative humidity up to
60 % without condensation. In cold, damp rooms, there is a possibility of freezing or condensation inside and outside the casing.
In order to prevent condensation on the internal walls of the unit, it is necessary that the surface temperature of the casing is 2-3 °C above
the dew point temperature of the transported air.
The unit should be operated continuously, and in cases where ventilation is not necessary, reduce the air flow of the fans to a
minimum (20%). This will ensure a favorable indoor climate and reduce the amount of condensation inside the unit, which can damage
electronic components. Never use the unit for dehumidification, for example, of new buildings.
The unit is rated as a Class I electrical appliance.
Hazardous parts access and water ingress protection rating:
IP20 for the unit connected to the air ducts
IP44 for the unit motors
The unit design is constantly being improved, thus some models may be slightly di
ff
erent from those described in this manual.