Air King ESFGH Series Скачать руководство пользователя страница 2

INSTALLATION INSTRUCTIONS
CAUTION:

 

MAKE SURE POWER IS SWITCHED OFF AT SERVICE PANEL BEFORE 

STARTING INSTALLATION.

SECTION 1

Preparing the Exhaust Fan

1. 

Unpack fan from the carton and confirm that all pieces are present. In addition to the 

exhaust fan you should have:

 

 

1 - Grill

 

 

1 - Damper Assembly (attached)

 

 

4 - Mounting Rails

 

 

1 - Mounting Flange

 

 

1 - Fluorescent Lamp

 

 

1 - Instruction/Safety Sheet   

2. 

Choose the location for your fan. To ensure the best air and sound performance, it is 

recommended that the length of ducting and the number of elbows be kept to a minimum, 

the radius of each elbow be as large as possible 

for the installation, and that insulated hard ducting 

be used. Larger duct sizes will reduce noise and 

airflow restrictions. This fan will require at least 10

 

of clearance in the ceiling or wall, and will mount 

through drywall up to 3/4

 thick.

3. 

Select the most convenient electrical knockout and 

remove using a straight-blade screw driver 

(Figure 1).

4. 

No additional vibration deadening materials are needed 

for this fan.

SECTION 2

New Construction

1. 

Install the rails into the mounting channel on the housing. Center the mounting channel in 

the slots on the housing, then from inside the housing tighten the mounting channel nuts 

so the channel is securely in place. Position the housing next to the joist. Line up housing 

so that it will be flush with the finished ceiling. Secure the ends of the rails with screws or 

nails (not included) to the joists and slide the housing into the final position 

(Figure 2).

SECTION 3

Existing Construction

1. 

Set housing in position between the joist and trace an outline onto the ceiling material 

(Figure 3).

 Set housing aside and cut opening, being careful not to cut or damage any 

electrical or other hidden utilities. Install the rails into the mounting channel on the 

housing. Center the mounting channel in the slots on the housing, then from inside the 

housing tighten the mounting channel nuts so the channel is securely in place. Position 

the housing in the previously cut hole so that it is flush with the finished ceiling. Secure 

the ends of the rails to the joists 

(Figure 2).

www.airkinglimited.com

6728056 Rev. C 5-14

2 of 12

SECTION 4

Ducting

CAUTION:

 

ALL DUCTING MUST COMPLY WITH LOCAL AND NATIONAL 

BUILDING CODES.

1. 

Connect the ducting to the fan’s duct collar 

(Figure 4).

 Secure in place using tape 

or screw clamp. Always duct the fan to the outside through a wall or roof cap. It is 

recommended that low restriction termination fittings be used.

SECTION 5

Wiring

CAUTION:

 MAKE SURE POWER IS SWITCHED OFF AT SERVICE PANEL BEFORE 

STARTING INSTALLATION.

CAUTION:

 ALL ELECTRICAL CONNECTIONS MUST BE MADE IN ACCORDANCE 

WITH LOCAL CODES, ORDINANCES, OR NATIONAL ELECTRICAL CODE. IF YOU ARE 

UNFAMILIAR WITH METHODS OF INSTALLING ELECTRICAL WIRING, SECURE THE 

SERVICES OF A QUALIFIED ELECTRICIAN.

NOTE:

 This unit includes a side access panel for wiring that does not require the removal of 

the fan’s blower assembly. If you choose to wire the unit from the inside, you will need to 

remove the blower assembly and internal wiring compartment. Both methods are equally 

effective.

1a.  External Wire Compartment: Remove the wire compartment cover screw and place 

cover in a secure place 

(Figure 5).

1b.  Internal Wire Compartment: Using a 7/16

"

 socket, remove the two hex nuts holding the 

blower assembly in place. Lift up on the assembly and slide it out of the tabs on the 

housing 

(Figure 6).

 Remove the wire compartment cover screw (or screws) and place 

the cover in a secure place 

(Figure 7).

NOTE:

 If the fan motor plug is connected to the fan housing receptacle, unplug so the blower 

assembly can be completely removed.

Figure 1

Ducting

Duct 

Collar

Figure 4

Figure 5

Screw

Wire 

Compartment 

Cover

Figure 3

Joist

Housing

Joist

Mounting Rails

Figure 2

Plug

Tabs

Hex Nuts

Figure 6

Содержание ESFGH Series

Страница 1: ...son s in accordance with all applicable codes and standards including fire related construction b Sufficient air is needed for proper combustion and exhausting of gases through the flue chimney of fue...

Страница 2: ...nel on the housing Center the mounting channel in the slots on the housing then from inside the housing tighten the mounting channel nuts so the channel is securely in place Position the housing in th...

Страница 3: ...quired NOTE This fan is rated for direct insulation contact Type IC and it is recommended that this fan be completely covered by insulation in order to reduce heat loss or gain to unconditioned space...

Страница 4: ...imum on time to 30 minutes see numbers in Step 2b The sensor will then flash the number of times for the new setting 3 times before exiting back to the programming mode 3 Once all setting have been ma...

Страница 5: ...unauthorized repairs made or attempted This warranty does not cover shipping costs for the return of products to Air King for repair or replacement Air King will pay return shipping charges from Air K...

Страница 6: ...14 1 26 Watt Lamp 5S1999720 15 1 Light Lens 5S1239116 REPLACEMENT PARTS DIAGRAM 1 2 4 5 6 All Models Qty Description Replacement Part 10 1 Wire Compartment Assembly 5S1239824 15 3 Adjustment Knob 5S12...

Страница 7: ...bles incluant la construction relative aux incendies b De l air en quantit suffisante est requis pour la bonne combustion et l vacuation de gaz par le conduit chemin e provenant d quipement de br lage...

Страница 8: ...canal de montage dans les fentes sur le bo tier puis de l int rieur du bo tier serrez les crous de montage de sorte que le canal soit bien en place Positionnez le bo tier dans le trou pr alablement d...

Страница 9: ...ion directe type IC Il est aussi recommand que ce ventilateur soit compl tement recouvert par l isolation afin de r duire la perte de chaleur ou de gagner de l espace inconditionn 2 Si l assemblage de...

Страница 10: ...3 fois avant de quitter pour revenir au mode de programmation 3 Une fois que tous les r glages ont t faits le capteur retournera au mode de d tection et le LED clignotera lorsque l occupation de la sa...

Страница 11: ...e manipulation ou op ration de dommages d exp dition d abus de mauvaise utilisation de r paration faite ou tent es non autoris es Cette garantie ne couvre pas les co ts d exp dition pour le retour des...

Страница 12: ...1 Lampe de 26 watts 5S1999720 15 1 Objectif de lumi re 5S1239116 Tous les mod les de pi ce Qt Description de remplacement 8 1 Assembl e du compartiment du fil ESF80SGH 5S1239818 1 Assembl e du compart...

Отзывы: