Air King ESBGH Series Скачать руководство пользователя страница 4

6. 

Restore power and test your installation.

SECTION 7

Programming the Occupancy Sensor

1a. 

Setting the Occupancy Time Delay.

 This will set the amount 

of time the fan will continue to operate after the room is 

vacated. Locate the motion sensor on the fan’s grill and press 

the button 2 times. The LED on the sensor will then flash the 

number of times to indicate the current setting, this will repeat 

3 times:

 

 

1 time = 30 seconds 

 

 

2 times = 2.5 minutes  6 times = 12.5 minutes

 

 

3 times = 5 minutes   7 times = 15 minutes 

 

 

4 times = 7.5 minutes   8 times = 17.5 minutes

 

 

5 times = 10 minutes   9 times = 20 minutes

1b.  To adjust the setting, while the sensor is still flashing from 

Step 1a

, press the button the 

number of times that corresponds with the amount of time you desire, for instance 3 times 

sets the delay to 5 minutes (see numbers in 

Step 1

). The sensor will then flash the number 

of times for the new setting 3 times before exiting back to the programming mode.

2a 

Setting the Minimum On Time.

 This sets the minimum time the fan will operate once 

motion is detected within the room. This works in conjunction with the Occupancy Time 

Delay feature set in 

Steps 1a

 and 

1b

. For instance if you set the minimum time on for 15 

minutes and the Time Delay for 5 minutes, the fan will operate for at least 15 minutes 

then 5 additional minutes.

 

NOTE:

 This is a minimum time that the fan will operate. If the room is occupied longer, the 

fan will continue to run until the room is vacated and the occupancy time delay has elapsed.

2b.  Locate the motion sensor on the fan’s grill and press the button 10 times. The LED on 

the sensor will then flash the number of times to indicate the current setting, this will 

repeat 3 times:

 

 

1 time = 0 minutes 

 

4 times = 45 minutes

 

 

2 times = 15 minutes   

5 times = 60 minutes

 

 

3 times = 30 minutes

2c.  To adjust the setting, while the sensor is still flashing from 

Step 2b

, press the button 

the number of times that corresponds with the amount of time you desire, for instance 

3 times sets the minimum on time to 30 minutes (see numbers in 

Step 2b

). The sensor 

will then flash the number of times for the new setting 3 times before exiting back to the 

programming mode.

3.  Once all setting have been made and the sensor will return to detection mode and the 

LED will flash when occupancy of the room is detected.

www.airkinglimited.com

6728055 Rev. B 5-14

4 of 12

SECTION 8

Setting the Humidistat

This fan is equipped with a humidity sensor that automatically turns the fan on when humidity 

is above set point and off when humidity is at or below set point. If the fan is operating too long 

or not enough, first check to see the humidity sensor set point. In cases where the ambient 

humidity level of the room rises higher than the preset level, the fan will turn on even if the 

room is not occupied. This helps prevent conditions that lead to mold growth.

CAUTION:

 MAKE SURE POWER IS SWITCHED OFF AT SERVICE PANEL BEFORE 

SERVICING THE UNIT.

1. 

To set the desired humidity level of the room, remove the grill and locate the 

dehumidistat dial located on the wire compartment cover. 

2. 

Set the dial to the relative humidity you want the fan to maintain usually between 50 & 

80%. Moist climates will require higher settings than dry climates. When the humidity 

level of the room is below this setting the fan will remain off. When the humidity level 

rises about this setting the fan will turn on and run until the humidity level falls below 

this setting. 

3. 

Reinstall the grill and restore power. 

SECTION 9

Activating the Boost Speed

Should it be determined that additional flow is necessary due to excessive duct resistance or 

other field conditions this model is equipped with a boost speed. To activate the boost speed:

Single Speed Models

1a.  Remove the grill and find the 2 pin wire harness from the fan motor to the capacitor.

1b.  Disconnect the harness from the capacitor at the quick connect fitting and remove the 

“Boost Label” from the quick connect fitting on the boost capacitor.

1c.  Plug the motor harness into the boost capacitor and reinstall grill.

Dual Speed Models

2a.  Remove the grill and find the rocker switch located on the main wire compartment in 

the corner of the fan housing.

2b.  Push the rocker switch to the boost position and reinstall grill.

SECTION 10

Use and Care

CAUTION:

 MAKE SURE POWER IS SWITCHED OFF AT SERVICE PANEL BEFORE 

SERVICING THE UNIT.

1. 

Cleaning the Grill:

 Remove grill and use a mild detergent, such as dishwashing liquid, 

and dry with a soft cloth. NEVER USE ANY ABRASIVE PADS OR SCOURING POWDERS. 

Completely dry grill before reinstalling. Refer to instructions in 

Section 5

 

Finishing the 

Installation

, to reinstall grill.

2. 

Cleaning the Fan Assembly:

 Wipe all parts with a dry cloth or gently vacuum the fan. 

NEVER IMMERSE ELECTRICAL PARTS IN WATER.

Figure 13

Содержание ESBGH Series

Страница 1: ...ctrical wiring must be done by qualified person s in accordance with all applicable codes and standards including fire related construction b Sufficient air is needed for proper combustion and exhaust...

Страница 2: ...the housing Center the mounting channel in the slots on the housing then from inside the housing tighten the mounting channel nuts so the channel is securely in place Position the housing in the previ...

Страница 3: ...the wire compartment cover Connect the two pin connector from the humidistat compartment to the two pin connector from the side of the wire compartment cover These cords will only fit one way into th...

Страница 4: ...is detected www airkinglimited com 6728055 Rev B 5 14 4 of 12 SECTION 8 Setting the Humidistat This fan is equipped with a humidity sensor that automatically turns the fan on when humidity is above s...

Страница 5: ...unauthorized repairs made or attempted This warranty does not cover shipping costs for the return of products to Air King for repair or replacement Air King will pay return shipping charges from Air K...

Страница 6: ...ensor Compartment 5S1239826 12 1 Knob 5S1299802 All Models Qty Description Replacement Part 10 1 Wire Compartment Assembly 5S1239830 13 3 Adjustment Knob 5S1299802 Specific to Models ESVDGH Qty Descri...

Страница 7: ...lifi e s en conformit avec tous les codes et normes applicables incluant la construction relative aux incendies b De l air en quantit suffisante est requis pour la bonne combustion et l vacuation de g...

Страница 8: ...les fentes sur le bo tier puis de l int rieur du bo tier serrez les crous de montage de sorte que le canal soit bien en place Positionnez le bo tier dans le trou pr alablement d coup de sorte qu il so...

Страница 9: ...raccordement r installer la soufflante en inversant les instructions l tape 1b de la Section 5 C blage 3 Branchez les c bles 2 broches du ventilateur et les c bles 3 broches de connexion rapide du mot...

Страница 10: ...3 fois avant de quitter pour revenir au mode de programmation 3 Une fois que tous les r glages ont t faits le capteur retournera au mode de d tection et le LED clignotera lorsque l occupation de la sa...

Страница 11: ...e manipulation ou op ration de dommages d exp dition d abus de mauvaise utilisation de r paration faite ou tent es non autoris es Cette garantie ne couvre pas les co ts d exp dition pour le retour des...

Страница 12: ...Compartiment du capteur d humidit 5S1239826 12 1 Bouton 5S1299802 Tous les mod les de pi ce Qt Description de remplacement 8 1 Assembl e du compartiment du fil ESB80SGH 5S1239822 1 Assembl e du compa...

Отзывы: