Air King AKF100H Скачать руководство пользователя страница 3

2.  For proper fan operation, the humidity sensing fan will require a 3 way switch (not 

included). Run wiring between the fan and the switch location. Make sure you leave 
enough wiring in each box to make the connections. At the switch box connect the Black 
wire from the house to the common terminal of the switch. Connect the black wire from 
the fan to one of the switched terminals on the switch. This position will energize the 
automatic mode and the fan will energize upon a rise in humidity. Connect the Red wire 
from the fan to the other switched terminal on the switch. This position will activate the 
Manual On feature and energize the fan. Use approved methods for all connections.

3.  To operate the main light and the night light, run wiring from two toggle switches (not 

included). At the switch box, connect the Black wire from the house to the common 
terminal of each toggle switch. Connect the Yellow wire from the fan to one of the toggle 
switches (this is the main light control). Connect the Purple wire from the fan to the other 
toggle switch (this is the night light control). Use approved methods for all connections.

4.  From where you have chosen to access the fan’s junction box, connect the White wire 

from the house to the two White wires from the fan. Connect the ground wire (green or 
bare copper) from the house to the Green wire from the fan 

(Figure 8)

. Use approved 

methods for all connections.

5.    Mount the switches and cover using a 3-gang electrical box (not included).

NOTE:

 The fan’s receptacle wires might need to be pulled outside compartment for connection. 

Only pull the three loose wires outside of compartment. Additional wires will be present.

6.  Carefully tuck wires back inside wire compartment and replace wire compartment cover 

securing with the screw that was removed earlier.

SECTION 6

Completing the Installation

1.  Use a sealant appropriate for contact with the building materials present and for the 

temperature requirements of the installation to prevent air leakage from unconditioned 
spaces is recommended. If gaps between unit housing and ceiling are great, additional 
material (backing rod, ceiling material) may be required.

NOTE:

 This fan is rated for direct insulation contact (Type IC) and it is recommended that this fan 

be completely covered by insulation in order to reduce heat loss or gain to unconditioned space.

2.  If the fan’s blower assembly was removed during the wiring process, reinstall the blower 

by reversing the directions in 

Step 1b

 in 

Section 5

 

Wiring

.

3.  Connect the fan wire harness by plugging the 3 pin quick connect end into the receptacle 

located on the side of the wire compartment cover. Confirm that the 5 pin quick connect 
end is plugged into the receptacle from the blower assembly. Connect the light wire harness 
by plugging the 3 pin rectangular quick connect end into the receptacle located at the top of 
the wire compartment. These cords will only fit one way into the receptacles 

(Figure 9)

.

www.airkinglimited.com

6728023 Rev. G 5-14

3 of 12

4.  Install the included 26 watt fluorescent lamp into the lamp holder by lining up the pins on 

the lamp base to the socket of the lamp holder and turning the lamp body clockwise until 
the lamp snaps into place and is firmly seated in the lamp holder. Install a 4 watt maximum 
type C7 (candelabra base) night light (not included) into the side lamp holder 

(Figure 10).

 

5.  Install the reflector onto the grill by placing the slots on the side of the reflector over the 

lens clips near the center of the grill. While squeezing the middle of the reflector, slide it so 
that the plastic notches rest under the lens clips and the reflector feels secure 

(Figure 11).

6.  Install the grill (with reflector) by squeezing the two ends of the springs together and installing 

them up into the slots on the fan’s housing. Push the grill up into position 

(Figure 12).

7.  Restore power and test your installation.

Figure 12

Figure 10

Lamp

Lamp Holder

Pin

Night Light

Socket

Slot

Clip

Figure 11

Figure 7

Screw

Wire Compartment 

Cover

Humidity Set 

Point Knob

Figure 8

Supply from 

house

White

Ground

Hot (Yellow)

Hot 

(Red)

Hot 

(Black)

Hot (Purple)

Figure 9

Содержание AKF100H

Страница 1: ...applicable codes and standards including fire related construction b Sufficient air is needed for proper combustion and exhausting of gases through the flue chimney of fuel burning equipment to preven...

Страница 2: ...ies Install the rails on the housing and position the housing in the previously cut hole so that it is flush with the finished ceiling Secure the ends of the rails to the joists Figure 2 www airkingli...

Страница 3: ...nstallation to prevent air leakage from unconditioned spaces is recommended If gaps between unit housing and ceiling are great additional material backing rod ceiling material may be required NOTE Thi...

Страница 4: ...e grill and locate the dehumidistat dial located on the wire compartment cover 2 Set the dial to the relative humidity you want the fan to maintain usually between 50 80 Moist climates will require hi...

Страница 5: ...KING S LIABILITY UNDER ANY EXPRESS OR IMPLIED WARRANTY INCLUDE I INCIDENTAL OR CONSEQUENTIAL DAMAGES FROM ANY CAUSE WHATSOEVER OR II REPLACMENT OR REPAIR OF ANY HOUSE FUSES CIRCUIT BREAKERS OR RECEPTA...

Страница 6: ...or Cap Harness AKF80H 5S9202502 1 Motor Cap Harness AKF100H 5S9202505 5 1 Motor Harness 5S1202051 6 1 Wire Compartment Assembly 5S1202808 7 1 Blower Assembly 5S2202029 Qty Description Replacement Part...

Страница 7: ...ion relative aux incendies b De l air en quantit suffisante est requis pour la bonne combustion et l vacuation de gaz par le conduit chemin e provenant d quipement de br lage au combustible pour pr ve...

Страница 8: ...utilit s Installer les traverses sur le ch ssis et positionner le ch ssis dans le trou perc pr c demment afin qu il soit effleurement avec le plafond fini Fixer les extr mit s des traverses aux soliv...

Страница 9: ...c la vis qui fut enlev e pr c demment SECTION 6 Compl tion de l installation 1 Il est recommand d utiliser un scellant appropri pour le contact avec les mat riaux de construction actuels et pour les b...

Страница 10: ...TION EST COUP E AU PANNEAU DE SERVICE AVANT DE COMMENCER L INSTALLATION 1 Pour r gler le niveau d sir d humidit de la salle enlevez la grille et localisez le cadran de l humidostat situ sur le couverc...

Страница 11: ...E OU TACITE POUR I DES DOMMAGES ACCIDENTELS OU INDIRECTS DE N IMPORTE QUELLE CAUSE OU II LE REPLACEMENT OU LA R PARATION DE TOUS FUSIBLES DISJONCTEURS OU R CEPTACLES DE MAISON MALGR N IMPORTE QUOI L E...

Страница 12: ...0H 5S9202502 1 Harnais du Capuchon du Moteur AKF100H 5S9202505 5 1 Harnais du Moteur 5S1202051 6 1 Assembl e du compartiment du fil 5S1202808 7 1 Assemblement de ventilateur 5S2202029 de pi ce Qte Des...

Отзывы: