Air King AKEV Series Скачать руководство пользователя страница 4

www.airkinglimited.com

6728104 Rev. B 5-20

4 of 8

SECTION 9

Adjusting Fan Speed for Balancing and Capacity Requirements

For high-speed adjustment/balancing, use any means to initiate high speed (e.g. ES-M1, R—Hi 

jumper wire, or engage 24V R—Hi control), then:
1.  Press and hold either the FRESH air or 

EXHAUST air push buttons (not both) for 3 

Seconds to initiate SPEED ADJUST MODE.

2.  Press the corresponding button to adjust 

the fresh air fan or the exhaust fan speed, 

thereby changing the air flow. Each press 

reduces motor speed until the default 

minimum is reached, at which point 

the motor will return to its peak speed. 

Allowing a brief pause between presses 

(about 0.5 seconds), you will press the 

adjust button about 70 times before 

reaching minimum speed. During the balancing procedure, you can switch between 

adjusting the fresh air motor or exhaust air motor.

3.  To exit balancing/speed adjust mode, stop pressing buttons for 10 seconds. This will place 

the unit back in operating mode with the new speeds saved to the circuit board’s memory.

Low-Speed Adjustment/Balancing. If low speed adjustment is desired, use a jumper wire (R—

Lo) or remote control to put the unit into low speed and follow steps 1-3.

SECTION 10

Installing the Wall Control

Your unit includes a model RVC8 wall control. Your unit can also accommodate other 24 VAC 

controls and can be connected in Series or Parallel.

CAUTION: 

IF INSTALLING OTHER 24 VAC CONTROLS FOLLOW 

ALL INSTRUCTIONS INCLUDED WITH THE CONTROL AS WELL AS ANY 

LOCAL OR NATIONAL CODES THAT MAY APPLY.

CAUTION: 

FOR UNITS WITHOUT A RECIRCULATION DAMPER, TURN OFF 

RECIRCULATION FUNCTIONS IN CUSTOM SETTINGS. 

WARNING: 

ROUTE CONTROL WIRING ACCORDING TO LOCAL 

BUILDING CODES.

Mounting the Control

1.  Mount in a central location within the building. 
2.  Fits a standard 2" x 3" (nominal) electrical wall box (not 

included). While your wall control comes with a screwless face 

plate, you can substitute it with another to match any décor by 

using a flat screwdriver to pry off the original face plate and by 

removing the 5 mm screws securing the faceplate base.

3.  Drywall anchors may be used where a wall box is not available.

Wiring

1.  Using a 3 mm flat head screwdriver, connect 4-conductor wire 

to the 12 VDC (4-wire) removable terminal block provided. 

Wiring the controls involves simply matching 

terminals on the control to those of the ERV/HRV 

terminal block (see right).

WARNING: 

DO NOT 

CROSS THE +12V/12 AND GROUND 

(GND/G) WIRES. FOR RVC8 CONTROLS, DOING SO 

WITH POWER CONNECTED TO THE ERV/HRV MIGHT 

DAMAGE THE WALL CONTROL PROCESSOR.

USING THE CONTROLLER
Backlight

Press any key to turn on the backlight. The backlight will remain 

illuminated for 10 seconds after the last button is pushed. 

Power

Use this key as a quick means to turn the ventilator off. 

Mode

Use this button to enter the mode selection menu and to activate 

a chosen mode of operation.

Timer

Use this button to activate the ventilator into high speed for 20, 

40 or 60 minutes. The timer button can also be used to turn off 

the high speed timer function. 

Down Arrow

Use this button to decrease desired humidity setting, or to scroll through menu options. 

Up Arrow

Use this button to increase desired humidity setting, or to scroll through menu options.

Fresh air 

adjust button

Exhaust air 

adjust button

SELECTING A MODE OF OPERATION

Press the mode button and you will see that the current mode icon 

and mode number (00-06) will flash. Use the arrow buttons to scroll 

up and down the numbered menu choices. To initiate a desired 

mode, press the mode button once more, or, after 4 seconds of no button activity, the control 

will automatically activate the last mode option displayed.

CHOOSING A HUMIDITY SETTING

Press the up or down arrow key until the present humidity setting 

and % symbol are flashing. Use the up/down arrow buttons to adjust 

humidity setting in 5% increments. After 4 seconds of no button activity, presently selected 

humidity setting will be programmed. The current ambient humidity will then be displayed.
When ambient humidity exceeds the chosen setpoint a water drop icon will appear and the 

ventilator will operate in high speed until the humidity level drops below setpoint. Available 

humidity setting range: 20-80%.
In cases where humidity control is not desired or practical, use the arrow keys to toggle the 

humidity “setpoint” to one click above 80% or one click below 20%. Also use arrow keys to 

reactivate humidity control. 

NOTE:

 Generally, a humidity setting of 40-60% is desired. While your ventilator is not a 

dehumidifier, ventilation can have the effect of reducing indoor humidity when exchanging 

moisture-laden air from the interior space with less humid, fresh air from outside.

OPERATION MODES

OFF:

 Ventilator is off, but the control itself is on and will display ambient 

humidity level. 

STANDBY:

 Ventilator is idle. During this mode, a static pause icon will display. 

During standby mode the ventilator will temporarily switch to high speed on 

demand from the lumina humidity sensor or a timer. 

LOW SPEED:

 Ventilator runs in low speed continuously. During this mode, an 

animated 3-blade fan will display. During low speed mode the ventilator will 

temporarily switch to high speed on demand from the lumina humidity sensor 

or a timer. 

HIGH SPEED:

 Ventilator runs in high speed continuously. During this mode, 

an animated 6-blade fan will display. Ventilator will remain in high speed on 

demand from the lumina humidity sensor or a timer and continue in high speed 

after the humidity/timer demand is met. 

20 LO/40 STANDBY:

 Ventilator cycles continuously between 20 minutes of low 

speed operation and 40 minutes of standby operation. During low speed cycle, 

the fan 3-blade fan icon will animate and the pause symbol will flash twice 

every 5 seconds. During the standby cycle, the pause icon will be static and 

the fan icon will flash twice every 5 seconds. During 20 lo/40 standby mode the ventilator will 

temporarily switch to high speed on demand from the lumina humidity sensor or a timer.

RECIRCULATION MODES

RECIRCULATION:

 Ventilator continuously recirculates air within the home and 

does not bring in air from outside, i.E. Air exchange does not occur. During this 

mode an animated cycling arrow will display. During recirculation mode the 

ventilator will temporarily switch to high speed on demand from the humidity 

sensor or an external timer. 

20 LO/40 RECIRCULATION:

 Ventilator cycles continuously between 20 minutes 

of low speed operation and 40 minutes of recirculation operation. During the low 

speed cycle, the fan will animate and the recirculation ring will flash twice every 

5 seconds. During the recirculation cycle, the recirculation arrow will animate and 

the fan icon will flash twice every 5 seconds. During 20 lo/40 recirculation mode the ventilator 

will temporarily switch to high speed on demand from the lumina humidity sensor or a timer.

USING THE HIGH SPEED TIMER

For timed high speed operation, press the hourglass button once for 20 

minutes, twice for 40 minutes, or three times for 60 minutes. Hourglass 

icons will appear from left to right at the bottom right of the LCD display 

and a high speed fan icon will appear on the screen. After 3 seconds of 

no button activity the high speed cycle will begin. As each 20 minute cycle 

expires, one hourglass icon will disappear from right to left. You can manually turn off the timer 

cycle by pressing the hour glass button until all the hourglass icons disappear.

If you would like to view or change modes during a high speed call, simply use the mode and 

arrow keys and the chosen mode will resume/commence after the timer cycle has expired.

NOTE:

 Additional timers are compatible with your control, however, the control will not indicate 

that these external timers are active (i.E. It will continue to display present mode of operation 

only). You can change the desired mode of operation during a timer cycle; it will commence after 

the timer cycle has expired.

MAINTENANCE INDICATOR/RESETTING MAINTENANCE CLOCK

Your control has a maintenance run clock (it only counts time when the 

ventilator is turned on). Factory default for the maintenance clock is 3 

months, at which time a wrench icon will appear in the upper right of 

the LCD screen and a yellow led will light. This indicates that it is time to 

check your ventilator to see if it needs cleaning and to see if your filters 

00

01

02

03

05

04

20/40

06

20/40

55%

02

40%

TERMINAL 

BLOCK

CONTROL

G

GND

A

A BUS

B

B BUS

12

+12V

20/40

55%

Содержание AKEV Series

Страница 1: ...perature falls below 32 F i This unit must be grounded The power cord is equipped with a three prong grounded plug that must be inserted into a matching receptacle Under no circumstances should the gr...

Страница 2: ...used to transfer stale air from the wet rooms to the ERV HRV 2 Extended System Continuous Ventilation The furnace fan may not need to run continuously with this system Check local code requirements Fo...

Страница 3: ...ITH METHODS OF INSTALLING ELECTRICAL WIRING SECURE THE SERVICES OF A QUALIFIED ELECTRICIAN For simplified return return duct systems it is mandatory that the unit be interlocked with the furnace blowe...

Страница 4: ...ed until the humidity level drops below setpoint Available humidity setting range 20 80 In cases where humidity control is not desired or practical use the arrow keys to toggle the humidity setpoint t...

Страница 5: ...peed in the ventilator The unit will run in high speed until the ambient air returns to the setpoint RH Your ventilator is not a dehumidifier however ventilating can have a dehumidifying effect by sim...

Страница 6: ...re present Install back draft dampers as needed Check defrost system Note minimal frost build up is expected on cores before unit initiates defrost cycle function The supply air feels cool ERV HRV air...

Страница 7: ...NTY INCLUDE I INCIDENTAL OR CONSEQUENTIAL DAMAGES FROM ANY CAUSE WHATSOEVER OR II REPLACEMENT OR REPAIR OF ANY HOUSE FUSES CIRCUIT BREAKERS OR RECEPTACLES NOTWITHSTANDING ANYTHING TO THE CONTRARY IN N...

Страница 8: ...Latch 5S7759004 8 2 Keeper 5S7759005 9 1 Door Switch 5S7760006 10 1 Core 5S7759006 11 1 Door Assembly 5S7759007 12 1 Fuse Holder 5S7760002 13 1 Fuse 2 5 amp 5S7760003 14 1 Transformer 5S7759001 15 2 C...

Отзывы: