WIRING DIAGRAM:

IS-SS-RA-R

IS-CCU

IS-MV

IS-PU-UL

N/O Dry Contact 

24V AC/DC 500mA

CAT-5e

CAT-5e

NO

COM

NC

FCC WARNING:

This device complies with Part 15 of the FCC rules.

Operation is subject to the following two conditions:

(1)  This device may not cause harmful interference.

(2)  This device must accept any interference that may cause undesired operation.

• 

For proper regulatory compliance, the drain wire should be disconnected at the power 

supply end of the cable.

• 

Changes or modifications not expressly approved by the party responsible for 

compliance could void the user’s authority to operate the equipment.

TOLL FREE TECHNICAL SUPPORT:

(800) 692-0200

E-MAIL: [email protected]

SPECIFICATIONS:

Terminations:   

RJ45 jack for audio

 

 

 

Screw terminals for door release and relay outputs

Relay rating:   

24V AC/DC 500mA on Door station, 24V AC/DC 1.0A on relay board

Operating Temp: 

14° ~ 140°F / -10° ~ 60°C

Wiring Distance: 

980’ with Cat-5e/6 cable

Dimensions:   

11-3/4” H x 7” W

w/SBX-ISDVFRA: 

11-11/16” H x 7-1/16” W x 2-13/16” D (top), 1-13/16” D (bottom)

OFF ON

NO

NO

C

NC

C

NC

1234

OFF ON

NO

NO

C

NC

C

NC

1234

Board on back of unit

See wiring below

RELAY BOARD WIRING AND SETTINGS:

Relay 1 Output

N/O, COM, N/C

Relay 2 Output

N/O, COM, N/C

**Relay 2 External Reset

Connect to N/O dry switch

Configuration Switch 

See Settings to right

ON

1
2
3
4

Default Configuration when shipped

Optional Configuration

Normal Call
Emergency Call
Talking
Door Release

Trigger Source

RY1 Triggered?

RY1 Remains ON 

During Talking?

RY2 Triggered?

RY2 Remains ON 

During Talking?

RY2 Requires 

Reset?

YES

NO

N/A

YES
YES

YES

YES

YES

NO

NO

NO
NO

N/A

N/A
N/A

N/A

N/A
N/A

YES

YES

ON

1
2
3
4

Contact Technical Support if additional switch configurations 

are required.  

Relay 1 triggers on normal call, emergency call, and communication. Relay 1 remains on during communication.  

Relay 2 triggers on emergency call and remains on during communication.

Relay 1 triggers on normal call, emergency call, and communication. Relay 1 remains on during communication.  

Relay 2 triggers on an emergency call and remains on during communication.  Relay 2 requires reset.

Normal Call
Emergency Call
Talking
Door Release

Trigger Source

RY1 Triggered?

RY1 Remains ON 

During Talking?

RY2 Triggered?

RY2 Remains ON 

During Talking?

RY2 Requires 

Reset?

YES

NO

N/A

YES

NO

N/A

N/A

N/A

YES

YES
YES
YES

YES

YES

N/A

N/A
N/A

NO
NO

YES

**

* IS-SS-RA-R can connect to any 

control unit (IS-CCU, IS-SCU, IS-RCU)

Station must be programmed as an 

audio only station.

*

2-pin connector