9
Operating Procedure
A.
Verify the battery operating Voltage And protection switch is on (inverter off)
B.
Turn protection switch #1 “off” (circuit breaker) once the battery connection has been verified.
C.
Turn protection switch #3 “off”. If the buzzer is sounding, turn the connected AC devices off and toggle the power switch off then on. The
buzzer should stop.
D.
Connect the battery cable to terminal #1 (+ is Red, - is Black, refer to figure #1). The length of the cable may vary slightly, but should
preferably be less than 10 Ft. The shorter the length of the cable the better the batteries will perform. If a longer distance is needed, a larger
gauge cable is required.
E.
Connect the Red cable lug to the po on the battery and Black lug to the negative – of the battery. Arrange the battery cables to the
safest angles.
F.
Now you should connect and turn the AC devices on. Most equipment using motors, have a higher startup requirement. This may cause the
inverter to buzz and go into overload or pop the circuit breakers. This should not damage the inverter; however you should not continue to try
and power up the equipment. Repeated overloads will cause damage to the inverter Call AIMS Power Tech support and verify startup
requirements.
G.
The frequency of the inverter is fine-tuned at 60Hz from the manufacture. You may however find it convenient and necessary to adjust it
using switch #10 to 50Hz.
H.
The inverter may operate in overload for a short period of time. If you continue the use in overload, the inverter may overheat and shut down.
You will then be required to turn the inverter off and on again.