MODEL (Ei105R4)

Supply Voltage:

8.0 to 16.0 Volts

Standby Current: 250 Microamps (max)
Alarm Current:

20 to 60 mA

Cable:

Multicore low voltage signal cable.
Maximum resistance 20 ohms

Power-On
Indicator:

LED flashes every 40 seconds

Alarm:

Electronic Piezoelectric horn in unit
85dB @3M

Alarm Sound
Output:

85dB(A) (minimum) at 3m

Alarm Status:

LED flashes every second on unit
sensing fire

Temperature
Range:

4 to 40°C (39 to 104°F)

Humidity Range:

0% to 90% Relative Humidity.

Relay Contacts:

24 Volts/1 Amp (resistive), normally closed
and normally open.

Interconnect:

Up to 12 Ei100R3 / 105R3 / 105R4 / 103R
only can be interconnected. Max cable 
resistance 20 ohms. LED flashes every 
second to identify the unit sensing fire. (I/O
line can supply 3.5 volts at 4 mA)

Dimensions:

(Ei100R3) 140 x 125 x 46 mm
(Ei105R3) 140 x 125 x 46 mm
(Ei105R4) 140 x 125 x 46 mm
(Ei103R)   140 x 125 x 58 mm

Weight:

170 grams (6 oz)

Specifications are subject to change

TROUBLESHOOTING

ALARM SOUNDS FOR NO APPARENT REASON:

(1) Identify the alarm source. On all interconnected units, the

red light under the test button or on the cover will flash
rapidily only on the unit which is the source of the alarm.

(2) Check for fumes, steam etc. from the kitchen or bathroom.

Paint and other fumes can cause nuisance alarms.

(3) Fan the unit vigorously with a newspaper to disperse

fumes.

(4) If alarm does not stop, disconnect the 12V supply.

INTERCONNECTED ALARM DO NOT ALL SOUND:

(1) Hold test button for 10 seconds after first alarm has

sounded to ensure signal is transmitted to all units.

(2) Check that cables have been correctly connected and that

the connections are tight.

15

13425-R1-12V COMMON-UC  29/9/09  7:56 AM  Page 15

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание Ei100R

Страница 1: ...ALARM UNTIL ALL BUILDING WORK IS COMPLETED TO AVOID CONTAMINATION AFTER CHECKING OPERATION COVER SMOKE ALARM WITH DUST COVER UNTIL REQUIRED FOR USE LOCATE IONISATION ALARMS Ei100R3 AWAY FROM KITCHENS...

Страница 2: ...g is given For maximum protection you should put individual Smoke Alarms in all the rooms where fire is most likely to break out apart from kitchens bathrooms garages see Locations to Avoid A Smoke Al...

Страница 3: ...out from a room is often cool and slow moving so it can take a long time to rise to the ceiling and travel to a detector which could be some distance away A Heat Alarm in the closed room will give ea...

Страница 4: ...ot be sufficient This is because no matter where it is located it will be more than 7 5 metres from potential fires In houses with more than one sleeping area Smoke Alarms should be placed between eac...

Страница 5: ...re that it wouldn t wake a person If a Smoke Alarm is too far away for it to wake a person it is best to interconnect it to another Smoke Alarm or Heat Alarm near the bedroom The following alarms Ei10...

Страница 6: ...detector chamber can cause intermittent alarms Insects and contamination on the Heat Alarm sensor can increase its response time POSITIONING SMOKE HEAT ALARMS The location must comply with applicable...

Страница 7: ...when appropriate Excessive dust and debris from building work can contaminate the smoke chamber and cause problems it will also invalidate the guarantee If it must be installed cover it completely pa...

Страница 8: ...arms and Heat Alarms When a fire is sensed the alarm must be given throughout the house Up to twelve 12 Smoke Alarms models Ei100R3 Ei105R3 Ei105R4 only and Heat Alarms model Ei103R only can be interc...

Страница 9: ...every second while horn is sounding The alarm will stop when the button is released Pressing the test button simulates the effect of smoke heat during a real fire and is the best way to ensure the Al...

Страница 10: ...the Ei100R3 Ionisation alarm due to cooking fumes you could consider replacing it with an Optical Alarm Ei105R3 or Ei105R4 as they are significantly less susceptible to cooking fumes If you experienc...

Страница 11: ...e not a substitute for insurance The supplier or manufacturer is not your insurer The chamber inside the Ionisation Ei100R3 Smoke Alarm contains a small amount of radioactive material 33kBq of Americi...

Страница 12: ...Smoke Heat Alarms have significantly helped to reduce the number of fire fatalities in countries where they are widely installed However independent authorities have stated that they may be ineffecti...

Страница 13: ...Alarm Optical or Ion Both types respond in all standard fires but each type may respond faster to particular fires as shown The EI company manufactures complementary 12 Volt Smoke Alarms Optical Smoke...

Страница 14: ...Am241 Airspeed No false alarms up to 22mph 10M s Button Test Simulates the effect of smoke and checks chamber electronics and horn Ei105R3 Ei105R4 Sensor Optical uses light scatter from smoke Sensitiv...

Страница 15: ...i100R3 140 x 125 x 46 mm Ei105R3 140 x 125 x 46 mm Ei105R4 140 x 125 x 46 mm Ei103R 140 x 125 x 58 mm Weight 170 grams 6 oz Specifications are subject to change TROUBLESHOOTING ALARM SOUNDS FOR NO APP...

Отзывы: