![AHRI RJNL-B Скачать руководство пользователя страница 3](http://html1.mh-extra.com/html/ahri/rjnl-b/rjnl-b_installation-instructions-manual_2870559003.webp)
3
The units are weatherized for mounting outside of the building.
The information on the rating plate is in compliance with the
FTC and DOE rating for single phase units. The following infor-
mation is for three phase units which
are not
covered under
the DOE certification program.
1. The efficiency rating of this unit is a product thermal effi-
ciency rating determined under continuous operating condi-
tions independent of any installed system.
B. MAJOR COMPONENTS
The unit includes a hermetically-sealed refrigerating system
(consisting of a compressor, condenser coil, evaporator coil
biflow thermal expansion valve, reversing valve), a circulation
air blower, a condenser fan, and all necessary internal electri-
cal wiring. The cooling system of these units is factory-evacu-
ated, charged and performance tested. Refrigerant amount
and type are indicated on rating plate.
C. R-410A REFRIGERANT
All units are factory charged with R-410A refrigerant.
1. Specification of R-410A:
Application: R-410A is not a drop-in replacement for R-22;
equipment designs must accommodate its higher pressures. It
cannot be retrofitted into R-22 units.
Pressure: The pressure of R-410A is approximately 60%
(1.6 times) greater than R-22.
Recovery and recycle equip-
ment, pumps, hoses and the like need to have design pressure
ratings appropriate for R-410A.
Manifold sets need to range
up to 800 psig high-side and 250 psig low-side with a 550 psig
low-side retard. Hoses need to have a service pressure rating
of 800 psig. Recovery cylinders need to have a 400 psig ser-
vice pressure rating.
DOT 4BA400 or DOT BW400.
Combustibility:
At pressures above 1 atmosphere, mixture of
R-410A and air can become combustible.
R-410A and air
should never be mixed in tanks or supply lines, or be
allowed to accumulate in storage tanks. Leak checking
should never be done with a mixture of R-410A and air.
Leak checking can be performed safely with nitrogen or a mix-
ture of R-410A and nitrogen.
2. Quick Reference Guide For R-410A
• R-410A refrigerant operates at approximately 60% higher
pressure (1.6 times) than R-22. Ensure that servicing equip-
ment is designed to operate with R-410A.
• R-410A refrigerant cylinders are pink.
• R-410A, as with other HFC’s is only compatible with POE
oils.
• Vacuum pumps will not remove moisture from POE oil.
• R-410A systems are to be charged with liquid refrigerants.
Prior to March 1999, R-410A refrigerant cylinders had a dip
tube. These cylinders should be kept upright for equipment
charging. Post March 1999 cylinders do not have a dip tube
and should be inverted to ensure liquid charging of the
equipment.
• Do not install a suction line filter drier in the liquid line.
• A liquid line filter drier is standard on every unit.
• Desiccant (drying agent) must be compatible for POE oils
and R-410A.
3. Thermostatic Expansion Valve (TXV)
The Bi-Flow TXV is specifically designed to operate with R-
410A heat pumps.
Replacement of the TXV should only be
made with the factory specified bi-flow R-410A valve. Do
not use an R-22 TXV.
4. Tools Required For Installing & Servicing R-410A Models
Manifold Sets:
-Up to 800 PSIG High side
-Up to 250 PSIG Low Side
-550 PSIG Low Side Retard
Manifold Hoses:
-Service Pressure Rating of 800 PSIG
Recovery Cylinders:
-400 PSIG Pressure Rating
-Dept. of Transportation 4BA400 or BW400
R-410A systems operate at higher pressures than R-22 sys-
tems. Do not use R-22 service equipment or components on
R-410A equipment.
CAUTION
!
Содержание RJNL-B
Страница 5: ...5 ST A1132 04 ST A1132 05 FIGURE 3 UNIT DIMENSIONS FIGURE 4 UNIT DIMENSIONS FRONT VIEW ...
Страница 6: ...6 ST A1132 06 ST A1132 07 FIGURE 5 BOTTOM VIEW FIGURE 6 REAR VIEW SUPPLY AIR RETURN AIR ...
Страница 18: ...18 Model RJNL B090 C090 ...
Страница 19: ...19 ...
Страница 27: ...27 FIGURE 18 JNL SERIES 7 5 10 TON ...
Страница 28: ...28 FIGURE 19 JNL SERIES 7 5 10 TON ...
Страница 29: ...29 FIGURE 20 JNL SERIES 7 5 10 TON ...
Страница 30: ...30 FIGURE 21 JNL SERIES 7 5 10 TON ...