OPERATION 

   First Power Up 

 

On connecting power, the detector enters ‘sensor stabilisation’ phase for approximately 60 

seconds – during this period the screen will display an ‘initialisation’ message 
indicating that the device is not yet ready for gas detection. 

 
When the sensor has stabilised – the screen will display; 
 

a.

 

the relevant gas type intended to be detected 

b.

 

detected gas level in the area 

c.

 

the measurement value  

d.

 

the detector unique serial number 

e.

 

the detector ID number 

 
 

   

Gas Level Indicators 

 

 
 
 
 
 
 
 

 

   

End of Life Indicator 

 

This message indicates that the detector has reached its expected operational lifecycle.  
No gas levels will be displayed. Contact your supplier and replace the unit immediately. 

 

SAFE 

Safe gas levels will be 

displayed GREEN.

 

ATTENTION! 

Low gas levels will be 

displayed YELLOW. 

DANGER! 

Dangerous gas levels 

will be displayed RED. 

 

The expected lifecycle will depend on the type of gas your detector is 

targeting and may vary depending on environmental conditions. 

 

At dangerous gas levels, the alarm will continuously sound if the buzzer dip-switch is ON. 

There are no provisions to silence this alarm.  

Only when gas levels are at a safe level will the audible alarm stop. 

 

Содержание Merlin TFT

Страница 1: ...merican Gas Safety we supply a full range of remote gas detectors including carbon monoxide CO natural gas NG and liquid petroleum gas LPG that are compatible with our range of Merlin panels The infor...

Страница 2: ...5 Wiring the Detector 5 Merlin X Systems 5 Merlin S Systems 7 Merlin GDP Systems 7 X Chain ID Switches 8 Audible Alarm Switch 8 Factory Set Condition 8 Trouble Shooting 9 Specification 9 OPERATION 10...

Страница 3: ...for detectors will vary based on the intended application and target gas they should be located near identified sources of a potential gas leaks pockets where hazardous gas could quickly accumulate a...

Страница 4: ...ully remove the rear cover from the unit by releasing the two latching clips located at the bottom of the case To do this use a small flat head screwdriver 2 Using the rear cover mark the screw holes...

Страница 5: ...verview Wiring the Detector Merlin X Systems 12 24V Power and data supply via DETECTOR X CHAIN terminal and Merlin GDP X range terminal DETECTOR CHAIN Detectors can be wired in any configuration IN OU...

Страница 6: ...ain System Typical Wiring Example Chain System Termination Switches 120ohm Chain Termination Resistor Switch Signal communication issues may occur where the bus length is too long or high baud rates a...

Страница 7: ...en in alarm or when gas is detected BMS terminals can be used in conjunction with other external relays that affect other devices and controls such as purge fans and audible alarms etc Merlin GDP Syst...

Страница 8: ...ck reference For more information refer to your GDP X manual Audible Alarm Switch There is a switch on the detector TFT board Buzzer On Off The user can choose whether to have an audible alarm when da...

Страница 9: ...TFT Thin Film Transistor Screen Brightness Non adjustable Initial Stabilisation Time 60 Seconds approx Power Input Voltage 12 24V 7 30VDC Relay Output 0 5A Switching Current resistive load Consumptio...

Страница 10: ...ber e the detector ID number Gas Level Indicators End of Life Indicator This message indicates that the detector has reached its expected operational lifecycle No gas levels will be displayed Contact...

Страница 11: ...sic principles DO carefully remove any accumulated dust from the outer enclosure once a month NEVER use detergents or solvents to clean your device this may permenantly or temporarily damage the gas s...

Страница 12: ...working safely If the bump test results are not within the acceptable range the gas detector must not be used until a full calibration has been conducted Bump testing has a number of benefits for the...

Страница 13: ...H One Year Warranty O2 Warranty coverage The manufacturer warrants to the original consumer purchaser that this product will be free of defects in material and workmanship for a period of three 3 yea...

Страница 14: ...Installation Operation Manual Merlin Gas Detector TFT AGSDETTFT IOM Iss 5 06 20 14 NOTES...

Страница 15: ...Installation Operation Manual Merlin Gas Detector TFT AGSDETTFT IOM Iss 5 06 20 15 NOTES...

Страница 16: ...o the system owner user Date of Installation Installation Location Organisation Stamp Signature of the installer Replacement Date CONTACT US AGS Head Office Tel 727 608 4375 Fax 727 538 4237 info amer...

Отзывы: