Installation, Operation & Maintenance Manual                                                                  CO2-TFT

 

 

 

Rev 3   11-20 

8  

   Configuration Settings  

 

There is a settings switch on the CO2-TFT board.  
Switch it on to prompt the on-screen menu.  

Navigate the menu using the buttons on the board.  
When changes have been made – turn the settings switch off. 
 

[SEL.] button 

 

Scroll through functions (highlighted red). 

 

Change the desired setting when highlighted. 

[OK] button 

 

Highlights setting (red). 

 

Press to save desired setting.

 

 

 

   Menu Overview 

 

VENT. TYPE

 

 

 

 NAT. (Natural mode) – Recommended for buildings without mechanical ventilation. 

 

 MECH. (Mechanical mode) – Recommended for buildings with mechanical ventilation. 

 

 KITCH. (Kitchen mode) – Recommended for kitchen environments. 

 

MIN 0-10 OUT

 

1 & 2

 

Minimum voltage output from the 0-10V Analogue out 1 & 2 terminals.

 

 
0-10V OUT

 

1 & 2 

0-10V output can be driven by current CO

ppm

 

level only, by current temperature only or by the status of 

both – whichever is the greatest.  
 
BUZZER 
The buzzer will operate as selected in KITCHEN ventilation type only. You can select the buzzer to beep 
three times every 15 seconds, every 10 minutes or not at all when the alarm status is reached. 
 
TEMP. UNITS 
Select between measuring the temperature in degrees °Celsius or °Fahrenheit.  
 
BOOST (MIN

.) 

Analogue outputs will run at optimum capacity (10V) for time specified.  
Select from 1 – 10 minutes. Outputs return to normal after the specified boost time.  
 
FAN ENABLE 
This relay will switch on a fan from the current CO

level only, by current temperature only or by the status 

of both – whichever is the greatest. 
 
BRIGHTNESS  
There are three (3) levels of screen backlight brightness: LOW, MED and HIGH. 
 
SCREEN SAVER 
If ON is selected, the display will remain off and wake up at pre-alarm/ alarm status. To wake up the 
screen for ten seconds press the touch button. If OFF is selected the display will remain on. 
 
FACTORY RESET 

 

Restores all settings to factory set condition. 

 

Содержание MERLIN CO2-TFT

Страница 1: ...itch between ventilation programs when gas is used Boost Mute and Wake Up button Installation Operation Maintenance Manual Please read this manual carefully and retain for future use The Merlin CO2 TF...

Страница 2: ...om date of purchase The manufacturer s liability hereunder is limited to replacement of the product with repaired product at the discretion of the manufacture This warranty is void if the product has...

Страница 3: ...rview 5 Wiring your CO2 TFT 6 Configuration Settings 8 Menu Overview 8 Optional Configurations 9 Factory Set Condition 10 Specification 10 OPERATION 11 First Power Up 11 Traffic Light Indicator 12 Ala...

Страница 4: ...ede the accuracy and operation of the detectors such as condensation vibration extreme temperatures pressure presence of other gases electromagnetic interference and draft zones Take in to account the...

Страница 5: ...or cable entry provided on the inside of the rear cover which may be cut away as required 4 After executing the mounting and the connections replace the rear cover ensuring the two clips are latched 5...

Страница 6: ...l or Mechanical ventilation mode see settings for ventilation types When gas is supplied in use the CO2 TFT will receive a signal from the gas valve and display the GAS IN USE message The CO2 TFT will...

Страница 7: ...0ppm 73 4 F 23 C N O 550ppm 71 6 F 22 C These levels cannot be altered 0 10V ANALOGUE OUT 1 OUTPUT 2 These connections are used to regulate external fan speed controllers supplied separately Connect d...

Страница 8: ...current temperature only or by the status of both whichever is the greatest BUZZER The buzzer will operate as selected in KITCHEN ventilation type only You can select the buzzer to beep three times ev...

Страница 9: ...put Linear Progression o Min output 1 5V from 600ppm 23 C 73 4 F o Max output 10V from 2800ppm 27 C 80 6 F Boost from 400 2799ppm 0 C 32 F 26 9 C 80 4 F Buzzer alarm Mute from 2800ppm MIN 0 10 OUT 1 A...

Страница 10: ...2 16VA without load or 12 24V AC or DC 25V AC DC Max Gas Valve Input 100 120V AC CO2 Pre Alarm Relay Output Max 0 5A Signal CO2 Alarm Relay Max 3A 120V Fan Enable Relay Output Max 0 5A Signal Consumpt...

Страница 11: ...utton f is pressed The audible alarm buzzer must be set to on or every 10 minutes and can only occur when gas is in use or KITCH Ventilation mode is selected and when CO2 levels rise above 2800ppm f T...

Страница 12: ...echanical Ventilation Mode Green 800ppm 23 C 73 4 F Yellow 800ppm 23 C 73 4 F Red 1000ppm 25 C 77 0 F CO2 Pre alarm relay switch 800ppm CO2 Alarm relay switch 1000ppm 0 10V Analogue Output Progression...

Страница 13: ...xit screen the saver mode when either the CO2 or Temperature changes status yellow or red To view the screen during this mode press the touch button the screen will be visible for 10 seconds End of Li...

Страница 14: ...ackground CO2 levels 75ppm For maintenance purposes the device should be exposed to fresh air intermittently to aid with this process Inaccuracies that do not resolve over a 24 hour period may require...

Страница 15: ...Installation Operation Maintenance Manual CO2 TFT Rev 3 11 20 15 Notes blank...

Страница 16: ...of Installation Installation Location Organisation Stamp Signature of the installer Replacement Date American Gas Safety LLC Head office 6304 Benjamin Road Suite 502 Tampa FL 33634 Tel 727 608 4375 in...

Отзывы: