Installation, Operation & Maintenance Manual                                                                  CO2-TFT

 

 

 

Rev 3   11-20 

1  

 

 

MERLIN CO2-TFT 

Carbon Dioxide & Temperature Monitor 

             
 

 

CO

2

 measured and displayed in parts per million (PPM). 

 

Temperature can be displayed in degrees Celsius (°C) or Fahrenheit (°F). 

 

0-10V Signal Output progress bar display. 

 

Monitor, record and display average CO

2

 concentration over 8 hour periods. 

 

User friendly settings menu. 

 

Pre-alarm and alarm relay output. 

 

Fan controller enabled relay output. 

 

Dual power 100-240VAC or 12-24V. 

 

End of Life notification for CO

sensing element. 

 

Automatically switch between ventilation programs when gas is used. 

 

Boost, Mute and Wake Up button. 

 

 

 

 

 



Installation, Operation & Maintenance Manual 

Please read this manual carefully and retain for future use. 

 

The Merlin CO2-TFT is designed to monitor carbon dioxide (CO

2

) in the air and temperature.  

The monitor has a digital traffic light style display indicating the carbon dioxide levels and temperature in 

the area. When CO

2

 gas or temperature reaches alarm state – this device is able to automatically drive 

ventilation fans reducing CO

2

 and/or temperature. 

 
 

 

The information contained within this manual should be referenced for typical installation and operation 
only. For specific requirements that may deviate from the information in this guide – contact your supplier.  

 

Содержание MERLIN CO2-TFT

Страница 1: ...itch between ventilation programs when gas is used Boost Mute and Wake Up button Installation Operation Maintenance Manual Please read this manual carefully and retain for future use The Merlin CO2 TF...

Страница 2: ...om date of purchase The manufacturer s liability hereunder is limited to replacement of the product with repaired product at the discretion of the manufacture This warranty is void if the product has...

Страница 3: ...rview 5 Wiring your CO2 TFT 6 Configuration Settings 8 Menu Overview 8 Optional Configurations 9 Factory Set Condition 10 Specification 10 OPERATION 11 First Power Up 11 Traffic Light Indicator 12 Ala...

Страница 4: ...ede the accuracy and operation of the detectors such as condensation vibration extreme temperatures pressure presence of other gases electromagnetic interference and draft zones Take in to account the...

Страница 5: ...or cable entry provided on the inside of the rear cover which may be cut away as required 4 After executing the mounting and the connections replace the rear cover ensuring the two clips are latched 5...

Страница 6: ...l or Mechanical ventilation mode see settings for ventilation types When gas is supplied in use the CO2 TFT will receive a signal from the gas valve and display the GAS IN USE message The CO2 TFT will...

Страница 7: ...0ppm 73 4 F 23 C N O 550ppm 71 6 F 22 C These levels cannot be altered 0 10V ANALOGUE OUT 1 OUTPUT 2 These connections are used to regulate external fan speed controllers supplied separately Connect d...

Страница 8: ...current temperature only or by the status of both whichever is the greatest BUZZER The buzzer will operate as selected in KITCHEN ventilation type only You can select the buzzer to beep three times ev...

Страница 9: ...put Linear Progression o Min output 1 5V from 600ppm 23 C 73 4 F o Max output 10V from 2800ppm 27 C 80 6 F Boost from 400 2799ppm 0 C 32 F 26 9 C 80 4 F Buzzer alarm Mute from 2800ppm MIN 0 10 OUT 1 A...

Страница 10: ...2 16VA without load or 12 24V AC or DC 25V AC DC Max Gas Valve Input 100 120V AC CO2 Pre Alarm Relay Output Max 0 5A Signal CO2 Alarm Relay Max 3A 120V Fan Enable Relay Output Max 0 5A Signal Consumpt...

Страница 11: ...utton f is pressed The audible alarm buzzer must be set to on or every 10 minutes and can only occur when gas is in use or KITCH Ventilation mode is selected and when CO2 levels rise above 2800ppm f T...

Страница 12: ...echanical Ventilation Mode Green 800ppm 23 C 73 4 F Yellow 800ppm 23 C 73 4 F Red 1000ppm 25 C 77 0 F CO2 Pre alarm relay switch 800ppm CO2 Alarm relay switch 1000ppm 0 10V Analogue Output Progression...

Страница 13: ...xit screen the saver mode when either the CO2 or Temperature changes status yellow or red To view the screen during this mode press the touch button the screen will be visible for 10 seconds End of Li...

Страница 14: ...ackground CO2 levels 75ppm For maintenance purposes the device should be exposed to fresh air intermittently to aid with this process Inaccuracies that do not resolve over a 24 hour period may require...

Страница 15: ...Installation Operation Maintenance Manual CO2 TFT Rev 3 11 20 15 Notes blank...

Страница 16: ...of Installation Installation Location Organisation Stamp Signature of the installer Replacement Date American Gas Safety LLC Head office 6304 Benjamin Road Suite 502 Tampa FL 33634 Tel 727 608 4375 in...

Отзывы: