Installation, Operation & Maintenance                                                                                   Merlin CO2-X

 

 

 

Rev 5   10-21 

4  

Installation 

   Typical Location & Positioning 

 

Consider the coverage required and function of the area. Emphasis should be placed on airflow patterns and correct 
placement, not perceived detecting ranges. The target gas will only be identified when contact is made with the 
sensing element itself. Your monitor should be installed in populated areas that risk high concentrations of CO

2

 gas or 

varied temperatures e.g. educational and government buildings including laboratories and commercial kitchens. 
Take in to account the design of the airflow within the zone area. Avoid conditions such as; condensation; vibration; 
extreme temperatures and draft zones.  Avoid conditions of any other environmental factors that could potentially 
impede the accuracy and operation of the detectors such as; condensation; vibration; extreme temperatures, 
pressure, presence of other gases, electromagnetic interference and draft zones. Avoid positioning near draft areas 
(windows and door entrances). Where possible, monitors must be fixed in such a position as to allow natural air 
circulation. These recommended heights may vary based on airflow and temperature conditions in addition to the 
proposed application and location. 
 
Laboratories/educational buildings: Seated head height 
Commercial kitchens: 
1700mm (5.6ft) from ground level 

 

 

Multiple monitors may be required to adequately protect property and/or persons! 

 

   Access & Mounting 

 

The monitors are designed for surface mounting and must be installed by a licensed, insured contractor or competent 
person. A deeper back enclosure is supplied to accommodate wiring where required. 

 

Carefully remove the rear cover from the unit by releasing the two latching clips located at the bottom of the case. To 
do this – use a small flat head screwdriver. 
Using the rear cover - mark the screw holes to the wall and ensure the wall surface is flat to prevent base distortion. 
There are two pre-fractured areas for cable entry provided on the inside of the rear cover, which may be cut away as 
required.

 

After executing the mounting and the connections – replace the rear cover ensuring the two clips are 

latched. Make a note of the installation date on the label located on the side of the unit. 

 

   Board Overview 

 

Содержание CO2-X

Страница 1: ...cally switch between ventilation programs when gas is used Boost Mute and Wake Up feature Installation Operation Maintenance Please read this manual carefully and retain for future use The Merlin CO2...

Страница 2: ...ounting 4 Board Overview 4 Wiring your CO2 X 5 Configuration Settings 6 Configuration 6 Factory Set Condition 7 Operation 8 Initial Power Up Indicators 8 Traffic Light Indicator 9 Alarms Configuration...

Страница 3: ...d to replacement of the product with repaired product at the discretion of the manufacturer This warranty is void if the product has been damaged by accident unreasonable use neglect tampering or othe...

Страница 4: ...ere possible monitors must be fixed in such a position as to allow natural air circulation These recommended heights may vary based on airflow and temperature conditions in addition to the proposed ap...

Страница 5: ...until the gas supply is turned off see Settings for configuration Recommended for teaching areas with gas appliances such as laboratories and food technology rooms CO2 ALARM Not a mains output This t...

Страница 6: ...setting red Press to save desired setting Configuration NAT Natural Ventilation Mode Recommended for buildings without mechanical ventilation Pre Alarm 1300ppm 23 C 73 4 F Alarm 1500ppm 25 C 77 0 F C...

Страница 7: ...minutes Boost can be activated only if analogue outputs are set to either CO2 or DUAL mode only Select 1 2 3 4 5 6 7 8 9 10 minute s FAN ENABLE Fan switch is energised by CO2 ON 600ppm OFF 550ppm TEMP...

Страница 8: ...rs when the touch button f is pressed The audible alarm buzzer must be set to on or every 10 minutes and can only occur when gas is in use or KITCH Ventilation mode is selected and when CO2 levels ris...

Страница 9: ...Default Green 1500ppm 23 C 73 4 F Yellow 1500ppm 23 C 73 4 F Red 2800ppm 25 C 77 0 F CO2 Pre alarm relay switch 2800ppm CO2 Alarm relay switch 4500ppm 0 10V Analogue Output Progression Min output 1 5V...

Страница 10: ...e device High concentrations of alcohol found in many products may damage deteriorate or affect the gas sensing elements such as wine deodorants stain removers thinners etc Auto Calibration Our CO2 se...

Страница 11: ...mm 5 51 x 3 74 x 1 18 Unit Weight Approx 0 08kg Housing Material Polylac PA765 Environmental Ingress Protection IP40 Storage Conditions Dry Temp 10 50 C 14 122 F 30 80 rh Compliance CE EN 50270 EN 610...

Страница 12: ...this document or their consequences AGS would greatly appreciate being informed of any errors or omissions that may be found in the content of this document For information not covered in this documen...